Baumer PA418 User manual

V1 | 2/1/2024
EN-US
Operating Manual
PA418
Process display

Table of contents Baumer
ii Operating Manual PA418 | V1
Table of contents
1 About this document .................................................................................................................................. 4
1.1 Purpose and scope of application ....................................................................................................... 4
1.2 Applicable documents ......................................................................................................................... 4
1.3 Labels in this manual .......................................................................................................................... 4
1.4 Warnings in this manual...................................................................................................................... 5
2 General functionality................................................................................................................................... 6
3 Mounting the process display.................................................................................................................... 7
4 Electrical connection of the process display ........................................................................................... 8
4.1 Connection examples.......................................................................................................................... 10
5 Interfaces ..................................................................................................................................................... 12
5.1 LED indicator....................................................................................................................................... 12
6 Operating functions .................................................................................................................................... 14
6.1 Input signal configuration .................................................................................................................... 14
6.2 Configuration of the display................................................................................................................. 16
6.3 Configuration of the limit value outputs ............................................................................................... 20
6.4 Configuration of the analog output ...................................................................................................... 23
6.5 Control input configuration .................................................................................................................. 24
6.6 Set limit values .................................................................................................................................... 26
6.7 Protect programming level via code.................................................................................................... 27

Baumer List of illustrations
V1 | PA418 Operating Manual 3
List of illustrations
Ill. 1 Block diagram of the configuration modules ....................................................................................... 13
Ill. 2 Limit value outputs - Time delay ......................................................................................................... 20
Ill. 3 Limit value outputs - asymmetrical hysteresis..................................................................................... 20

1 | About this document Baumer
4 Operating Manual PA418 | V1
1 About this document
1.1 Purpose and scope of application
This document enables safe and efficient sensor parameterization using various interfaces. The
manual describes the available functions to support installation and software use via the inter-
faces.
The illustrations are examples only. Deviations are at the discretion of Baumer at all times. The
manual is a supplementary document to the existing product documentation.
1.2 Applicable documents
nAvailable for download at www.baumer.com:
▪ Data sheet
▪ Functional and interface description
▪ EU Declaration of Conformity
nAttached to product:
▪ Quickstart
▪ General information sheet (11042373)
1.3 Labels in this manual
Identifier Usage Example
Dialog element Indicates dialog elements. Click the OK button.
Unique name Indicates the names of products,
files, etc.
Internet Explorer is not supported
in any version.
Code Indicates entries. Enter the following IP address:
192.168.0.250

Baumer About this document | 1
V1 | PA418 Operating Manual 5
1.4 Warnings in this manual
Warnings draw attention to potential personal injury or material damage. The warnings in this
manual indicate different hazard levels:
Symbol Warning term Explanation
DANGER Indicates an imminent potential danger with high risk of death or
serious personal injury if not being avoided.
WARNING Indicates potential danger with medium risk of death or (serious)
personal injury if not being avoided.
CAUTION Indicates a danger with low risk, which could lead to light or
medium injury if not avoided.
NOTE Indicates a warning of material damage.
INFO Indicates practical information and tips that enable optimal use of
the devices.

2 | General functionality Baumer
6 Operating Manual PA418 | V1
2 General functionality
The process display is intend for visualizing, monitoring, control and calculation of measured
values in industrial applications.
nFor voltage ±10 V or current ±20 mA
nFor thermocouples J, K, T, N, Pt100
nFor weight, pressure, torsion, strain
nFor potentiometers
n11 supporting points for parameterization of Input characteristic
nThree control inputs, programmable
nDisplay stabilization filter
nLED display, 5-digit, 3-color, programmable
nFunction tare, min, max
nDIN housing 96 x 48 mm

Baumer Mounting the process display | 3
V1 | PA418 Operating Manual 7
3 Mounting the process display
1
3
2
Instruction:
a) Prepare the cut-out according to the dimensions.
b) Push device (1) with seal (2) into the cut-out.
c) Secure the device from behind using the clamping frame (3).
d) Perform the electrical connection.

