Beckett SF User manual

RESIDENTIAL BURNERS
Potential for Fire, Smoke and Asphyxiation Hazards
To the Homeowner or Equipment Owner:
Please read and carefully follow all instructions
provided in this manual regarding your
responsibilities in caring for your heating
equipment.
Contact a professional, qualified service agency for
installation, start-up or service work.
Save this manual for future reference.
y
y
y
Incorrect installation, adjustment, or misuse of this burner could result in death, severe
personal injury, or substantial property damage.
To the Professional, Qualified Installer or Service Agency:
Please read and carefully follow all instructions provided
in this manual before installing, starting, or servicing this
burner or heating system.
The Installation must be made in accordance with all state
and local codes having jurisdiction.
y
y

2
To the Owner:
Thank you for purchasing a Beckett
burner for use with your heating appliance.
Please pay attention to the Safety Warnings
contained within this instruction manual.
Keep this manual for your records and
provide it to your qualified service agency
for use in professionally setting up and
maintaining your oil burner.
Your Beckett burner will provide years of
efficient operation if it is professionally
installed and maintained by a qualified
service technician. If at any time the burner
does not appear to be operating properly,
immediately contact your qualified
service agency for consultation.
We recommend annual inspection/
service of your oil heating system by a
qualified service agency.
Daily – Check the room in which your
burner/appliance is installed. Make sure:
Air ventilation openings are clean and
unobstructed
Nothing is blocking burner inlet air
openings
No combustible materials are stored
near the heating appliance
There are no signs of oil or water
leaking around the burner or appliance
Weekly
Check your oil tank level. Always
keep your oil tank full, especially
during the summer, in order to prevent
condensation of moisture on the inside
surface of the tank.
y
y
y
y
y
Remainder of manual to be used ONLY BY
QUALIFIED SERVICE TECHNICIANS
▼▼
Contents
General Information ....................................................3
Hazard Definitions ........................................................................ 3
Inspect/Prepare Installation Site................................ 5
Special Requirements ................................................................... 5
Inspect chimney or direct vent system .......................................... 6
Combustion air supply................................................................... 6
Clearances to burner and appliance ............................................. 7
Combustion chamber — Burner retrofitting................................... 7
Prepare the Burner...................................................... 7
Burner fuel unit.............................................................................. 7
Attach air tube (if not already installed) ........................................ 7
Install burner nozzle (if not already installed)
................................ 7
Check/adjust electrodes................................................................ 8
Servicing nozzle line assembly ..................................................... 8
Mount Burner on Appliance .......................................8
Mounting options........................................................................... 8
Mounting dimensions .................................................................... 8
Check/Adjust ‘Z’ Dimension - ‘F’ Heads ........................................ 8
Installing the Oil Tank and Supply System .................................. 10
Connect fuel lines........................................................................ 10
Wire Burner ................................................................ 11
Burner packaged with appliance ..................................................11
Burner installed at jobsite.............................................................11
Burner Controls......................................................... 12
GeniSys Model 7505 Control ...................................................... 12
Features ...................................................................................... 12
Wiring .......................................................................................... 12
Reset Button Operation............................................................... 14
Wire Burner ................................................................................. 16
Start Up Burner/Set Combustion ............................. 16
Cad Cell Resistance Measurement............................................. 16
Resetting From Restricted or Hard Lockout................................ 16
Startup / Checkout ...................................................................... 17
Check Safety Features................................................................ 17
Set combustion with instruments ................................................ 17
Perform Regular Maintenance..................................18
Shutting the Burner Off ............................................................... 18
Replacing the blower wheel: ....................................................... 18
Replacement Parts ....................................................19
Limited Warranty Information .................................. 20

3
SF/SM Burner Manual
Section: General Information
General Information
Hazard Definitions
Within the boundaries of the hazard warning, there will
be information presented describing consequences if the
warning is not heeded and instructions on how to avoid
the hazard.
Indicates a hazardous situation,
which, if not avoided, will result
in death or serious injury.
Indicates a hazardous situation,
which, if not avoided, could
result in death or serious injury.
Indicates a hazardous situation,
which, if not avoided, could
result in minor or moderate injury.
Intended to bring special attention
to information, but not related to
personal injury or property damage.
Feature SM SF
Firing Rate Range 1.25 to 3.00 gph 1.25 to 5.50 gph
Motor 1/5 HP 1/4 HP
Fuel pump capacity 3 gph (standard) 7 gph (standard)
UL Air Tube Combinations See Table 2 See Table 2
Blocking oil solenoid valve Optional Required above 3 gph
Primary control lockout timing 15 to 45 seconds (optional) 15 seconds maximum
Figure 1. Burner Label Location
This manual contains information that applies to both SM and SF burners. These burners may
appear to be basically identical, but there are differences in design and performance. Please
review the comparison chart below:
Owner’s Responsibility
Incorrect installation, adjustment, and
use of this burner could result in severe
personal injury, death, or substantial
property damage from fire, carbon
monoxide poisoning, soot or explosion.
Contact a professional, qualified service agency for the
installation, adjustment and service of your oil heating
system. This work requires technical training, trade
experience, licensing or certification in some states and
the proper use of special combustion test instruments.
Please carefully read and comply with the following
instructions:
Never store or use gasoline or other flammable
liquids or vapors near this burner or appliance.
Never attempt to burn garbage or refuse in this
appliance.
Never attempt to light the burner/appliance by
throwing burning material into the appliance.
Never attempt to burn any fuel not specified and
approved for use in this burner.
Never restrict the air inlet openings to the burner or
the combustion air ventilation openings in the room.
y
y
y
y
y

4
Section: General Information
Table 1 – Burner Specifications
Model SM
Capacity
(Note1)
Firing rate range: 01.25 – 3.00 GPH
Input: 175,000 – 420,000 Btu/hr
Model SF
Capacity
(Note1)
Firing rate range: 1.25 - 5.50 GPH
Input: 175,000 – 770,000 Btu/hr
Certifications/
Approvals
Model SM - UL listed to comply with ANSI/
UL296 and CSA-B140.0.
Model SF - UL listed to comply with ANSI/UL
296 and CSA-B140.0.
Fuels
DO NOT USE GASOLINE,
CRANKCASE OIL, OR ANY OIL
CONTAINING GASOLINE.
U.S. #1 or #2 fuel oil only (ASTM D396)
Canada #1 stove oil or #2 furnace oil only
Electrical
Power supply: 120 volts AC, 60 Hz, single phase
Operating load (SM): 5.8 Amps max
Operating load (SF): 7.1 Amps max
Motor (SM): 1/5 hp, 3450 rpm, NEMA ’N’ flange,
manual reset over load protection
Motor (SF): 1/4 hp, 3450 rpm, NEMA ’N’ flange,
manual reset over load protection
Ignition: Continuous duty solid-state igniter
Fuel pump Outlet pressure: Note 2
Air tube ATC code: See Table 2
Dimensions
(Standard)
Height: 12.5 in.
Width: 15 in.
Depth: 8.50 in.
Air tube diameter: 4.00 in.
Air tube ATC code: See Table 2
Note 1: Approval agency listed rating for Model SM is 1.25 to
3.00 gph and Model SF is 1.25 to 5.50 gph. However, the firing
rate range is limited by the specific air tube combination being
used. Refer to Table 2.
Note 2. UL Recognized to 4.0 GPH with a CleanCut pump for
use in pressure washers.
Note 3. See appliance manufacturer’s burner specifications
for recommended pump discharge pressure.
Frozen Plumbing and
Water Damage Hazard
If the residence is unattended in severely cold weather,
burner primary control safety lockout, heating system
component failures, power outages or other electrical
system failures could result in frozen plumbing and
water damage in a matter of hours. For protection, take
preventive actions such as having a security system
installed that operates during power outages, senses low
temperature and initiates an effective action. Consult with
your heating contractor or a home security agency.

