BEA Mc-25 User manual

75.0066.07 MC-25 20180913 Page 1 of 4
MC-25
PRECAUTIONS
75.0066.07 MC-25 20180913 Page 1 of 4
Delay-on-make / Delay-on-break
time relay
ENGLISH
DESCRIPTION
TECHNICAL SPECIFICATIONS
Power supply: 15 – 24 VAC/VDC -5 – 10%
Operating frequency: 4 MHz (microprocessor)
Power consumption: 10 mA at rest; 50 mA max.
Output: 2 SPST relays
Max. voltage (relay contact): 30 VDC / 120 VAC
Max. current (relay contacts): 1.0A DC / 0.5A AC
Specifications are subject to change without
prior notice.
All values measured in specific conditions.
Shut off all power going to header before attempting any wiring procedures.
Maintain a clean and safe environment when working in public areas.
Constantly be aware of pedestrian traffic around the door area.
Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected
reactions by the door.
ESD (electrostatic discharge): Circuit boards are vulnerable to damage by electrostatic discharge. Before
handling any board, ensure you dissipate your body’s ESD charge.
Always check placement of all wiring before powering up to ensure that moving door parts will not catch
any wires and cause damage to equipment.
Ensure compliance with all applicable safety standards (i.e. ANSI A156.10) upon completion of installation.
DO NOT attempt any internal repair of the components. All repairs and/or component replacements must
be performed by BEA, Inc. Unauthorized disassembly or repair:
1. May jeopardize personal safety and may expose one to the risk of electrical shock.
2. May adversely affect the safe and reliable performance of the product resulting in a voided warranty.

Page 2 of 4 75.0066.07 MC-25 20180913Page 2 of 4 75.0066.07 MC-25 20180913
WIRING
ELECTRICAL INSTALLATION
RELAY 2 N.O. contact
RELAY 2 N.C. contact
RELAY 2 COM contact
COM / N.O. (Act. Device input contact)
Power (-) 15 – 24 VAC/VDC
COM / N.O. (Act. Device input contact)
Power (+) 15 – 24 VAC/VDC
RELAY 1 COM contact
RELAY 1 N.O. contact
RELAY 1 N.C. contact
BLACK
RED
GRAY
GRAY
ORANGE
PURPLE
BROWN
GREEN
BLUE
YELLOW
JP11
4 JP2
JP
1
JP
2
1
4
MC-25
NO COM
Push Plate,
Motion Sensor, etc.
DRY INPUT
R
E
L
A
Y
1
R E L A Y 2
GRAY GRAY
GREEN YELLOW BLUE
(NC) (COM) (NO)
PURPLE (NC)
RED (COM)
BLACK (NO)
ORANGE
BROWN
NOTE : Unused wires must be insulated
to prevent damage. No voltage
should be applied to the gray wires
or damage to the unit will result.
MAGLOCK / ELECTRIC STRIKE
can either be a wet or dry output,
depending on jumper position
DOOR CONTROL
activation circuit at door control
Use blue and yellow for activation circuits requiring
a closed contact to activate the control.
observe polarity when
using DC power
15 – 24
VAC

75.0066.07 MC-25 20180913 Page 3 of 475.0066.07 MC-25 20180913 Page 3 of 4
MODULE SETTINGS
JUMPER SETTINGS: choice of wet or dry output for RELAY 1
DRY (no voltage/current supplied by time delay) = both jumpers on left and middle pins
WET (voltage/current supplied by time delay) = both jumpers on right and middle pins
supplied voltage = input voltage
DIP SWITCH SETTINGS: hold-open time delay
RELAY 1:
Adjustable from 0 to 7 seconds; red LED
on for duration of time delay set on
RELAY 1; independent of time delay set
on RELAY 1, RELAY 2 activates 0.5 or 1.5
seconds after RELAY 1 begins.
RELAY 2:
Time delay set to RELAY 2 is the hold open time delay
for the door; adjustable from 0 to 15 seconds; green
LED indicates RELAY 2 is active and sending signal to
door control to hold door open.
DELAY OPTION:
Time delay between
Relay 1 being activated
and Relay 2 being
activated.
OFF
ON
7654321
green LED (safety beams)
red LED (lock-out time)
8
RED LED
(RELAY 1 active)
GREEN LED
(RELAY 2 active)
JP1
JP2
1
4
BLUE
GREEN
YELLOW
GRAY
ORANGE
GRAY
BROWN
RED
BLACK
PURPLE
DRY OUTPUT ON RELAY 1
BLUE
GREEN
YELLOW
GRAY
ORANGE
GRAY
BROWN
RED
BLACK
PURPLE
JP1
JP2
1
4
WET OUTPUT ON RELAY 1
TIME
DELAY
(sec)
DIP 1
(1 sec)
DIP 2
(2 sec)
DIP 3
(4 sec)
1ON OFF OFF
2OFF ON OFF
3ON ON OFF
4OFF OFF ON
5ON OFF ON
6OFF ON ON
7ON ON ON
TIME
DELAY
(sec)
DIP 4
(1 sec)
DIP 5
(2 sec)
DIP 6
(4 sec)
DIP 7
(8 sec)
1ON OFF OFF OFF
2OFF ON OFF OFF
3ON ON OFF OFF
4OFF OFF ON OFF
5ON OFF ON OFF
6OFF ON ON OFF
7ON ON ON OFF
8OFF OFF OFF ON
9ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON
TIME
DELAY
(sec)
DIP 8
0.5 OFF
1.5 ON

Page 4 of 4 75.0066.07 MC-25 20180913Page 4 of 4 75.0066.07 MC-25 20180913
TROUBLESHOOTING
Door sequencer
will not activate
Faulty power supply or
activation input
Ensure correct power supply of 15 – 24 VAC / VDC.
Power should come from an isolated transformer – not
from the door control.
Check for proper power at the orange and brown
wires of the Door Sequencer. If power source is good,
but not present at the connector, check the orange
and brown wires for continuity with an ohm meter.
Replace as necessary.
When powering with DC power, observe polarity.
Orange must be (-) and brown must be (+).
Using a multi-meter, check both gray wires for continu-
ity.
Door stays open
too long
Total time delay between the
door sequencer and the door
control is too long
For hold-open time, use the Time Delay Module timer
if the door control does not have a time-delay adjust-
ment. If it does, set the Time Delay Module to the
minimum setting, and use the door control’s hold time
exclusively.
Door unlocks but
will not open
Lock device is drawing too
much from the power supply
Install separate power supply for lock device.
BEA, the sensor manufacturer, cannot be held responsible for incorrect installations or inappropriate adjustments of the sensor/device; therefore, BEA
does not guarantee any use of the sensor outside of its intended purpose.
BEA strongly recommends that installation and service technicians be AAADM-certified for pedestrian doors, IDA-certified for doors/gates, and factory-
trained for the type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor
system installation is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer recommendations
and/or per AAADM/ANSI/DASMA guidelines (where applicable) for best industry practices. Safety inspections must be performed during each service
call – examples of these safety inspections can be found on an AAADM safety information label (e.g. ANSI/DASMA 102, ANSI/DASMA 107).
Verify that all appropriate industry signage and warning labels are in place.
BEA INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
PLEASE KEEP FOR FURTHER USE – DESIGNED FOR COLOR PRINTING
Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462
©BEA | Original Instructions | 75.0066.07 MC-25 20180913
Other BEA Other manuals