4 | Electrical connection of the process display Baumer
8 Operating Manual PA418 | V1
4 Electrical connection of the process display
Instruction:
a) Make sure the device is disconnected from power supply and not live.
b) Connect the device according to the pin assignment.
Pin assignment (at rear)
2
1
-+
2
14
3
54
387
621
4
5
6
1
2
3
1
11
64
2
-
+
4 5
21 3
Operating voltage (1)
Pin VAC VDC
1 Phase -
2 Neutral +
Input signal (2)
Pin Current/voltage
1 Sensor supply -
2 Sensor supply +24V
3 n.c.
4 n.c.
5 Current input +
6 Voltage input +
7 n.c.
8 Current/voltage -
Pin Thermocouple Pt100
1 n.c. n.c.
2 n.c. n.c.
3 n.c. n.c.
4 n.c. Pt100 A
5 n.c. n.c.
6 n.c. n.c.
7 Thermo+ Pt100 B
8 Thermo- Pt100 B Common

Baumer Electrical connection of the process display | 4
V1 | PA418 Operating Manual 9
Pin Strain gauge
1 Sensor supply -
2 n.c.
3 Sensor supply +5V / +10 V
4 n.c.
5 n.c.
6 n.c.
7 Input mV+
8 Input mV-
Control input (3)
Pin
1 Common
2 Tara*
3 Reset Tara*
4 Hold*
* Factory settings. Other functions can be assigned via configuration.
Relay output (4), optional
Pin Two relays
1 normally closed 1
2 Inverter 1
3 normally open 1
4 normally closed 2
5 Inverter 2
6 normally open 2
Pin Four relays
1 normally closed 1
2 normally closed 2
3 normally closed 3
4 normally closed 4
5 n.c.
6 Common
Analog output (5), optional
Pin
1 (-) 4...20mA / 0...10V
2 (-) 4...20mA / 0...10V

4 | Electrical connection of the process display Baumer
10 Operating Manual PA418 | V1
4.1 Connection examples
Input voltage
4-wire sensor, ex-
ternal supply
Display
V-
Sensor
V+ OUT+ OUT-
V IN+
IN-
ext. Sensor
supply -
+
87654321
3-wire sensor, ex-
ternal supply
V+ OUT+ OUT-
V IN+
IN-
+
87654321
-
Display Sensorext. Sensor
supply
4-wire sensor,
supplied by de-
vice
Display Sensor
V+ OUT+ OUT-
V IN+
IN-
87654321 V-
Sensor supply-
Sensor supply+
3-wire sensor,
supplied by de-
vice
Display Sensor
V+ OUT+ OUT-
V IN+
IN-
87654321
Sensor supply+
Input current
4-wire sensor, ex-
ternal supply
V-
V+ OUT+ OUT-
I IN+
IN-
-
+
87654321
Display Sensorext. Sensor
supply
3-wire sensor, ex-
ternal supply
V+ OUT+ OUT-
I IN+
IN-
+
87654321
Display Sensorext. Sensor
supply
2 Wire 4 ... 20 mA
sensor, external
supply
V+ OUT+ OUT-
I IN+
IN-
+
87654321
-
Display Sensorext. Sensor
supply
4-wire sensor,
supplied by de-
vice
Display Sensor
V+ OUT+ OUT-
I IN+
IN-
87654321 V-
Sensor supply-
Sensor supply+

Baumer Electrical connection of the process display | 4
V1 | PA418 Operating Manual 11
3-wire sensor,
supplied by de-
vice
Display Sensor
V+ OUT+ OUT-
I IN+
IN-
87654321
Sensor supply+
2 Wire 4 ... 20 mA
sensor
V+ OUT+
I IN+
87654321
Sensor supply+
Display Sensor
Input strain gauge
Strain gauge
bridge circuit
Display
OUT+ OUT-
IN+
IN-
87654321
Sensor supply+
Sensor supply- IN-
IN+
LC
Device can directly supply two strain gauge sensors with 5 V or 10 V max. 60 mA. Connecting
more than 3 strain gauge sensors calls for parallel circuit configuration and external supply.
Input temperature
Pt100
Pt100
4 7 8
Thermocouple
Thermocouple
-+
8 7
Potentiometer input
Potentiometer
Potentiometer
Display
87654321

5 | Interfaces Baumer
12 Operating Manual PA418 | V1
5 Interfaces
This section describes the interfaces via which you can communicate with the device.
All functions can be set directly on the device via the display and the membrane buttons.
5.1 LED indicator
The device's LED display makes it easy to operate and monitor measured values.
1
2
3
4
TARE
MAX
MIN
PROG
TARE
MAX/MIN
1
3
456
2
9
8
10
7
After power on the device is in RUN mode. The current value (actual value) is displayed.
Mode PROG enables the entire device configuration.
No. Designation
Function in mode
RUN PROG
1 Display 5-digit LED display
2 LED 1 to 4 Output 1 ... 4 active
3 Label Position for unit sticker
4Button Call mode PROG Programming line selection
5Button MIN/MAX display Digit/Function selection
6Button Trigger TARE Incrementing the selected
digit
7 LED PROG Programming mode active
8 LED MIN MIN value display
9 LED MAX MAX value display
10 LED TARE TARA value stored