5
SF/SM Burner Manual
Inspect/Prepare
Installation Site
Section: Inspect/Prepare Installation Site
Special Requirements
THE INSTALLATION OF A BURNER SHALL BE IN
ACCORDANCE WITH THE REGULATIONS OF
AUTHORITIES HAVING JURISDICTION.
For recommended installation practices in the U.S.
refer to the latest edition of NFPA 31. (CSA-B139
and CSA-B140 in Canada.
Concealed damage — If you discover damage to
the burner or controls during unpacking, notify the
carrier at once and file the appropriate claim.
When contacting Beckett for service information
— Please record the burner serial number (and have
available when calling or writing). You will find the
serial number on the silver label located on the left
rear of the burner. Refer to Figure 1.
○
○
○
○
Professional Service
Required
Incorrect installation, adjustment, and
use of this burner could result in severe
personal injury, death, or substantial
property damage from fire, carbon
monoxide poisoning, soot or explosion.
Please read and understand the manual supplied with
this equipment. This equipment must be installed,
adjusted and put into operation only by a qualified
individual or service agency that is:
Licensed or certified to install and provide technical
service to oil heating systems.
Experienced with all applicable codes, standards
and ordinances.
Responsible for the correct installation and
commission of this equipment.
Skilled in the adjustment of oil burners using
combustion test instruments.
The installation must strictly comply with all applicable
codes, authorities having jurisdiction and the latest
revision of the National Fire Protection Association
Standard for the installation of Oil-burning Equipment,
NFPA 31 (or CSA-B139 and CSA-B140 in Canada).
Regulation by these authorities take precedence over the
general instructions provided in this installation manual.
y
y
y
y
Fire, Smoke & Asphyxiation
Hazard
Carefully inspect the chimney or exhaust vent system.
Make sure it is properly sized and in good working
condition.
Follow the instructions supplied by the appliance
manufacturer.
The installation must strictly comply with all applicable
codes, authorities having jurisdiction and the latest
revision of the National Fire Protection Association
Standard NFPA 31 for the installation of chimneys
and vent sizing, (or CSA-B139 and CSA-B140 in
Canada).
Regulation by these authorities take precedence
over the general instructions provided in this
installation manual.
y
y
y
y
y
Table 2 – Air Tube Combination (ATC) codes
Firing
Rate
(gph)
Head
Static
plate
size
ATC Codes for usable air tube lengths
(‘A’ in inches; See Figure 3.)
(min-max) (in.) 6-5/8 9 13 16
SF Burner Only
1.25-2.25 F12 2-3/4 SF65VW SF90VW SF130VW SF160VW
1.75-2.75 F22 2-3/4 SF65VP SF90VP SF130VP SF160VP
1.75-3.25 F220 None SF65FD SF90FD SF130FD SF160FD
2.5-5.5 F310 None SF65FU SF90FU SF130FU SF160FU
SM Burner Only
1.25-2.00 F12 2-3/4 SM65VW SM90VW SM130VW SM160VW
2.00-3.00 F220 None SM65FF SM90FF SM130FF SM160FF
2.00-3.00 F22 None SM65VM SM90VM SM130VM SM160VM
Table 3. Chamber Dimensions
Chamber Dimensions (inches)
Firing
Rate
(GPH)
Round
I.D.
Rectangular Height Floor to
nozzle
Width Length
1.25 11 10 11 12 5-6
1.50 12 11 12 13 6-7
2.00 14 12 15 13 6-7
2.50 16 13 17 14 7-8
3.00 18 14 18 15 7-8
3.50 19 15 19 15 7-8
4.00 20 16 21 16 8-9
5.00 23 18 23 18 9-10
5.50 24 19 24 19 10-11

6
Inspect chimney or direct vent system
Starting with minimum gph firing rate, the minimum
size recommended is 6” flue pipe with 8” X 8”
inside chimney, unless specified otherwise by the
appliance manufacturer.
A chimney flue shall extend at least 3 feet above
the highest point at which the chimney comes in
contact with the roof, and not less than 2 feet above
the highest roof surface or structure within 10 feet
horizontally of the chimney. Refer to Figure 2.
Any accumulation of soot or debris in chimney
offsets should be removed.
Any obstructions such as a protruding joint or a
piece of broken tile wedged in the chimney should
be removed.
No other appliance connection should be made to
the same flue pipe.
The flue pipe should have an upward pitch toward
the chimney of at least 1/4” per foot of length. It
should fit tightly and should not project into the
chimney.
Any leakage between tiles, around clean-out doors,
or around the vent pipe should be sealed.
INSULATED STAINLESS STEEL CHIMNEY LINERS
The new designs of high efficiency oil furnaces and
boilers in conjunction with flame retention oil burners
are more efficient. One result of increased efficiency is
lower flue gas temperatures. As flue gases rise in the
chimney, they will cool and condense when they reach
the dew point. The condensation will mix with the sulphur
in the flue gases creating sulphuric acid. The acid will
attack the chimney mortar, brick and clay liners causing
corrosion, deterioration and blockage of the chimney.
Eventually the blockage could prevent exhausting the
flue gases. Instead, the flue gases could vent out the
barometric damper into the living space.
1.
2.
3.
4.
5.
6.
7.
Therefore, it is strongly recommended that an approved
insulated stainless steel liner be installed.
For those installations not requiring a chimney, such
as through-the-wall vented appliances, follow the
instructions given by the appliance and power venter
(if used) manufacturers.
Combustion air supply
See NFPA 31 Standard for complete details.
○
Appliance located in confined space
The confined space should have two (2) permanent
openings: one near the top of the enclosure and one
near the bottom of the enclosure. Each opening shall
have a free area of not less than (1) one square inch
per 1,000 BTU’s per hour of the total input rating of all
appliances within the enclosure. The openings shall
have free access to the building interior, which should
have adequate infiltration from the outside.
Section: Inspect/Prepare Installation Site
Figure 2 - Chimney Design - Above the Roof
Minimum Clearence: 2 FT.
NOTE: Correct
chimney design is
shown by dotted lines.
Incorrect chimney
design, as shown by
the solid lines, may
result in down-drafts.
Adequate Combustion
and Ventilation Air Supply
Required
Failure to provide adequate air supply could
seriously affect the burner performance and result in
damage to the equipment, asphyxiation, explosion or
fire hazards.
The burner cannot properly burn the fuel if it is not
supplied with a reliable combustion air source.
Follow the guidelines in the latest editions of the
NFPA 31 and CSA-B139 regarding providing
adequate air for combustion and ventilation
y
y

