Bailey Platinum standard Series User manual


WBPEEUI110505A0
Preface
This publication is for the use of technical personnel responsi-
ble for the installation, calibration, operation, maintenance,
and repair of the Type PTSDL Platinum Standard Smart Level
Transmitter.
It is important for safety and operating reasons to read and
understand this instruction. Until doing so, do not install or
complete any tasks or procedures related to calibration, opera-
tion, maintenance, or repair.

WBPEEUI110505A0
List of Effective Pages
Total number of pages in this instruction is 98, consisting of the following:
Page No. Change Date
Preface Original
List of Effective Pages Original
iii through ix Original
1-1 through 1-11 Original
2-1 through 2-11 Original
3-1 through 3-13 Original
4-1 through 4-8 Original
5-1 through 5-8 Original
6-1 through 6-9 Original
7-1 through 7-5 Original
8-1 through 8-12 Original
9-1 through 9-8 Original
Index-1 through Index-4 Original
When an update is received, insert the latest changed pages and dispose of the super-
seded pages.
NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer mar-
gin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in the
outer margin next to the figure caption. The date the update was prepared will appear beside the
page number.

Table of Contents
Page
WBPEEUI110505A0 iii
SECTION 1 - INTRODUCTION....................................................................................................1-1
OVERVIEW ..................................................................................................................1-1
INTENDED USER.........................................................................................................1-1
EQUIPMENT DESCRIPTION.........................................................................................1-1
FEATURES...................................................................................................................1-1
EQUIPMENT APPLICATION..........................................................................................1-3
INSTRUCTION CONTENT .............................................................................................1-3
HOW TO USE THIS INSTRUCTION...............................................................................1-3
REFERENCE DOCUMENTS..........................................................................................1-4
NOMENCLATURE ........................................................................................................1-4
SPECIFICATIONS.........................................................................................................1-7
OPTIONS AND ACCESSORIES ...................................................................................1-10
SECTION 2 - DESCRIPTION AND OPERATION........................................................................2-1
INTRODUCTION...........................................................................................................2-1
FUNCTIONAL OPERATION ...........................................................................................2-1
Cell and Characterization Board Assembly.............................................................2-2
Electronics Assembly .............................................................................................2-3
EZ CAL Option.......................................................................................................2-4
Communications....................................................................................................2-4
Temperature Compensation...................................................................................2-6
Diagnostics............................................................................................................2-6
Software Functions................................................................................................2-7
Spherical Tank Volume Calculation .................................................................2-7
Flat End (Cylindrical) Tank Volume Calculation...............................................2-9
Function Generator..............................................................................................2-11
SECTION 3 - INSTALLATION .....................................................................................................3-1
INTRODUCTION...........................................................................................................3-1
UNPACKING AND INSPECTION....................................................................................3-1
LOCATION CONSIDERATIONS.....................................................................................3-1
SETUP AND PHYSICAL INSTALLATION ........................................................................3-2
Mounting...............................................................................................................3-3
Flange Adapter ................................................................................................3-3
Vent/Drain Plugs ............................................................................................3-3
Electronics Housing Orientation ......................................................................3-3
Indicator Orientation .......................................................................................3-4
EZ CAL Option ................................................................................................3-5
Piping....................................................................................................................3-6
Open Tank Level Measurement........................................................................3-8
Closed Tank Level Measurement......................................................................3-9
Wiring..................................................................................................................3-11
Analog Mode..................................................................................................3-11
Digital Mode ..................................................................................................3-12
Grounding.....................................................................................................3-13
SELECTING DEFAULTS .............................................................................................3-13
HAZARDOUS LOCATION INSTALLATIONS (FLAMMABLE ATMOSPHERES).................3-13
SECTION 4 - CALIBRATION.......................................................................................................4-1
INTRODUCTION...........................................................................................................4-1
CALIBRATION PROCEDURES ......................................................................................4-1