Baumer Interfaces | 5
V1 | PA418 Operating Manual 13
Mode PROG (configuration mode)
The programming mode allows the complete configuration of the process display. It comprises
several modules:
nInput signal configuration
nConfiguration of the display
nLimit value output configuration
nAnalog output configuration
nControl input configuration
Configuration
Display
* Configuration
Limits
* Configuration
Analog output
Configuration
Input signal
Configuration
Control inputs
Ill.1: Block diagram of the configuration modules
* As an option, according to product variant (see data sheet)
Programming process
Instruction:
a) Press to have appear on the display as initial view of the programming level.
b) Select the required configuration module with button . The individual modules provide
short descriptions. (CnInP, CndSP, etc.).
c) Confirm selected module with and start parameterization of the desired functions using
buttons , and . Having confirmed the final parameter, appears again on the
display. Press button to select another configuration module or to exit the programming
level.
Result:
ü appears briefly on the display and parameterization is being saved.
NOTICE
Access to programming can be blocked at programming level. The various programming lines
can then only be visualized but not changed. When entering the programming level, then
appears instead of .

6 | Operating functions Baumer
14 Operating Manual PA418 | V1
6 Operating functions
6.1 Input signal configuration
This function is used to configure the input signal.
Configuration
Input signal
Select the input signal type with l.
Standard signals ±10 V, ±20 mA or potentiometer
Strain gauge (pressure, weight,...)
Temperature: Thermocouples, Pt100
Confirm with .
Input standard signals
Select standard signal type with button .
Input voltage ±10 V/potentiometer
Input current ±20 mA
Confirm with .
Input strain gauge
Select voltage range with .
±15 mV
±30 mV
±150 mV
Confirm with .
Input temperature
Select temperature sensor with button r.
Pt100
Thermocouple J, K, T, N
Confirm with .

Baumer Operating functions | 6
V1 | PA418 Operating Manual 15
Pt100
Select the desired unit with button .
Degrees Celsius
Degrees Fahrenheit
Confirm with .
Select display resolution with button .
Resolution in 1/10 degrees
Resolution in degrees
Confirm with .
Proceed with configuration of display offset.
Programmable from -9.9 to +99 units depending on resolution.
The offset value can serve to compensate for any difference between actual
value and measured value.
Confirm with .
Thermocouple
Select thermocouple with button .
Thermocouple J
Thermocouple K
Thermocouple T
Thermocouple N
Select the desired unit with button .
Degrees Celsius
Degrees Fahrenheit
Confirm with .
Select display resolution with button .
Resolution in 1/10 degrees
Resolution in degrees
Confirm with .
Proceed with configuration of display offset.
Programmable from -9.9 to +99 units depending on resolution.
The offset value can serve to compensate for any difference between actual
value and measured value.
Confirm with .

6 | Operating functions Baumer
16 Operating Manual PA418 | V1
6.2 Configuration of the display
This function is used to configure the representation of the input signal on the display.
Positive gradient:
Displayed
value 2
Displayed
value 1
Measured
value 1
Measured
value 2
The scaling determines the relationship between the in-
put signal and the display value. For linear behavior, two
measured values(inP) or display values(dSP) must be
defined. To achieve the best precision, these 2 points
should be selected at both ends of the display range.
Negative gradient:
Displayed
value 1
Displayed
value 2
Measured
value 1
Measured
value 2
The coordinates of these two points can be entered di-
rectly using the keypad (scaling mode) or the measured
values are automatically adopted. Only the assigned dis-
play values need to be entered via the keypad (teach
mode).
Configuration
Display
INFO
Only the configuration parameters for the selected input signal can be selected.
Select the parameter to be configured with button .
Scaling mode (teach-in using known support points)
Teach mode (teach-in using measured support points)
Display stabilization filter
Round display value
Display brightness
Behavior of TAR function
Confirm with .