7
SF/SM Burner Manual
Install burner nozzle (if not already installed)
Exhaust fans and other air-using devices
Size air openings large enough to allow for all air-
using devices in addition to the minimum area required
for combustion air. If there is any possibility of the
equipment room developing negative pressure (because
of exhaust fans or clothes dryers, for example), either
pipe combustion air directly to the burner or provide a
sealed enclosure for the burner and supply it with its own
combustion air supply.
Clearances to burner and appliance
Provide space around burner and appliance for easy
service and maintenance.
Check minimum clearances against those shown
by the appliance manufacturer and by applicable
building codes.
Combustion chamber — Burner retrofitting
Verify that the appliance combustion chamber provides
at least the minimum dimensions given in Table 3.
○
○
Prepare the Burner
Burner fuel unit
Verify that the burner fuel unit is compatible with the
oil supply system. For more details, refer to the pump
manufacturer’s instructions provided with the burner.
Attach air tube (if not already installed)
If using a flange and gasket, slide them onto the air tube.
Then attach the air tube to the burner chassis using the
four sheet metal screws provided. Refer to Figure 4 for
details.
Remove the plastic plug protecting the nozzle
adapter threads
Place a ¾” open-end wrench on the nozzle adapter.
Insert the nozzle into the adapter and finger tighten.
Finish tightening with a ⅝” open-end wrench. Use
care to avoid bending the electrodes.
If the nozzle is already installed, remove the nozzle
line assembly to verify that the nozzle size and
spray pattern are correct for the application (per
appliance manufacturer’s information). Verify that
the electrode tip settings comply with Figure 3.
If the nozzle is not installed, obtain a nozzle
having the capacity and spray angle specified
in the appliance manufacturer’s information. For
conversions or upgrades, when information is not
available for the application:
Refer to Table 5 to select the mid-range nozzle
spray angle for the head type being used.
Fire the burner and make sure the combustion
is acceptable and the flame is not impinging on
chamber surfaces.
If a shorter flame is needed, select a wider spray
angle. If a longer flame is needed, select a
narrower spray angle.
Either hollow or solid spray patterns may be
used. If combustion results are not satisfactory
with the selected spray pattern, try the other
pattern.
1.
2.
3.
4.
○
○
○
○
Section: Prepare the Burner
Protect Steel Combustion
Chamber From Burnout
Failure to comply could result in damage to the heating
equipment and result in fire or asphyxiation hazards.
When retrofitting appliances that have unlined
stainless steel combustion chambers, protect the
chamber by lining the inside surfaces with a ceramic
fiber blanket, such as a wet-pac or other suitable
refractory material.
Some steel chambers may not require liners
because the appliance was designed and tested
for use with flame retention burners. Refer to the
manufacturer’s instructions.
y
y
Correct Nozzle and Flow
Rate Required
Incorrect nozzles and flow rates could
result in impaired combustion, under-
firing, over-firing, sooting, puff-back of
hot gases, smoke and potential fire or
asphyxiation hazards.
Use only nozzles having the brand, flow rate (gph),
spray angle and pattern specified by the appliance
manufacturer.
Follow the appliance manufacturer’s specifications for
the required pump outlet pressure for the nozzle, since
this affects the flow rate.
Nozzle manufacturers calibrate nozzle flow rates at
100 psig.
When pump pressures are higher than 100 psig, the
actual nozzle flow rate will be greater than the gph
stamped on the nozzle body. (Example: A 1.00 gph
nozzle at 140 psig = 1.18 gph)
Securely tighten the nozzle (torque to 90 inch pounds).
For typical nozzle flow rates at various pressures refer
to Table 4.
y
y

8
Mount Burner on Appliance
Mounting options
Table 4. Nozzle Flow Rate by Size
Nozzle flow rate U. S. gallons per hour of No. 2 fuel oil when
pump pressure (psig) is:
Nozzle
size
(rated at
100 psig)
125
psi
140
psi
150
psi
175
psi
200
psi
1.25 1.39 1.48 1.53 1.65 1.77
1.35 1.51 1.60 1.65 1.79 1.91
1.50 1.68 1.77 1.84 1.98 2.12
1.65 1.84 1.95 2.02 2.18 2.33
1.75 1.96 2.07 2.14 2.32 2.48
2.00 2.24 2.37 2.45 2.65 2.83
2.25 2.52 2.66 2.76 2.98 3.18
2.50 2.80 2.96 3.06 3.31 3.54
2.75 3.07 3.25 3.37 3.64 3.90
3.00 3.35 3.55 3.67 3.97 4.24
3.25 3.63 3.85 3.98 4.30 4.60
3.50 3.91 4.14 4.29 4.63 4.95
3.75 4.19 4.44 4.59 4.96 5.30
4.00 4.47 4.73 4.90 5.29 -
4.50 5.04 5.32 5.51 - -
5.00 5.59 ----
5.50 -----
Table 5. Nozzle Spray Angles
Recommended nozzle spray angles
“F” head 70°, 80° or 90° nozzle
Note: Always follow the appliance manufacturer’s nozzle specification,
when available.
Figure 3. – Electrode Tip Adjustment
Bolt the burner to the appliance using the factory-
mounted flange or an adjustable flange.
Mounting dimensions
When using the Beckett universal adjustable flange,
mount the air tube at a 2° downward pitch unless
otherwise specified by the appliance manufacturer.
Verify that the air tube installed on the burner
provides the correct insertion depth. See Figure 5.
The end of the air tube should normally be 1/4”
back from the inside wall of the combustion
chamber. Never allow the leading edge of the
head assembly to extend into the chamber, unless
otherwise specified by the heating appliance
manufacturer. Carefully measure the insertion
depth when using an adjustable flange. Verify the
insertion depth when using a welded flange.
1.
2.
3.
Check/adjust electrodes
Check the electrode tip settings. Adjust if necessary
to comply with the dimensions shown in Figure 3. To
adjust, loosen the electrode clamp screw and slide/rotate
electrodes as necessary. Securely tighten the clamp
screw when finished.
Servicing nozzle line assembly
Turn off power to burner before proceeding.
Disconnect oil connector tube from nozzle line.
Loosen the two screws securing igniter retaining
clips and rotate both clips to release igniter
baseplate. Then tilt igniter back on its hinge.
Remove splined nut.
“F” head air tube. - Remove nozzle line assembly from
burner, being careful not to damage the electrodes
or insulators while handling. To ease removal of long
assemblies (over 9 inches), rotate assembly 180° from
installed position after pulling partially out of tube.
To replace the nozzle assembly, reverse the above
steps.
1.
2.
3.
4.
5.
6.
Check/Adjust ‘Z’ Dimension - ‘F’ Heads
See Figure 4 for complete details.
Section: Mount Burner on Appliance
Do Not use Adjustable
Mounting Flange on Mobile
Units
The shock and vibration could cause loss of burner
alignment and insertion problems resulting in flame
impingement, heavy smoke, fire and equipment
damage.
Only use specified factory-welded flange and air
tube combinations.
y