iv WBPEEUI110505A0
Table of Contents (continued)
Page
SECTION 4 - CALIBRATION (continued)
Equipment Required for Calibration ......................................................................4-1
Analog Mode Calibration........................................................................................4-2
Bench Calibration ........................................................................................... 4-2
D/A Adjustment (Fine Tuning the Analog Loop)...............................................4-3
Digital Mode Calibration........................................................................................4-5
RERANGING THE ANALOG OUTPUT............................................................................4-6
REZERO PROCEDURE ................................................................................................4-6
VERIFYING CALIBRATION WITH THE EZ CAL OPTION................................................4-6
ALTERNATE CALIBRATION METHOD.......................................................................... 4-7
Analog Mode Transmitters.....................................................................................4-7
Digital Mode Transmitters .....................................................................................4-8
SECTION 5 - OPERATING PROCEDURES................................................................................5-1
INTRODUCTION ..........................................................................................................5-1
OPERATOR INTERFACE ..............................................................................................5-1
CONFIGURATION PROCEDURE ..................................................................................5-1
ID Tag ...................................................................................................................5-1
Select Mode...........................................................................................................5-1
Channel Number...................................................................................................5-2
Transmitter Type................................................................................................... 5-2
Output Type..........................................................................................................5-2
Output Action .......................................................................................................5-2
Damping Adjustment.............................................................................................5-2
Primary Engineering Units.....................................................................................5-3
Primary Upper and Lower Range Values................................................................5-3
Startup and Failure Conditions ............................................................................. 5-3
Secondary Engineering Units.................................................................................5-4
Secondary Lower and Upper Range Values ............................................................5-4
Cell Temperature Alarm Limits..............................................................................5-4
Get Config Key.......................................................................................................5-4
Send Config Key .................................................................................................... 5-5
View Config Key.....................................................................................................5-5
OPERATIONAL FUNCTIONS.........................................................................................5-5
Special Feature Key...............................................................................................5-5
Fix Output/Cancel Fix Output........................................................................5-5
Local LCD Setup ............................................................................................. 5-5
Standard Configuration...................................................................................5-5
Output Key............................................................................................................5-6
Monitor Output............................................................................................... 5-6
Monitor Input..................................................................................................5-6
Monitor Cell Temperature................................................................................ 5-6
Monitor Secondary Engineering Units..............................................................5-6
Status Key............................................................................................................. 5-6
F1 Key...................................................................................................................5-7
CONFIGURATION LOCKOUT PROCEDURE.................................................................. 5-7
SECTION 6 - TROUBLESHOOTING...........................................................................................6-1
INTRODUCTION ..........................................................................................................6-1
ERROR MESSAGES AND CORRECTIVE ACTION .........................................................6-1

WBPEEUI110505A0 v
Table of Contents (continued)
Page
SECTION 7 - MAINTENANCE.....................................................................................................7-1
INTRODUCTION...........................................................................................................7-1
PREVENTIVE MAINTENANCE SCHEDULE ...................................................................7-1
PREVENTIVE MAINTENANCE PROCEDURES...............................................................7-2
Checking Connections ...........................................................................................7-2
Indicator Window Cleaning ....................................................................................7-2
Transmitter Exterior Cleaning................................................................................7-3
SECTION 8 - REPAIR AND REPLACEMENT PROCEDURES ..................................................8-1
INTRODUCTION...........................................................................................................8-1
COMPONENT REMOVAL AND INSTALLATION PROCEDURES......................................8-1
Tank Flange/Cell and Characterization Board Assembly Removal ..........................8-2
Tank Flange/Cell and Characterization Board Assembly Installation......................8-4
Amplifier Assembly Removal ..................................................................................8-6
Amplifier Assembly Installation..............................................................................8-6
Electronics Housing and Housing Cover Replacement............................................8-7
Bolting Removal.....................................................................................................8-7
Bolting Installation ................................................................................................8-8
Process Flange Removal (Low Pressure Side Only)..................................................8-8
Process Flange Installation (Low Pressure Side Only)..............................................8-9
O-Ring Replacement ............................................................................................8-10
OPTIONAL EQUIPMENT REMOVAL AND INSTALLATION PROCEDURES ....................8-10
Indicator Removal................................................................................................8-10
Indicator Installation............................................................................................8-10
EZ CAL Option Removal.......................................................................................8-11
EZ CAL Option Installation ..................................................................................8-11
Flange Adapter Removal.......................................................................................8-11
Flange Adapter Installation ..................................................................................8-11
Vent/Drain Plug and Pipe Plug Removal ..............................................................8-11
Vent/Drain Plug and Pipe Plug Installation..........................................................8-12
Tagging Replacement (Wired Stainless Steel)........................................................8-12
SECTION 9 - SUPPORT SERVICES...........................................................................................8-1
INTRODUCTION...........................................................................................................8-1
REPLACEMENT PARTS ................................................................................................8-1
SPARE PARTS LISTS....................................................................................................8-1
O-Ring Kits............................................................................................................8-1
Flange and Bolting Kits..........................................................................................8-3
Electronics Kits......................................................................................................8-4
Hardware Kits........................................................................................................8-5
Tank Flange/Cell with Characterization Board Assembly Replacements.................8-7
TRAINING ....................................................................................................................8-7
TECHNICAL DOCUMENTATION...................................................................................8-8