Baumer Operating functions | 6
V1 | PA418 Operating Manual 17
Scaling mode (teach-in using known support points)
Configuration of input and display values is done manually using the soft-touch keypad at the
process display. This method is appropriate if the sensor-supplied signal values are known at
each extreme point of the process.
First measured value
Keypad entries from -19999 to 99999.
Display value for the first measured value
The value entered here will be displayed upon the input signal reaching the
first measured value. Ranging from -19999 to 199999
Decimal point dSP1
Positioning decimal point, applies to dSP1 and dSP2.
Second measured value
Keypad entries from -19999 to 99999.
Display value for the second measured value
The value entered here will be displayed upon the input signal reaching the
second measured value. Ranging from -19999 to 199999
Programming of input characteristic
For measured values without linear behavior, up to 11 interpolation points (measured and dis-
play values) can be defined. For programming access to other measuring or display points,
press and hold the button for 3 seconds after having programmed the display value assigned to
the 2nd point. The new values assigned to the measuring or display points are identified by the
messages [Inp xx] and [dSP xx], whereas xx represents the point number of (de 03 to 11).
Measured value xx
Ranging from -19999 to 199999
Display value assigned to measured value xx
The value entered here is displayed when the input signal has reached the
measured value xx which was entered in the previous step. Programmable
from -19999 to 199999.
To interrupt programming of measuring or display points and save the val-
ues already entered, press and hold the button for 3 seconds after having
entered the previous display value.
INFO
Mandatory to enter the measured or displayed values in ascending or descending order.

6 | Operating functions Baumer
18 Operating Manual PA418 | V1
Teach mode (teach-in using measured support points)
The input values are read directly at the input at the time the signal is detected at any point in
the process. Displayed value configuration is done manually using the soft-touch keypad of the
process display. This method is appropriate if the signal values are known at each point but run-
ning the process at the conditions defined by these extreme points is not feasible.
First measured value
The input signal value is automatically adopted.
Display value for the first measured value
The value entered here will be displayed upon the input signal reaching the
first measured value. Ranging from -19999 to 199999
Decimal point dSP1
Positioning decimal point, applies to dSP1 and dSP2.
Second measured value
The input signal value is automatically adopted.
Display value for the second measured value
The value entered here will be displayed upon the input signal reaching the
second measured value. Ranging from -19999 to 199999
Programming of input characteristic
For measured values without linear behavior, up to 11 interpolation points (measured and dis-
play values) can be defined. For programming access to other measuring or display points,
press and hold the button for 3 seconds after having programmed the display value assigned to
the 2nd point. The new values assigned to the measuring or display points are identified by the
messages [Inp xx] and [dSP xx], whereas xx represents the point number of (de 03 to 11).
Measured value xx
Ranging from -19999 to 199999
Display value assigned to measured value xx
The value entered here is displayed when the input signal has reached the
measured value xx which was entered in the previous step. Programmable
from -19999 to 199999.
To interrupt programming of measuring or display points and save the val-
ues already entered, press and hold the button for 3 seconds after having
entered the previous display value.
INFO
Mandatory to enter the measured or displayed values in ascending or descending order.

Baumer Operating functions | 6
V1 | PA418 Operating Manual 19
Display stabilization filter
Defines the limit frequency of the low-pass filter (Fc) applied to smoothen unwanted display fluc-
tuations.
Programmable from 0 to 9 with the button .
Increasing the filter value reduces the response time of the display. The
value 0 deactivates the filter.
Confirm with .
Round display value
Change display value in steps of 1
Change display value in steps of 5
Change display value in steps of 10
Confirm with .
Display brightness
High brightness
Low brightness
Confirm with .
TARA function
Select the TARE button functionality with .
Every press on button will reset the display to zero and save the input
signal value as an offset; the TARE LED lights up.
To reset the offset value, press and hold button for 3 seconds.
Enter the tare value using the keypad, it will be subtracted from the dis-
played value after saving operation StorE (*).
Press the button to set the display to the entered tare value (*).
(*) Tare input in RUN or operator level
Confirm with .
tArE1 Example: Tare value 100
In RUN mode, press button and hold for 3 seconds
Enter value 100 with button and
Save with button (StorE)

6 | Operating functions Baumer
20 Operating Manual PA418 | V1
tArE2 Example: Display value before tare entry = 1000.
Display value after tare entry and saving operation = 1000 -100 = 900.
tArE2 Example: Display value before tare entry = 1000.
Display value after tare entry and confirmation with = 100.
6.3 Configuration of the limit value outputs
Device can be ordered with max. 4 relay limit outputs. Configuration with High or Low defines
output trigger either at display value ≥ or ≤ limit value. The outputs can be programmed with a
time delay or with a hysteresis.
Time delay of the limit value outputs
The time delay is programmable from 0 to 99 s. This acts both when the limit value outputs are
switched on and off.
DelayDelay
DelayDelay
HIGH
LOW
Limit 1
Limit 2
Ill.2: Limit value outputs - Time delay
Asymmetric hysteresis
The hysteresis is programmed in display units from 0 to 9999. This only takes effect when the
limit value outputs are switched off.
Hysteresis
Hysteresis
HIGH
LOW
Limit 1
Limit 2
Ill.3: Limit value outputs - asymmetrical hysteresis