9
SF/SM Burner Manual
1-1/8” PLUS SHROUD LENGTH
Z
DIM.
1-1/8”
Dimension (inches) F Head
A = Usable air length (inches) (Measure accurately)
L(Total tube length) A Dim. + 1/2
R(electrode length), + 1/4 A Dim. + 2-1/4
S(adapter to static plate), + 1/16 (Note 1)
Q(nozzle line length), A Dim. + 15/16
Z(F head w/o head shroud)
(F head-with head shroud)
1-1/8
1-1/8 + shroud length. (Note 2)
Note 1: 1-3/8 for dimension A less than 4”; 1-5/8 for dimension A
from 4” through 4-1/2 “, 2-13/32” for dimension A greater than 4-1/2”.
Note 2: When using a straight edge.
Burner Dimensions - Models SM & SF
head. A Beckett T501 or T650 gauge may also
be used.
Slide the nozzle line forward or back until the
Z dimension for F heads is 1-1/8” (1-1/8” plus
shroud length, if using a straight edge).
Tighten the hex head screw to secure the
escutcheon plate to the burner chassis. Then
tighten the splined nut and attach the oil
connector tube.
Recheck the “Z” dimension periodically when
servicing to ensure the escutcheon plate has
not been moved. You will need to reset the “Z”
dimension if you replace the air tube or nozzle
line assembly. The Beckett Z gauge (part number
Z-2000) is available to permit checking the F
head “Z” dimension without removing the burner
from the appliance.
○
○
3.
The important ‘Z’ dimension is the distance from
the face of the nozzle to the flat face of the head
(or heat shield, if applicable). This distance for
F heads is 1-1/8” (1-3/8” if the air tube has a
heat shield). The “Z” dimension is factory set for
burners shipped with the air tube installed. Even
if factory set, verify that the “Z” dimension has not
been changed.
Use the following procedure to adjust the “Z”
dimension, if it is not correct:
Turn off power to the burner.
Disconnect the oil connector tube from the
nozzle line
See above figure. Loosen the splined nut from
the nozzle line. Loosen the hex head screw
securing the escutcheon plate to the burner
housing.
Place the end of a ruler at the face of the
nozzle and, using a straight edge across the
head, measure the distance to the face of the
1.
2.
○
○
○
○
Figure 4. Check/Adjust ‘Z’ Dimension for ‘F’ Heads
Section: Mount Burner on Appliance
Adjust the ‘Z’ dimension to
the required specification.
Incorrect Adjustments could cause combustion
problems, carbon deposition from flame impingement,
heavy smoke generation and fire hazard.
Make all adjustments exactly as outlined in the
following information.
y

10
Note: to determine the proper fuel line size, refer to the
fuel pump manufacturer’s instructions provided with
the burner. Refer to Figure 6 or Figure 7 for typical
installation layouts.
Installing the Oil Tank and Supply System
Figure 5. – Mounting Burner in Appliance
Connect fuel lines
Carefully follow the fuel unit manufacturer’s literature
and the latest edition of NFPA 31 for oil supply system
specifications (CSA B-139 in Canada).
Fuel supply level with or above burner –
The burner may be equipped with a single-stage fuel
unit for these installations. Connect the fuel supply to the
burner with a single supply line if you want a one-pipe
system (making sure the bypass plug is NOT installed in
the fuel unit.) Manual bleeding of the fuel unit is required
on initial start-up. If connecting a two-pipe fuel supply,
install the fuel unit bypass plug.
Figure 6. – Inside Tank Gravity Feed System
Figure 7. – Outside Buried Tank-Lift System
To further protect the fuel supply
system and reduce nozzle orifice
plugging, a dual filtration system can be installed. This
typically consists of a 50 micron primary filter, located
near the fuel tank and a secondary filter rated for at least
10 microns located near the burner.
Section: Mount the Burner/Connect Oil Supply
SK8745
Tilt down 2
°
If space between burner air
tube and opening exceeds
1/2 inch, pack burner
opening with ceramic fiber
refractory.
4”
1/4” A
7/8”
Oil Leak and Fire Hazard
Install the oil tank following applicable standards in the
U.S. by referring to the latest edition of NFPA 31 or CSA-
B139 & CSA-B140 in Canada, and all authorities having
jurisdiction.
Do Not Use Teflon Tape
Damage to the pump could cause impaired burner
operation, oil leakage and appliance soot-up.
Never use Teflon tape on fuel oil fittings.
Tape fragments can lodge in fuel line components
and fuel unit, damaging the equipment and
preventing proper operation.
Use oil-resistant pipe sealant compounds.
y
y
y