vi WBPEEUI110505A0
No. Title Page
List of Figures
2-1. Type PTSDL Transmitter .......................................................................................2-1
2-2. Cell and Characterization Board Assembly ............................................................2-2
2-3. Electronics Block Diagram.....................................................................................2-3
2-4. Analog Point-to-Point Wiring..................................................................................2-5
2-5. Digital Field Bus Wiring.........................................................................................2-5
2-6. Communication Noise Rejection.............................................................................2-6
2-7. Spherical Tank Measurement ................................................................................2-8
2-8. Flat End (Cylindrical) Tank Measurement............................................................ 2-10
2-9. Function Generator Example............................................................................... 2-11
3-1. External and Mounting Dimensions.......................................................................3-2
3-2. Cell Lock ...............................................................................................................3-4
3-3. Indicator Orientation.............................................................................................3-5
3-4. Open Tank Level Measurement..............................................................................3-7
3-5. Closed Tank (Noncondensing Atmosphere) Level Measurement..............................3-8
3-6. Closed Tank (Condensing Atmosphere) Level Measurement ...................................3-9
4-1. Shop Calibration Fixture .......................................................................................4-2
4-2. Calibration Setup (Typical) ....................................................................................4-3
5-1. Lockout Jumper....................................................................................................5-8
6-1. Troubleshooting Flowchart (Sheet 1 of 3)...............................................................6-7
6-2. Troubleshooting Flowchart (Sheet 2 of 3)...............................................................6-8
6-3. Troubleshooting Flowchart (Sheet 3 of 3)...............................................................6-9
8-1. Internal Transmitter Components.......................................................................... 8-3
8-2. Tank Flange/Cell and Characterization Board Assembly........................................8-4
8-3. Type PTSDL Level Transmitter...............................................................................8-5
List of Tables
No. Title Page
1-1. Reference Documents............................................................................................ 1-4
1-2. Nomenclature........................................................................................................1-4
1-3. Specifications........................................................................................................1-7
1-4. Ambient Condition Limits for Certified Applications............................................. 1-10
1-5. Options and Accessories...................................................................................... 1-10
3-1. Dimensions for Figure 3-1.....................................................................................3-2
6-1. Error Messages......................................................................................................6-2
6-2. Output Troubleshooting ........................................................................................6-5
7-1. Preventive Maintenance Schedule..........................................................................7-2
9-1. O-Rings, Cell and Cover.........................................................................................8-1
9-2. O-Ring, Process Flange, Low Pressure ...................................................................8-2
9-3. O-Ring, Flange Adapter .........................................................................................8-2
9-4. Process Flange, Low Pressure Side.........................................................................8-3
9-5. Flange Adapter, Low Pressure Side........................................................................8-3
9-6. Bolting ..................................................................................................................8-4
9-7. Amplifier Assembly (Compensated) ........................................................................8-4
9-8. Indicator, Add-On..................................................................................................8-4
9-9. Indicator, Spare.....................................................................................................8-5
9-10. EZ CAL Option ......................................................................................................8-5

WBPEEUI110505A0 vii
No. Title Page
List of Tables (continued)
9-11. Tag, Stainless Steel, Wired.....................................................................................8-5
9-12. Electronics Housing...............................................................................................8-6
9-13. Cover, Housing ......................................................................................................8-6

viii WBPEEUI110505A0
Safety Summary
SPECIFIC
WARNINGS Consider the corrosive properties of the measured substance when
selecting piping materials. Degradation of the piping can upset the
process. Some process upsets can injure personnel and damage
equipment. (p. 3-6)
When pressurizing, avoid overloading and pressure hammer. Refer
to the introduction section for the pressure limits of the cell. Exceed-
ing this pressure could result in damage to the cell and cause seri-
ous injury to personnel. (p. 3-6)
Explosionproof/dust-ignitionproof installations and intrinsically safe
installations in Class II or Class III hazardous locations require that
the assembly be kept tight while circuits are live unless the location
is known to be nonhazardous at the time. (p. 4-1, 7-1, 8-1)
System maintenance must be performed only by qualified personnel
and only after securing the equipment controlled by the circuit.
Altering or removing components from an active circuit may upset
the controlled process leading to personnel injury and equipment
damage. (p. 7-1)
Repairs must be performed only by qualified personnel and only
after securing the equipment controlled by the circuit. Altering or
removing components from an active circuit may upset the con-
trolled process leading to personnel injury and equipment damage.
(p. 8-1)
The outputs of smart devices change to a fixed value during initial-
ization and detected failure conditions. These values must be
selected by the user to insure safe operation. (p. 5-3)
SPECIFIC
CAUTIONS Clean the diaphragms with a soft rag and appropriate solvent. The
use of metal brushes, blades, or other tools will damage the dia-
phragms. (p. 7-3)
Do not attempt to remove the two screws that secure the cell and
characterization board assembly to the tank flange assembly. The
capillary is welded into place. Attempting to remove the cell and
characterization board assembly from the tank flange assembly
could damage the weld. (p. 7-3, 8-4)

