BELIMED WD230 User manual

Hospital Technician
Technical Manual
WD230 and WD250
Rev. 1.8 E
©Copyright by the manufacturer Belimed AG Ballwil,
Switzerland 2006
Art. No. 73018_E rev 1 8.doc

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 2 73018_E rev 1 8-Technical Manual.doc
TABLE OF CONTENT
! Important Note ! ........................................................................................................................4
1. Machine Dimensions .......................................................................................................5
1.1 Performance Data ........................................................................................................5
2. Connections .....................................................................................................................6
2.1 Plumbing ......................................................................................................................6
2.2 Steam...........................................................................................................................6
2.3 Exhaust Air...................................................................................................................7
2.4 El. Connected Load......................................................................................................7
2.5 Connecting Conditions .................................................................................................8
3. Maintenance Items...........................................................................................................9
4. Service Programs ..........................................................................................................13
4.1 Input Modules for Servicing........................................................................................13
4.1.1 General Key Functions Service Module.............................................................13
4.1.2 Access Authorization .........................................................................................13
4.1.3 Access to Service Module .................................................................................14
4.1.4 Service assignments: Opening of both doors ....................................................14
4.1.5 Overview Service Module ..................................................................................15
4.2 Analysis Module (1 Analysis) .....................................................................................17
4.2.1 Actual values temperature sensor NTC.............................................................17
4.2.2 Level sensor ......................................................................................................17
4.2.3 Validating mode! ................................................................................................18
4.3 Dosing Module (2 Dosage) for Dosing Agent Manufacturers.....................................19
4.3.1 Simultaneous dosing from several dosing units: Mix dosing .............................20
4.3.2 Calibration of Dosing Pump (Time)....................................................................21
4.3.3 Calibration of Flow Meters (Impulse) .................................................................21
4.4 Direct Control Module (3 Control) for Service Technicians Hospital .........................22
4.5 Parameter Module (4 Parameter) ..............................................................................22
4.5.1 Overview Parameter Input .................................................................................24
4.5.2 M1 medium CW for cold water cycle .................................................................25
4.5.3 M2 medium WW for warm water cycle ..............................................................26
4.5.4 M3 medium CW + WW mix water cycle.............................................................26
4.5.5 M4 medium DI water cycle.................................................................................26
4.5.6 M5 medium hot air (dry).....................................................................................26
4.5.7 M6 condenser functions.....................................................................................26
4.5.8 M9 pre-heated DI water (final rinse) ..................................................................26
4.5.9 F0 function step inactive ....................................................................................27
4.5.10 F1 – F5, F8 and F 9, FD, FE function display..................................................27
4.5.11 F6 and F 7 thermal disinfection or chemical disinfection ...................................27
4.5.12 FA Thermal disinfecting AO= 3000....................................................................27
4.5.13 FB Thermal disinfecting AO= 600......................................................................28
4.5.14 FF and FE, empty ..............................................................................................28
4.6 Configuration Module 1 (5 Configuration) ..................................................................29
4.6.1 Timer for self-disinfection / DI tank drainage .....................................................29

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 3 73018_E rev 1 8-Technical Manual.doc
4.6.2 Maintenance Warning........................................................................................29
4.6.3 Naming Automat ................................................................................................29
4.6.4 Input Door Pressure...........................................................................................29
4.6.5 Suppressing liquid drainage acc. ∫18 ISSG Infection protection law (BGA / RKI)30
4.6.6 Automatic Program Recognition ........................................................................31
4.6.7 Display and Message in case of error. ..............................................................31
4.6.8 At Program end, CS door opens automatic .......................................................32
4.6.9 Door Interlock Unclean Side: .............................................................................32
4.6.10 User Identification ..............................................................................................32
4.6.11 Automatic Rack Identification ............................................................................33
4.6.12 Input batch content on or off ..............................................................................33
5. Printouts .........................................................................................................................34
6. Hardware Configuration................................................................................................35
6.1 Outputs.......................................................................................................................35
6.2 Inputs .........................................................................................................................36
6.2.1 SA Load cut-off (external)................................................................................37
6.2.2 SB Leakage Floor Pan.....................................................................................37
6.2.3 SC DI Boiler Code ...........................................................................................37
6.2.4 SD Float Switch DI Boiler ................................................................................37
6.2.5 SE Door US open ............................................................................................37
6.2.6 SF Door CS close ............................................................................................37
6.3 Temperature Sensor ..................................................................................................38
6.4 Interfaces ...................................................................................................................38
6.4.1 Bach documentation system Sauter ICS 8535 / 8565 .......................................38
6.4.2 Telegram assignment to Bach documentation system Sauter...........................39
6.4.3 Overview for Interface as Modem, Printer and Scanner ....................................40
7. Loading of new SW in Control Unit..............................................................................41
8. Errors with Process Interrupt and their Remedy........................................................43
8.1 Procedure in case of malfunction...............................................................................43
8.2 Color Code of Low Voltage Circuits ...........................................................................43
8.3 Error code / Error chart / Remedy ..............................................................................44
9. Cycle value and process variables of Factory Settings.............................................53
9.1 Process Time .............................................................................................................53
9.2 Water consumption and Electrical Energy .................................................................53
9.3 Validated Process Parameters P1 – P7.....................................................................53
9.4 Assignment of respective media ................................................................................53
9.5 Overview Factory Settings ........................................................................................54
9.6 P1 Alkaline Cleaning of Instruments .........................................................................56
9.7 P2 Alkaline intensive Cleaning of Instruments ...........................................................57
9.8 P3 Alkaline Cleaning of anesthetic Material...............................................................58
9.9 P4 Neutral Cleaning of Containers.............................................................................59
9.10 P5 Alkaline Cleaning of MIC Instruments...................................................................60