11
SF/SM Burner Manual
Fuel supply below the level of the burner –
When the fuel supply is more than eight feet below
the level of the burner, a two-pipe fuel supply system
is required. Depending on the fuel line diameter and
horizontal and vertical length, the installation may
also require a two-stage pump. Consult the fuel
unit manufacturer’s literature for lift and vacuum
capability.
Fuel line installation –
Wire Burner
Burner packaged with appliance
Continuous lengths of 0.035” nominal wall (0.032”
minimum) copper tubing are recommended. Always
use flare fittings. Never use compression fittings.
Always install fittings in accessible locations.
Proper routing of fuel lines is required to prevent air
cavitation and vibration.
Fuel line valve and filter –
Install two high quality, oil duty rated, fusible-handle
design shutoff valves in accessible locations on the
oil supply line to comply with the NFPA 31 Standard
and authorities having jurisdiction. Locate one
close to the tank and the other close to the burner,
upstream of the filter for service access.
Install a generous capacity filter inside the building
between the fuel tank shutoff valve and the burner,
locating both the filter and the valve close to the
burner for ease of servicing. Filter should be rated
for 50 microns or less.
○
○
○
Section: Wire Burner
Oil Supply Pressure
Control Required
Damage to the filter or pump seals could cause oil
leakage and a fire hazard.
The oil supply inlet pressure to the burner cannot
exceed 3 psig.
Insure that a pressure limiting device is installed in
accordance with the latest edition of NFPA 31.
Do NOT install valves in the return line. (NFPA 31,
Chapter 8.)
Gravity Feed Systems:
Always install an oil safety
valve (Webster OSV or Suntec PRV) in the oil supply
line or a solenoid valve (RWB Part # 2182602U) in
the pump/nozzle discharge tubing to provide backup
oil flow cut-off protection.
y
y
y
y
Refer to appliance manufacturer’s wiring diagram for
electrical connections.
Burner installed at jobsite
Refer to Figures 11a and 11b, for typical burner
wiring, showing cad cell primary controls. Burner
wiring may vary, depending on primary control
actually used.
Refer to the appliance manufacturer’s wiring
diagram prior to connecting the burner wiring. All
wiring must be in accordance with the latest revision
of National Electric Code NFPA 70 and all local
codes and regulations. In Canada, all wiring is to be
in accordance with the Canadian Electrical Code,
Part 1.
The 7505 primary control with valve-on delay (pre-
time) and burner motor-off delay (post-time) requires
a constant 120 volts AC power source supplied to the
BLACK wire on the control. The RED wire goes to the
appliance limit circuit. Please note that other control
manufacturers may use different wire colors for
power and limit connections.
○
○
○
Electrical Shock Hazard
Electrical shock can cause severe personal
injury or death.
Disconnect electrical power before installing or
servicing the burner.
Provide ground wiring to the burner, metal control
enclosures and accessories. (This may also be
required to aid proper control system operation.)
Perform all wiring in compliance with the National
Electrical Code ANSI/NFPA 70 (Canada CSA C22.1)
y
y
y

12
Burner Controls
GeniSys Model 7505 Control
Wiring
Figure 8 - 7505 Control
Features
Thermostat / Operating and Limit Control
Compatible
Welded Relay Protection
Limited Recycle
Limited Reset
3 Status Lights
Valve-On Delay / Motor-Off Delay (Field
programmable with 52067 GeniSys Display)
15 Second Lockout Time
Interrupted or Intermittent Duty Ignition
Technician Pump Priming Mode
Disable Function
Communication Ports
○
○
○
○
○
○
○
○
○
○
○
Section: Burner Controls
The control can malfunction if it gets wet, leading to
accumulation of oil or explosive oil vapors.
Never install where water can flood, drip or
condense on the control.
Never use a control that has been wet - replace it.
y
y
y
Can cause severe injury, death, or property
damage.
Fire or Explosion Hazard
Follow the appliance manufacturer’s wiring diagrams
and note all required safety controls.
Typical safety controls include high temperature or
pressure limits, low water cutoffs, pressure relief
valves and blocked flue sensing switches.
Verify all limit and safety controls are installed
and functioning correctly, as specified by the
manufacturer, applicable safety standards, codes
and all authorities having jurisdiction.
Ensure that the appliance is free of oil and oil vapor
before starting or resetting the burner.
y
y
y
y
All heating appliances must have HIGH
LIMIT protection to interrupt electrical
power and shutdown the burner if operating
or safety controls fail and cause a runaway
condition.
Explosion, Fire, Scald, and
Burn Hazard
Incorrect Wiring Will
Result in Improper Control
Operation
GeniSys wiring label colors may not match the wire
colors of the burner or other manufacturers’ controls.
The GeniSys Control should be wired according to
the appliance manufacturer’s instructions.
y
y
Display Module:
Permanent device for programming
and diagnostics
Alarm Module:
For adding isolated low voltage alarm
contacts to the base control. See Alarm
Module Instructions for specifications.
Contractor’s Tool:
Hand-held device for
programming and diagnostics
Cad Cell
Connections
Wiring
Connections
Communication Port 2
Reset Button with Red Light
Communication Port 1
Thermostat Terminals
Green Light
Yellow Light
Optional Components:

13
SF/SM Burner Manual
the igniter remains on for 10 additional seconds
to ensure flame stability.
Run: The flame is sustained until the call for
heat is satisfied. The burner is then sent to
Motor-Off Delay, if applicable, or it is shut down
and sent to Standby.
Recycle: If the flame is lost while the burner is
firing, the control shuts down the burner, enters
a 60 second recycle delay, and repeats the
ignition sequence. The control will continue
to Recycle each time the flame is lost, until
it reaches a pre-set time allotment. The
control will then go into Hard Lockout instead
of recycle. This feature prevents excessive
accumulation of oil in the appliance firing
chamber.
Motor-Off Delay: If applicable, the oil solenoid
valve is turned off and the control delays
turning the motor off for the set motor-off delay
time before the control returns to standby.
Pump Prime: The igniter and motor are on with
the oil solenoid valve energized for 4 minutes.
During Pump Prime mode, the cad cell is
disregarded, allowing the technician to prime
the pump without having to jumper the cad cell.
6.
7.
8.
9.
Typical Burner Sequence of Operation for GeniSys 7505 Control.
Refer to the appliance manufacturer’s wiring diagram for actual specifications.
Standby: The burner is idle, waiting for a call for
heat.
Valve-On Delay: The igniter and motor are
on while the control delays turning on the oil
solenoid valve for the programmed time.
Trial For Ignition: The oil solenoid valve is
energized. A flame should be established within
the factory set trial for ignition time (lockout
time).
Lockout: The control has shut down for one of
the following safety reasons:
The trial for ignition (lockout) time expired
without flame being established.
The cad cell detected flame at the end of the
Valve On Delay state.
To reset the control from lockout click the button
1-second.
NOTE: A recurrence of the above failure modes or a
failed welded relay check could cause the control to
enter a Hard Lockout state that must be reset only
by a qualified service technician.
To reset from Hard Lockout, hold the reset button for
15 seconds until the yellow light turns on.
Ignition Carryover: Once flame is established,
1.
2.
3.
4.
a.
b.
5.
2
1
3
5
6
8
4
7
Standby
Motor-off delay
Valve-on delay Trial for
ignition
Ignition carryover
Run
Lockout
Recycle
9
Pump
prime
Section: Burner Controls