WBPEEUI110505A0 ix
Trademarks and Registrations
Registrations and trademarks used in this document include:
™Platinum Standard Trademark of Elsag Bailey Process Automation.
™EZ CAL Trademark of Elsag Bailey Process Automation.
®HART Registered trademark of HART Communication Foundation.
®INFI 90 Registered trademark of Elsag Bailey Process Automation.
®Hastelloy Registered trademark of Haynes International, Incorporated.
®Viton Registered trademark of DuPont Dow Elastomers L.L.C.
®Teflon Registered trademark of E. I. DuPont de Nemours Company, Incorporated.
®NEVER-SEEZ Registered trademark of USM Corporation.
®Dow Corning Registered trademark of Dow Corning Corporation.
®Tape-Seal Registered trademark of Friesland Plastics Company.

OVERVIEW
WBPEEUI110505A0 1 - 1
SECTION 1 - INTRODUCTION
OVERVIEW
The Type PTSDL Platinum Standard Smart Level Transmitter
accurately measures the level of corrosive and noncorrosive
fluids. The transmitter can be configured to provide a polled
digital process variable signal (digital field bus mode) or a four
to 20-milliampere process variable signal (analog mode).
It is important for safety and operating reasons to read and
understand this instruction. Until doing so, do not complete
any tasks or procedures related to installation, calibration,
operation, maintenance, troubleshooting, or repair.
INTENDED USER
The information in this publication is a guide for technical per-
sonnel responsible for the installation, calibration, operation,
maintenance, troubleshooting, and repair of the Type PTSDL
Platinum Standard Smart Level Transmitter.
EQUIPMENT DESCRIPTION
The Type PTSDL level transmitter consists of a cell and char-
acterization board assembly, and an electronics assembly. The
electronics package uses the latest microprocessor technology,
allowing calibration, operation, and troubleshooting from a
local or remote location.
The Type STT Smart Transmitter Terminal communicates with
the transmitter to configure, calibrate, check transmitter sta-
tus, and perform other interactions with the transmitter. The
EZ CAL™option allows calibration validation without the
Type STT terminal. An optional LCD (liquid crystal display)
shows output in percent and user-defined secondary engineer-
ing units, input in primary engineering units, cell tempera-
ture, and the transmitter ID tag. An analog meter is also
available for local output indication for those applications
where the transmitter operates at temperature extremes (refer
to Table 1-3 for the temperature limits).
FEATURES
Accurate, Stable, and Reproducible Measurements. Differ-
ential reluctance cell technology provides precise, stable, and
reproducible level measurements.
Easy Zero and Span Validation. Nonintrusive EZ CAL
option does not violate transmitter case. Allows zero and span

INTRODUCTION
FEATURES
1 - 2 WBPEEUI110505A0
validation to previously defined pressure values without using
Type STT terminal. May be supplied at delivery or added in the
field, and can be used on any Type PTSDL level transmitter
(except those with stainless steel housings).
Enhanced Remote Communications. Communicates with
Type STT terminal. Hand-held communication device uses
high frequency AC signaling method known as FSK (frequency
shift keying). Functions in high noise environments found in
many factories. Communicates with transmitter anywhere
there is access to signal wires within 1.6 kilometers (1.0 mile)
of transmitter. Parallel connection does not disrupt isolated
analog four to 20-milliampere process variable signal. Termi-
nal is also available in French and Spanish language versions.
Types STT04 terminals and later have the ability to communi-
cate with HART®devices.
Optional Two-Line, Seven Character Liquid Crystal
Display. Displays output in percent and user-defined second-
ary engineering units, input in primary engineering units, cell
temperature, and transmitter ID tag. Analog meter is also
available for those applications where transmitter operates
outside temperature limits of LCD. Both are easily installed for
convenient local indication.
Advanced Electronics Insures Reliability. Amplifier assem-
bly uses surface mount technology, designed to exceed 50
years MTBF (mean time between failure).
Dual Cover Housing. Immune to radio frequency interference.
Reduced Installation and Service Costs. Remote communi-
cations, modular plug-in electronics, and long-term stability
reduce installation and service time.
Direct Replacement of Existing Analog Two-Wire
Transmitters. Transmitters used in the analog mode replace
most four to 20-milliampere output pressure transmitters that
operate over a two-wire system.
Digital Field Bus Compatibility. When used as a high speed
digital communicating device, analog signal processing does
not occur. This results in an overall accuracy that is improved
by more than three times compared to a traditional analog sys-
tem. Such applications are INFI 90®OPEN supported.
Transmitter Diagnostics. Performs a series of self-checks,
monitoring such areas as configuration integrity and input cir-
cuitry. Two user-defined cell temperature alarms are available.
These diagnostics reduce troubleshooting and service time.
Agency Certifications. Complies with FM (Factory Mutual)
and CSA (Canadian Standards Association) certifications as
intrinsically safe, explosionproof, and nonincendive. Selected