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 4 73018_E rev 1 8-Technical Manual.doc
9.11 P 6 Additional Drying..................................................................................................61
9.12 P7 Alkaline Cleaning of OP Shoes.............................................................................62
10. Functional and Electro Schematics .............................................................................63
10.1 Function Diagram Dosing...........................................................................................65
Edition
Rev. 1.4 September 2002 Pf / Software Index Rev. 1.04
Rev. 1.5 January 2003 Pf / Software Index Rev. 2.00
Rev. 1.6 January 2004 Pf / Software Index Rev. 2.01
Rev. 1.7 January 2005 Pf / Software Index Rev. 2.02
Rev. 1.8 Mai 2006 Pf / Software Index Rev. 2.03
Manufacturer:
Belimed AG
Dorfstrasse 4
CH-6275 Ballwil (Switzerland)
Phone: +41 41 449 78 88
Fax: +41 41 449 77 76
E-mail: [email protected]
! Important Note !
Please, carefully study this operation manual BEFORE starting the automat.
The manufacturer waives all responsibility for damages resulting from improper han-
dling or failure to follow instructions offered in this manual. Any changes made on the
automat, especially technical modifications performed without the written consent by
the manufacturer by non-authorized personnel will result in loss of product liability
rights.
The user has to check each time the cleanness of the instruments and is re-
sponsible for it

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 5 73018_E rev 1 8-Technical Manual.doc
1. Machine Dimensions
Type Door Machine Dimen-
sions
Max. Load
WD 230 Manual 900 / 800 / 1840 10 – 12 DIN sieves
WD 250 Automatic 900 / 800 / 1840 10 – 12 DIN sieves
Dimensions WD 230 / 250
Basket dimension height 670 mm
Basket dimension width 610 mm
Basket dimension depth 610 mm
Door opening height net / gross 670 / 690 mm
Door opening width net / gross 610 / 630 mm
Chamber opening depth 660 mm
Outside dimension height 1840 mm
Outside dimension width 900 mm
Outside dimension depth 800 mm
Lad height 870 mm
Base height 100 mm
1.1 Performance Data
Performance Characteristics / Components WD 230 / 250
Heat radiation free standing 900 (+/- 200) W
Weight of side covers 270 Kg
Noise emission with side covers installed 62 dB(A)
WD 250: door opens from top to bottom Automatic
WD 250: with safety shut-off Tape switch
Material: Frame, Panels, Covers CNS 1.4301, AISI = 304*
Material: Wash camber, Door CNS 1.4404, AISI 316L **
Material: Stainless steel (CNS) 1.4301
Wash pump capacity nominal 900 l / min
Wash pump capacity operating level 750 l / min
Wash pump electric power rating 1100 W
Material impeller wheel CNS
Tank heater power rating 15 kW
Tank heater power steam heat (2.5 bar) 30 kW
Wash arm length 580 mm

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 6 73018_E rev 1 8-Technical Manual.doc
Drain valve made of CNS 17 W DN 50
Dosing pump (Sair brand) voltage 24 V AC
No. of dosing pumps basic model 2 units, (max. 5)
Flow meter Optional (max. 5 units)
El. dryer connected load 10.5 kW
Steam drying, power steam and pure steam 16 kW at 3 bar
Dryer blower el. power (2 brush-less DC tur-
bines)
2.4 kW
Exhaust air throughput dryer 320 m 3/ h
Air filter: Filter class H13 EN 1822, retaining effi-
ciency with particle size from 0.1 to 0.2 μm
99.95%
Powered separator flap water / air 24 V DC
Processor
Mitsubishi M16C M306NOFG - Processor with 256 K Byte EEPROM (Program and pa-
rameter memory) and 10 K Byte RAM (Data memory)
2. Connections
2.1 Plumbing
Cold Water Connection 3/4 “
CW and WW Water pressure 200 - 600 kPa
Volume rating 40* l/min
*at water pressure of 2.2 bar
DI Water Connection 3/4 “
DI Water pressure 200 - 600 kPa
Volume rating* 40 l/min
Minimal volume rating 8 l/min
Recommended conductivity < 30 μS/cm
Drain Connection stud DO 56 mm
AB Temperature, max. 90 °C
PH value 5 - 12 pH
2.2 Steam
Steam Connec-
tion
Machine side R ½“
Pressure range 200 - 600 kPa
Steam temperature 133 - 165 °C
Water heating Saturated steam consumption 0.8 kg / min.
Consumption / batch at 3 bar 12-16 kg
Dryer heating Saturated steam consumption 0.45 kg / min.
Consumption / batch for 10
min.
4.5 Kg at 3 bar