14
Figure 9a. – Interrupted ignition, valve-on delay only
(no motor-off delay)
Figure 9b. – Interrupted ignition, valve-on delay and
motor-off delay
SAFETY AND
OPERATING
LIMITS
LIMIT
L1
L2 (VLV)
VALVE
L2
MOTOR
L2 (MTR)
L2 (IGN)
IGNITER
CAD
CELL
MOTOR
IGNITER
W
R
80
70
60
50
50
70
80
60
OIL VALVE
CAD CELL
THERMOSTAT
TR
TW
TR-TW
JUMPER
TR-TW TERMINALS
LOCATED ON OPPOSITE
SIDE OF CONTROL
L1
L2
SAFETY AND
OPERATING
LIMITS
LIMIT
L1
L2 (VLV)
VALVE
L2
MOTOR
L2 (MTR)
L2 (IGN)
IGNITER
CAD
CELL
MOTOR
IGNITER
W
R
80
70
60
50
50
70
80
60
OIL VALVE
CAD CELL
THERMOSTAT
TR
TW
TR-TW
JUMPER
TR-TW TERMINALS
LOCATED ON OPPOSITE
SIDE OF CONTROL
L1
L2
LIMIT L1 - LIMIT
JUMPER
Table 2 - Reset Button Operation
If the burner is in the
below state:
Pushing the reset button will:
Button Click
(press < 1 second)
Button Hold
(press > 1 second)
Button Hold
(press 15+ seconds)
Lockout Reset from Soft Lockout Reset from Restricted (Hard)
Lockout
Valve-on Delay, Trial for
Ignition, Ignition Carryover
Go to Pump Prime (see
“Priming the Pump” above)
Disable the Burner:
Any time the burner is running,
press and hold the reset button
to disable the burner. The
burner will remain off as long
as the button is held.
Enables Pump Priming:
After the reset button has been
held for 15 seconds, the button
can then be clicked during the
next ignition sequence to enter
Pump Prime mode.
Run (igniter is shut off) No action
Motor-Off Delay,
Standby No action
Pump Prime No action Exit Pump Prime mode and return to Standby
Table 3 - Status Lights
Light Color On Continuously Flashing
Red Restricted (Hard) Lockout Soft Lockout
Green Flame Sensed during normal operation (Could
be stray light during standby) Recycle
Yellow Control is in Pump Prime mode or
Reset button currently held for 15+ seconds. N/A
Reset Button Operation
Table 2 explains what action the control will take when the reset button is pressed for different lengths of time during
the various burner operating states.
Section: Burner Controls

15
SF/SM Burner Manual
RECYCLE. If the flame is lost while the burner is
firing, the control shuts down the burner, enters
a 60 second recycle delay, and then repeats the
above ignition sequence. If flame is lost three
times in a row, the control locks out to prevent
cycling with repetitious flame loss due to poor
combustion.
BURNER MOTOR-OFF DELAY. The fuel valve
is closed and the burner motor is kept on for the
selected motor-off delay time before the control
returns the burner to standby.
7.
8.
Figure 10. Typical Burner Wiring & Burner Sequence of Operation for R7184 Control.
Refer to the appliance manufacturer’s wiring diagram for actual specifications.
STANDBY. The burner is idle, waiting for a call for
heat. When a call for heat is initiated, there is a 3-
10 second delay while the control performs a safe
start check.
VALVE-ON DELAY. The ignition and motor are
turned on for a 15 second valve-on delay.
TRIAL FOR IGNITION (TFI). The fuel valve is
opened. A flame should be established within the
15 second lockout time.
LOCKOUT. If flame is not sensed by the end
of the TFI, the control shuts down on safety
lockout and must be manually reset. If the control
locks out three times in a row, the control enters
restricted lockout.
IGNITION CARRYOVER. Once flame is
established, the ignition remains on for 10
seconds to ensure flame stability before turning
off. If the control is wired for intermittent duty
ignition, the ignition unit stays on the entire time
the motor is running.
RUN. The burner runs until the call for heat is
satified. The burner is then sent to burner motor
off delay, if applicable, or it is shut down and sent
to standby.
1.
2.
3.
4.
5.
6.
Feature Interrupted
ignition
Limited reset,
Limited recycle
Valve-on
delay
Burner motor off
delay
Alarm
Contacts
R7184A YES YES — — —
R7184B YES YES YES — —
R7184P YES YES YES YES Optional
Control System Features
VALVE-ON
DELAY
STANDBY
TRIAL FOR
IGNITION
IGNITION
CARRYOVER
RUN
LOCKOUT
RECYCLE
MOTOR-OFF
DELAY
1
234
5
6
8
7
Section: Burner Controls

16
Start Up Burner/Set
Combustion
Explosion and Fire Hazard
Failure to follow these instructions could
lead to equipment malfunction and result
in heavy smoke emission, soot-up, hot
gas puff-back, fire and asphyxiation
hazards.
Do not attempt to start the burner when excess oil
has accumulated in the appliance, the appliance is
full of vapor, or when the combustion chamber is
very hot.
Do not attempt to re-establish flame with the burner
running if the flame becomes extinguished during
start-up, venting, or adjustment.
Vapor-Filled Appliance: Allow the unit to cool off
and all vapors to dissipate before attempting another
start.
Oil-Flooded Appliance: Shut off the electrical
power and the oil supply to the burner and then clear
all accumulated oil before continuing.
If the condition still appears unsafe, contact the Fire
Department. Carefully follow their directions.
Keep a fire extinguisher nearby and ready for use.
y
y
y
y
y
y
partially open air shutter. This is an initial air setting
for the pump bleeding procedure only. Additional
adjustments must be made with instruments to prevent
smoke and carbon monoxide generation.
Set the thermostat substantially above room
temperature.
Close the line voltage switch to start the burner. If the
burner does not start immediately you may have to
reset the safety switch of the burner primary control.
Bleed air from fuel unit as soon as burner motor starts
rotating.
To bleed the fuel unit, attach a clear plastic hose
over the vent fitting. Loosen the fitting and catch the
oil in an empty container. Tighten the fitting when all
air has been purged from the oil supply system.
If the burner locks out on safety during bleeding,
reset the safety switch and complete the bleeding
procedure. Note — Electronic safety switches can
be reset immediately; others may require a three- to
five-minute wait.
If burner stops after flame is established, additional
bleeding is probably required. Repeat the bleeding
procedure until the pump is primed and a flame is
established when the vent fitting is closed.
For R7184 primary controls, see Technician’s Quick
Reference Guide, part number 61351 for special
pump priming sequence.
For 7505 primary controls, see Technician’s Quick
Reference Guide, part number 61666 for special
pump priming sequence.
Prepare for combustion tests by drilling a ¼”
sampling hole in the flue pipe between the appliance
and the barometric draft regulator.
Initial air adjustment — Test the flue gas for smoke.
Adjust the air shutter (and air band, if necessary) to
obtain a clean flame. Now the additional combustion
tests with instruments can be made.
Cad Cell Resistance Measurement
If the Beckett 7505 control is equipped with the
GeniSys Display Module, part 52067U, the cad cell
resistance can be selected and read on the LCD
screen. Also, the GeniSys Contractor Tool, part
52082U, can be used for this purpose.
If these are not available, the cad cell leads can
be unplugged from the control and the resistance
measured with a meter in the conventional way.
Conduct these tests with flame present.
Flame Detection Range
Normal = 0 to 1600 ohms
Limited = 1600 ohms to lockout
Resetting From Restricted or Hard Lockout
If the control continues to lockout without a satisfied
call for heat, or fails the motor relay check, the control
3.
4.
5.
○
○
○
○
○
○
6.
○
○
○
Section: Start-up Burner/Set Combustion
Wire Burner
Some Thermostats Are Polarity
Sensitive. Reversed polarity
could cause erratic cycling of the burner control.
Connect the wire from the RHor R terminal on the
thermostat to the TR terminal on the control. Connect
the wire from the W terminal on the thermostat to the TW
terminal on the control.
Make connections to the control’s terminals as
shown in Figures 9a and 9b. Refer to the label on
the underside of the control for wiring details.
Note: Motor-off delay on a 7505P will be disabled if
the safety and operating limits as shown in Figures
9a and 9b interrupt power to the control terminal L1.
Connect thermostat leads to the TR and TW
terminals on the control or jumper the TR and TW
terminals on the control, as directed by the appliance
wiring diagram.
- Thermostat anticipator Current: 0.1 amp
- Thermostat voltage: 24 volts AC
Note that if the thermostat short cycles or operates
improperly, it may require an isolation relay for proper
operation. The Beckett A/C Ready Kit (part no. 51950U)
provides this function. Wiring instructions are included with
the A/C Ready Kit.
○
○
○
Open the shutoff valves in the oil supply line to the
burner.
If the air control is not preset, close air band and
1.
2.