INTRODUCTION
EQUIPMENT APPLICATION
WBPEEUI110505A0 1 - 3
transmitters may be supplied with CENELEC (European Com-
mittee for Electrotechnical Standardization) or SAA (Standards
Association of Australia) certifications on special order. A
NEMA 4X and IP67 housing makes the transmitter suitable for
corrosive environments. The standard electronics housing is
made of a low copper (less than one percent) Aluminum alloy.
A polyurethane coating provides environmental protection.
EQUIPMENT APPLICATION
Use the transmitter for process control in the power, gas,
water, petroleum, pulp and paper, and food industries.
INSTRUCTION CONTENT
This instruction is organized into nine sections.
Introduction Describes this instruction and the transmitter. Includes refer-
ence documents, nomenclature, specifications, and options
and accessories.
Description and
Operation Describes the functional operation of the transmitter and
associated equipment. Also includes information about special
applications such as volume measurements and the function
generator.
Installation Provides procedures for placing the transmitter into service.
Calibration Identifies the calibration status of the transmitter and provides
calibration check procedures. Calibration and validation pro-
cedures using both the Type STT terminal and EZ CAL option
appear here.
Operating Procedures
(Transmitter
Configuration)
Addresses startup procedures, configuring, and monitoring of
the transmitter (using the Type STT terminal), and the proce-
dures that make the unit operational.
Troubleshooting Provides steps that aid in solving operating difficulties that can
occur, tables that list corrective action for error messages, and
a troubleshooting flowchart.
Maintenance Contains preventive maintenance schedules and procedures.
Repair and Replacement
Procedures Details procedures involved in replacing transmitter
components.
Support Services Provides spare parts lists and ordering information for replace-
ment parts.
HOW TO USE THIS INSTRUCTION
Read this entire instruction through in sequence before
attempting to install, calibrate, operate, troubleshoot, service,

INTRODUCTION
REFERENCE DOCUMENTS
1 - 4 WBPEEUI110505A0
or repair the transmitter. After becoming completely familiar
with the transmitter and this instruction, it may be used as a
reference.
Throughout this instruction, the following text conventions
generally apply.
Display Item
Any item displayed on a screen appears as italic text.
REFERENCE DOCUMENTS
Table 1-1 lists Bailey-Fischer & Porter documents referred to
in this instruction.
NOMENCLATURE
Use Table 1-2 to select or verify transmitter type.
Table 1-1. Reference Documents
Number Description
B8113038 Board level wiring diagram
C-E21-50 Platinum Standard Series Smart Transmitters for Pressure, Flow and Level Mea-
surements, Type PTS Specification
D3055060 Dimension drawing
D3055064 Dimension drawing for optional indicator
D3055065 User field connections
I-E96-302 Field Bus I/O Module (IMFBS01) Instruction
I-G18-1 Instrument Connecting Piping
P-E21-001 Installing a 4 to 20 mA Transmitter in a Hazardous Location
WBPEEUI110502A0 Type STT Smart Transmitter Terminal Instruction
Table 1-2. Nomenclature
Position 56789101112131415 Platinum Standard Smart Level
Transmitter — D Type Cell
PTSD_____ ______
Measurement application
L____ ______Levelmeasurement
Measurement range1
C_________
D_________
F_________
Nominal Range Minimum Range
kPa in. H2O/psi kPa in. H2O/psi
0 - 30 0 - 120 in. H2O 0 - 5 0 - 20 in. H2O
0 - 90 0 - 360 in. H2O 0 - 5 0 - 20 in. H2O
0 - 500 0 - 75 psi 0 - 25 0 - 3.8 psi