17
SF/SM Burner Manual
OIL-BURNING EQUIPMENT
SHALL BE CONNECTED
TO FLUES HAVING SUITABLE PRESSURE
(DRAFT) AT ALL TIMES TO ASSURE SAFE
AND PROPER OPERATION OF THE BURNER.
enters Hard (restricted) Lockout in order to limit
accumulation of unburned oil in the combustion
chamber.
To reset, hold the button down for 15 seconds until
the red light turns off and the yellow light turns on.
Always verify the control functions according to all
specifications before leaving the installation site.
Replace the control if it does not operate as
specified.
Startup / Checkout
○
○
○
After flame is established and the burner igniter
turns off, close the hand valve in the oil supply line.
At flame loss, the control will enter Recycle mode.
Verify that the green light is flashing. The control
will remain in Recycle for 60 seconds.
After the 60 second recycle period, the control will
try to restart the system.
After the 15 second lockout time, the control will
lock out the burner and the reset button will flash.
Verify that the burner motor and igniter are off and
that the burner oil solenoid valve (if used) is not
energized.
Open the hand valve in the oil line.
Click the reset button and verify that the red light in
the reset button shuts off and that the burner lights.
End the call for heat.
Before leaving the installation, verify that all
thermostat and boiler/furnace control wiring is
correct. Consult heating appliance manual for
directions.
Set combustion with instruments
2.
3.
4.
5.
6.
7.
8.
○
Section: Start-up Burner/Set Combustion
Do not attempt to start the burner when excess oil
has accumulated in the appliance, the appliance is
full of vapor, or when the combustion chamber is
very hot.
Do not attempt to re-establish flame with the burner
running if the flame becomes extinguished during
start-up, venting, or adjustment.
Vapor-Filled Appliance: Allow the unit to cool off
and all vapors to dissipate before attempting another
start.
Oil-Flooded Appliance: Shut off the electrical
power and the oil supply to the burner and then clear
all accumulated oil before continuing.
If the condition still appears unsafe, contact the Fire
Department. Carefully follow their directions.
Keep a fire extinguisher nearby and ready for use.
y
y
y
y
y
y
Failure to follow these instructions could
lead to equipment malfunction and result
in heavy smoke emission, soot-up, hot
gas puff-back, fire and asphyxiation
hazards.
Explosion and Fire Hazard
If the burner or control fails any of the following tests,
recheck control wiring. If the burner or control still fails
any tests, replace the control.
Check Safety Features
Safe Start Check
Place a jumper across the cad cell terminals.
Refer to the steps for “Start up burner/set
combustion” and have the system call for heat.
Burner must not start. Verify that the green light
is on continuously and that the control remains in
Standby mode.
End the call for heat and remove the cad cell
jumper.
Simulate Flame Failure and Ignition Failure
Refer to the steps for “Start up burner/set
combustion” and have the system call for heat.
○
1.
2.
3.
4.
○
1.
Allow the burner to run for approximately 5 to 10
minutes.
Set the stack or over-fire draft to the level specified
by the appliance manufacturer.
Natural Draft Applications; typically over-fire
draft is -0.01” or -0.02” w.c.
Direct Venting; typically may not require draft
adjustment.
High Efficiency/Positive Pressure Appliances;
also vary from traditional appliances (see
manufacturer’s recommendations).
Follow these four steps to properly adjust the
burner:
Step 1: Adjust the air shutter/band until a trace of
smoke is achieved.
Step 2: At the trace of smoke level, measure the
CO2(or O2) . This is the vital reference
point for further adjustments. Example:
13.5% CO2(2.6% O2)
Step 3: Increase the air to reduce the CO2by 1.5 to
2 percentage points. (O2will be increased
by approximately 2.0 to 2.7 percentage
points.) Example: Reduce CO2from
13.5% to 11.5% (2.6% to 5.3% O2).
1.
2.
○
○
○
3.