INTRODUCTION
NOMENCLATURE
WBPEEUI110505A0 1 - 5
High pressure diaphragm and extension material,
extension length, and base size
1________
2________
3________
4________
5________
6________
7________
8________
A________
B________
C________
D________
E________
F________
G________
H________
High pressure flange material, size, and pressure rating
A_______
B_______
C_______
D_______
Low pressure diaphragm material and fill fluid
1______
2______
3______
4______
Low pressure flange material, threading, and ½-NPT
adapter
A_____
B_____
C_____
D_____
Table 1-2. Nomenclature (continued)
Position 56789101112131415 Platinum Standard Smart Level
Transmitter —D Type Cell
PTSD_____ ______
High Pressure Diaphragm and
Extension Extension
Length (in.) Base Size
(in.)
Stainless steel 316 (ordered most) Flush 3
Stainless steel 316 2 3
Stainless steel 316 4 3
Stainless steel 316 6 3
Stainless steel 316 Flush 4
Stainless steel 316 2 4
Stainless steel 316 4 4
Stainless steel 316 6 4
Hastelloy® C-276 Flush 3
Hastelloy C-276 2 3
Hastelloy C-276 4 3
Hastelloy C-276 6 3
Hastelloy C-276 Flush 4
Hastelloy C-276 2 4
Hastelloy C-276 4 4
Hastelloy C-276 6 4
Material Size (lbs) Pressure Rating
Stainless
steel 316 ANSI 150 class 1,890 kPa (275 psig) at 38°C (100°F)
Stainless
steel 316 ANSI 300 class 4,960 kPa (720 psig) at 38°C (100°F)
Carbon
steel ANSI 150 class 1,620 kPa (235 psig) at 38°C (100°F)
Carbon
steel ANSI 300 class 4,270 kPa (620 psig) at 38°C (100°F)
Diaphragm Material Fill fluid
Hastelloy C-276 Silicone oil
Tantalum Silicone oil
Hastelloy C-276 Fluorinated oil
Tantalum Fluorinated oil
Material Threading ½-NPT Adapter
Stainless Steel 316 North American 7/16 Not included
Stainless steel 316 North American 7/16 Included
Hastelloy C-276 North American 7/16 Not included
Hastelloy C-276 North American 7/16 Included

INTRODUCTION
NOMENCLATURE
1 - 6 WBPEEUI110505A0
Bolting and low pressure side O-ring material
1____
2____
3____
A____
B____
C____
M____
N____
P____
Certifications
0___NEMA4X—Bailey-Fischer & Porter standard
1 NEMA 4X and CENELEC flameproof and intrinsically safe
2___NEMA4XandFMandCSAexplosionproofandintrinsically
safe
Housing and electrical connection
1__
A__
Indicator, lightning arrestor, and EZ CAL option3
0_
1_
3_
4_
A_
B_
D_
E_
M_
N_
Q_
R_
Table 1-2. Nomenclature (continued)
Position 56789101112131415 Platinum Standard Smart Level
Transmitter —D Type Cell
PTSD_____ ______
Bolt Material O-Ring Material
Carbon steel (ordered most) Viton®
Stainless steel
ASTM A193 B7M: NACE Cl22
Carbon steel Teflon®(PTFE)
Stainless steel
ASTM A193 B7M: NACE Cl22
Carbon steel Ethylene propylene
Stainless steel
ASTM A193 B7M: NACE Cl22
Housing Electrical Connection
Standard - low Cu light alloy Al Two ½NPT with 1 plug
Stainless steel 316 Two ½NPT with 1 plug3
Indicator Lightning Arrestor EZ CAL Option3
Not included Not included Not included
Not included Included Not included
Not included Not included Included3
Not included Included Included3
LCD Not included Not included
LCD Included Not included
LCD Not included Included3
LCD Included Included3
Analog meter Not included Not included
Analog meter Included Not included
Analog meter Not included Included3
Analog meter Included Included3

INTRODUCTION
SPECIFICATIONS
WBPEEUI110505A0 1 - 7
SPECIFICATIONS
Table 1-3 lists the specifications for the Type PTSDL level
transmitter.
Configuration, tagging, and accessories
0
1
2
3
4
5
6
7
A
B
C
D
E
F
G
H
NOTES:
1. Units will be set to the nominal range. Specific customer calibrations are selected in nomenclature position 15. Refer to Table 1-5 for help.
2. NACE bolting cannot be used with transmitters with stainless steel high pressure diaphragm material (1 through 8 in nomenclature
position 7).
3. EZ CAL option cannot be used on transmitters with stainless steel housings (A in nomenclature position 13).
Table 1-2. Nomenclature (continued)
Position 56789101112131415 Platinum Standard Smart Level
Transmitter —D Type Cell
PTSD_____ ______
Configuration Customer Tagging Accessories
Standard Not included Not included
Standard Riveted stainless steel Not included
Standard Wired stainless steel Not included
Standard Paper Not included
Standard Not included Included
Standard Riveted stainless steel Included
Standard Wired stainless steel Included
Standard Paper Included
Custom Not included Not included
Custom Riveted stainless steel Not included
Custom Wired stainless steel Not included
Custom Paper Not included
Custom Not included Included
Custom Riveted stainless steel Included
Custom Wired stainless steel Included
Custom Paper Included
Table 1-3. Specifications
Property Characteristic/Value
Reference conditions
Temperature 15.0°to 35.5°C (59.0°to 95.9°F)
Humidity 45% to 75%
Barometric pressure 86.0 to 106.0 kPa (12.5 to 15.4 psi)

INTRODUCTION
SPECIFICATIONS
1 - 8 WBPEEUI110505A0
Measurement range,
turndown ratio, zero
suppression, and zero
elevation
Lower range value (zero) and upper range value (100%) can be calibrated at any
value of pressure, provided that:
1. Their algebraic difference (the calibrated span) corresponds to an
authorized TDR.
2. Both are within the following acceptable limits.
Reference accuracy -
perIEC 770andSAMA
PMC 31.1
The reference accuracy includes the effects of linearity, hysteresis, repeatability,
and deadband. This value is for transmitters with zero based spans, silicone oil fill,
and Hastelloy C-276 isolating diaphragms at a reference temperature of 25°C
(77°F). The value listed may vary depending on the URL and calibrated span of the
particular transmitter.
±0.20% of span or ± (% of span), whichever is greater.
Stability per 12-month
period ±0.25% of URL at reference conditions
Temperature limits
Table 1-3. Specifications (continued)
Property Characteristic/Value
Type
International System Units
Range Limits
(kPa) Span and Turndown Ratio (TDR)
Upper Lower Nominal (kPa) Maximum (kPa) Minimum (kPa)
PTSDLC 30 -30 30 1:1 TDR 60 0.5:1 TDR 5 6:1 TDR
PTSDLD 90 -90 90 1:1 TDR 180 0.5:1 TDR 5 18:1 TDR
PTSDLF 500 -500 500 1:1 TDR 1,000 0.5:1 TDR 25 20:1 TDR
Type
American Units
Range Limits
(in. H2O) Span and Turndown Ratio (TDR)
Upper Lower Nominal
(in. H2O) Maximum
(in. H2O) Minimum
(in. H2O)
PTSDLC 120 -120 120 1:1 TDR 240 0.5:1 TDR 20 6:1 TDR
PTSDLD 360 -360 360 1:1 TDR 720 0.5:1 TDR 20 18:1 TDR
—(psi)
PTSDLF 75 -75 75 1:1 TDR 150 0.5:1 TDR 3.8 20:1 TDR
0.016
URL
×
Span
--------------------------------
Parameter Electronics1Cell1,2,3 LCD4
°C°F°C°F°C°F
Normal
operating -40 to +85 -40 to +185 -40 to +85 -40 to +185 0 to +50 +32 to +122
Extreme
operating -50 to +85 -58 to +185 -50 to +120 -58 to +248 0 to +50 +32 to +122
Storage/
transport -55 to +85 -67 to +185 -55 to +85 -67 to +185 -20 to +70 -4 to +158