18
CENTER WHEEL FOR EQUAL
DISTANCE FROM HOUSING SIDES
Section: Perform Regular Maintenance
ALWAYS KEEP THE FUEL
OIL SUPPLY VALVE SHUT
OFF IF THE BURNER(S) IS SHUT DOWN
FOR AN EXTENDED PERIOD OF TIME.
Perform Regular Maintenance
Clean the blower wheel, air inlet, air guide, burner
housing and static plate of any lint or foreign
material.
If motor is not permanently lubricated, oil motor with
a few drops of SAE 20 nondetergent oil at each oil
hole. DO NOT over oil motor. Excessive oiling can
cause motor failure.
Check motor current. The amp draw should not
exceed the nameplate rating.
Check all wiring for secure connections or insulation
breaks.
Check the pump pressure and cutoff function.
Check primary control safety lockout timing.
Check ignition system for proper operation.
Inspect the vent system and chimney for soot
accumulation or other restriction.
Clean all flue passages and flue pipe. Replace
corroded or damaged pipes.
Clean the appliance thoroughly according to the
manufacturer’s recommendations.
Check the burner performance. Refer to the section
“Set combustion with test instruments”.
It is good practice to make a record of the service
performed and the combustion test results.
Shutting the Burner Off
□
□
□
□
□
□
□
□
□
□
□
□
Turn off all electric power to the burner.
Note: There could be more than one disconnect switch.
Replacing the blower wheel:
When replacing the blower wheel, insure that the wheel
is centered between the two sides of the burner housing
as shown below.
Annual Professional
Service Required
Tampering with or making incorrect
adjustments could lead to equipment
malfunction and result in asphyxiation,
explosion or fire.
DO NOT TAMPER WITH THE UNIT OR
CONTROLS - CALL YOUR QUALIFIED SERVICE
TECHNICIAN OR SERVICE PERSONNEL.
To ensure continued reliable operation, a qualified
service technician must service this burner annually.
More frequent service intervals may be required in
dusty or adverse environments.
Operation and adjustment of the burner requires
technical training and skillful use of combustion test
instruments and other test equipment.
y
y
y
y
Replace the oil supply line filter. The line filter
cartridge must be replaced to avoid contamination
of the fuel unit and nozzle.
Inspect the oil supply system. All fittings should be
leak-tight. The supply lines should be free of water,
sludge and other restrictions.
Remove and clean the pump strainer if applicable.
Replace the nozzle with the exact brand, pattern,
gph flow rate and spray angle..
Clean and inspect the electrodes for damage,
replacing any that are cracked or chipped.
Check electrode tip settings. Replace electrodes if
tips are rounded.
Inspect the igniter spring contacts.
Clean the cad cell lens surface, if necessary.
Inspect all gaskets. Replace any that are damaged
or would fail to seal adequately.
Inspect the combustion head and air tube. Remove
any carbon or foreign matter. Replace all damaged
units with exact parts.
□
□
□
□
□
□
□
□
□
□
Step 4: Recheck smoke level. It should be Zero.
-This procedure provides a margin of
reserve air to accommodate variable
conditions.
-If the draft level has changed, recheck
the smoke and CO2levels and readjust
the burner, if necessary
Once combustion is set, tighten all fasteners on air
band, air shutter and escutcheon plate.
Start and stop the burner several times to ensure
satisfactory operation. Test the primary control
and all other appliance safety controls to verify
that they function according to the manufacturer’s
specifications.
4.
5.
Figure 10. Blower Wheel Assembly

19
SF/SM Burner Manual
# Part No. Description
1 Burner Housing Assembly with Inlet
Bell
2 3215 Air shutter, 10 Slot
3 3819 Bulk Air Band, 10 Slot
4 3493 Nozzle-line Escutcheon Plate
5 Specify **
3399
Unit Flange or
Square Plate
3416 Air Tube Gasket (not shown)
6 2139 Hole Plug - Wiring Box
7 2900U
2364U
Drive Motor, 1/5 HP (SM Models)
Drive Motor, 1/4 HP (SF Models)
8 2383U Blower Wheel (6-1/4 X 3-7/16)
9 2433 Flexible Coupling (Fits 5/16” pump
shaft)
10
2591U
21188U
Fuel Units SF only
Single-Stage ‘A’
Two-Stage ‘B’
10
2184404U
2460
Fuel Units SM only
CleanCut
Single-Stage ‘A’
2256 Pump outlet fitting (not shown)
482 Pump holding screws (not shown)
13 5394 Connector tube assembly, pump to
nozzle line
# Part No. Description
14 51824U Igniter and Base Plate
14 2289U Ignition Transformer (10,000 V/23mA)
15 7505A Replaces R7184A - Interrupted Ignition
7505B Replaces R7184B - Pre-time
7505P Replaces R7184P - Pre and Post-time
16 5770 Electrical Box
17 7006U Cad Cell Detector
18 Specify ** Air Tube Combination
19
5780 Electrode Kit - F Head up to 9”
5782 Electrode Kit - F Head over 9”
20 5432
3616
Universal Flange w/ Gasket
Gasket Only
21 3666 Splined Nut
22 2182602U Blocking Oil Solenoid Valve
23 5685 Base Pedestal Kit
** Contact your Beckett Representative for part number
and pricing.
For best performance specify genuine Beckett replacement parts
Section: Replacement Parts
Replacement Parts
20
18
19
14
15
16
17
5
6
1
23
87
3
9
10 2
13
21
22
4

USA: P.O. Box 1289 ●Elyria, Ohio 44036
Canada: R.W. Beckett Canada, Ltd. ●Unit #3, 430 Laird Road ●Guelph, Ontario N1G 3X7
www.beckettcorp.com
Part Number 6104 BSF/SM R06, Printed in the U.S.A. 05/10
The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its “Products” from
Beckett for resale, or for incorporation into a product for resale (“Customers”), that its equipment is free
from defects in material and workmanship. To qualify for warranty benefits, products must be installed by a
qualified service agency in full compliance with all codes and authorities having jurisdiction, and used within
the tolerances of Beckett’s defined product specifications.
To review the complete warranty policy and duration of coverage for a specific product, or obtain a written
copy of warranty form 61545, please choose one of the following options:
Visit our website at: www.beckettcorp.com/warranty
Write to: R. W. Beckett Corporation, P. O. Box 1289, Elyria, OH 44036
NOTE: Beckett is not responsible for any labor cost for removal and replacement of equipment.
THIS WARRANTY IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE, AND PROVIDES
EXCLUSIVE REMEDIES EXPRESSLY IN LIEU OF ALL OTHER REMEDIES, AND IN PARTICULAR
THERE SHALL BE EXCLUDED THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE. IN NO EVENT WILL BECKETT BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGE OF ANY NATURE. Beckett neither assumes, nor authorizes any person to
assume for Beckett, any other liability or obligation in connection with the sale of this equipment. Beckett’s
liability and Customer’s exclusive remedy is limited to the cost of the product.
1.
2.
3.
Limited Warranty Information
Other manuals for SF
1
This manual suits for next models
1
Table of contents
Other Beckett Burner manuals

Beckett
Beckett CG15 User manual

Beckett
Beckett CF1400 User manual

Beckett
Beckett AF User manual

Beckett
Beckett AF Series User manual

Beckett
Beckett NX50LG User manual

Beckett
Beckett SDC 24 VDC User manual

Beckett
Beckett SF Series User manual

Beckett
Beckett CG10 User manual

Beckett
Beckett AFII 100 User manual

Beckett
Beckett AF User manual

Beckett
Beckett CG10 User manual

Beckett
Beckett CG15 User manual

Beckett
Beckett AFII 85 User manual

Beckett
Beckett NX User manual

Beckett
Beckett CF1400 User manual

Beckett
Beckett AF User manual

Beckett
Beckett NX User manual

Beckett
Beckett CF 2500 User manual

Beckett
Beckett CF 2300A User manual

Beckett
Beckett CF800 User manual