INTRODUCTION
SPECIFICATIONS
WBPEEUI110505A0 1 - 9
Ambient temperature
effect on zero and span These values are for transmitters with zero based spans, silicone oil fill, and Has-
telloy C-276 isolating diaphragms. The effects listed are for a variation of ±25°C
(±45°F) from a calibration done at a temperature between -30°and +80°C (-22°
and +176°F), as long as the variation does not take the transmitter out of the tem-
perature specifications listed under
Temperature limits
.
Range C with
extension ±(0.50% URL + 0.20% span)
All others ±(0.25% URL + 0.15% span)
Humidity limits 5% to 100% noncondensing continuous when the covers are properly installed and
the conduit is sealed
Pressure limits The minimum static pressure for all types is 3.4 kPa absolute (14.0 in. H2O abso-
lute or 0.5 psia). The maximum pressure is limited by the pressure rating of the
flange mounted on the high pressure side of the transmitter (Table 1-2, nomencla-
ture position 8).
Vibration effect ≤0.1% of URL for 1 g from 1 to 2,000 Hz in any axis of the transmitter
Enclosure rating NEMA 4X and IP67
Supply voltage 12 to 53 VDC (12 to 42 VDC for CSA certified applications)5,6. Installation
category III.
Power supply effect
Analog mode ±0.005% or URL per volt
Digital mode ±0.003% of URL per volt
Output signal
Analog 4 to 20 mA
Digital Bailey FSK communications
Output current limiting
Maximum ≥21.6 mA
Minimum ≤3.7
Loop load limits Refer to Figure 2-4
Damping/response
time(onetimeconstant
—approximately 62%
of final reading)
Analog and digital response to a step input change is adjustable from 0.0 to
32.0 secs and is entered during configuration. This value is in addition to:
Cell response time: dependent on cell and fill fluid
Electronics response time: approximately 0.25 secs
RFI/EMI effects ±0.1% of URL in fields from 4 to 1,000 MHz at 10 V/m
Surge tolerance Complies with IEEE 472 test criteria. 2.5 kV, 1.5 MHz, 150-Ωsource resistance
Weight
Table 1-3. Specifications (continued)
Property Characteristic/Value
Flange Type
Extension Type
None 50 mm (2 in.) 100 mm (4 in.) 150 mm (6 in.)
kg lbs kg lbs kg lbs kg lbs
3-in. ANSI 150 lb 10.2 22.4 11.2 24.6 11.6 25.8 12.0 26.4
3-in. ANSI 300 lb 12.7 27.9 13.0 28.6 13.5 29.7 14.0 30.8
4-in. ANSI 150 lb 12.7 27.9 13.7 30.1 14.3 31.5 15.0 33.0
4-in. ANSI 300 lb 17.5 38.5 18.0 39.6 18.6 40.9 19.0 41.8

INTRODUCTION
OPTIONS AND ACCESSORIES
1 - 10 WBPEEUI110505A0
OPTIONS AND ACCESSORIES
Table 1-5 lists and describes the options and accessories avail-
able with the Type PTSDL level transmitter.
FM and CSA
certifications7,8
Explosionproof and
dust-ignitionproof Class I, Division 1, Groups B, C and D; Class II, Division 1, Groups E, F and G;
Class III
Intrinsically safe Classes I, II and III, Division 1; applicable groups when connected per drawing
B222611
Nonincendive Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups E, F and G;
Class III
NOTES:
1. The normal operating temperature range is that at which the transmitter meets all specifications. The extreme operating temperature
range is that at which the transmitter remains powered without damage.
2. All transmitters with fluorinated oil filled cells can only be operated in temperatures from -10°to +80°C (+14°to +176°F).
3. The transmitter can be operated with fluid temperatures up to 150°C (302°F).
4. The normal operating temperature range for the LCD is that at which the LCD remains functional. Exceeding those conditions may cause
the LCD to go blank. The transmitter remains functional to its operating limits. When the temperature returns to the acceptable range,
the display is restored; however, the life of the display may be reduced.
5. The minimum supply voltage necessary to support communications is 17 VDC.
6. Add 0.4 VDC to all minimum supply voltage values if using the lightning arrestor option.
7. Refer to Table 1-4 for the ambient condition limits for certified applications.
8. The transmitters are only certified for those agencies and classes indicated on the certification label. Do not install the transmitters in
locations for which they are not suited. Refer to Table 1-2, nomenclature position 12.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
Table 1-4. Ambient Condition Limits for Certified Applications
Agency Category Tmax Tmin Pmax Pmin O2max
°C°F°C°F kPa psia kPa psia %
FM Explosionproof 80 176 -40 -40 108 15.7 86 12.5 21
Dust-ignitionproof
Intrinsic safety 65 (T4) 149 (T4)
Nonincendive
CSA Explosionproof 60 140
Dust-ignitionproof
Intrinsic safety 40 (T3C)
60 (T3A) 104 (T3C)
140 (T3A)
Nonincendive 60 (T4A) 140 (T4A)
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
Table 1-3. Specifications (continued)
Property Characteristic/Value
Table 1-5. Options and Accessories
Item Description
Type STT Smart Transmit-
ter Terminal Hand-held device for calibration, configuration,monitoring, and troubleshooting.
Also communicates with HART devices.
This manual suits for next models
1
Table of contents
Other Bailey Transmitter manuals
Popular Transmitter manuals by other brands

Endress+Hauser
Endress+Hauser RMA42 Brief operating instructions

Lectrosonics
Lectrosonics M2T-X Series instruction manual

HBC-Radiomatic
HBC-Radiomatic PM NTU operating instructions

Sennheiser
Sennheiser BT T100 instruction manual

Rotronic
Rotronic HygroFlex HF8 user guide

Connex
Connex Smart Transmitter user guide