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 7 73018_E rev 1 8-Technical Manual.doc
2.3 Exhaust Air
Exhaust Air Conn. Machine side duct DO 115 mm
Without condenser Exhaust air volume, drying 300 - 500 m3/h
Exhaust air temperature 60 - 90 °C
With condenser Exhaust air volume, drying 150 - 260 m3/h
Exhaust air temperature 30 - 60 °C
2.4 El. Connected Load
EU, AU,
PRC,
NZ
USA, CA JP JP
Voltage
Frequency
400V 3N AC
50 Hz
208V 3
A
C
60 Hz
200-220V 3
AC
50 Hz
200-220V 3
AC
60 Hz
Electrical water heating
Connected load total
Fusing
16 kW
25 A
13 kW
30 A
16 kW
40 A
16 kW
40 A
Water heating steam
Connected load total
Fusing
13 kW
20 A
13 kW
30 A
13 kW
30 A
13 kW
30 A
Water heating steam and
stem dryer
Connected load total
Fusing (without DI Tank)
3.5 kW
16 A
3.5 kW
16 A
3.5 kW
16 A
3.5 kW
16 A

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 8 73018_E rev 1 8-Technical Manual.doc
2.5 Connecting Conditions
Building side requirements Machine side delivery
CW, WW, DI water connections
Shut-off valve 3/4" 2.1 m armored hose
Fine filter 3/4" Mesh gauge 250μ
Free flow area
AB Drain
Floor drain 90 °C heat resistant
Drain stub DO 56 mm
T-piece for condensate drain
KD = DO 28 mm
Siphoned drain hose DI 56 mm
AL Exhaust Air
Exhaust duct DO 115 mm Exhaust duct DO 114 mm DI 109 mm
Exhaust hood not required Condensate water collector with drain
Exhaust air flap with ambient air opening
EL Electro Connection All pole main switch 52A
50 Hz 400 V 25 Amp 3P+N model cable L = 3 m, 5 x 2.5 mm 2, H o5 RN - F
60 Hz 208 V 30 Amp 3P model protective hose G16 L = 1.3 m, cable 3,5 m 4
x 4 mm 2
60 / 50 Hz 200 V 40 Amp 3P model cabeL = 3,5 m, 4 x 6 mm 2
DO Steam Connection
2 T-piece ½“ 1 2/2 way magn. valve ½“ (24 VAC)
2 Condensate separators ½“ 2 welding sleeve ½“
2 Shut-off valves ½“
1 Dirt separator ½“
(Protection device) Relief vent flap 7
bar
There is no need for compressed air supply.

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 9 73018_E rev 1 8-Technical Manual.doc
3. Maintenance Items
Clamp Connections
Check hose clamps for leaks and clamping torque, retighten if needed, replace clamps if
defective. EPDM hose clamps must be replaced if brittle.
Drying System
Dryer system components must be checked for performance and leaks. The entire sys-
tem needs to be thoroughly cleaned periodically. Check air hoses for cracks and other
errors. This switch serves to shut down the heater power (K18) in case of insufficient
blower efficiency.
.
Option pressure differential for blower unit
When reaching a pressure differential of 1.7 k Pa (17 m bar), air filters have arrived at
the end of their usefulness and “filter replace” will be displayed.
Over time, the sealing system
on the heat box is getting
pushed out and need to be
returned to the original posi-
tion.Caution, there is a pres-
sure switch inside the heater
box (P18).
Replace main filter (77317)
after about 500 h of service,
pre-filter (74422) after about
300 h of service.

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 10 73018_E rev 1 8-Technical Manual.doc
Assembly of the blower box
Dosing System
Check dosing system for leaks and accuracy. The dosing hoses
should be replaced at each service cycle. Check connection el-
bows of wash chamber for leaks and hose connections for clamp-
ing torque of clamps. At each maintenance cycle or replacement
of a safety related component, system needs to be recalibrated.
Frequency: min. once per year!
The dosage system must be newly calibrated after every mainte-
nance service or every change of detergents!
Flow Meter (Option)
The flow meters must be regularly checked for their proper func-
tion. The number of pulses of water is approximately 4000 beats
per liter.
Water Intake Valves
The water intake valves must be checked for connection safety and throughput capacity.
In case of improper tightness, valves must be replaced. The valve pre-filters must be
cleaned or replaced if damaged.
Recoil Cap at Entry of Water
Due to hygienic reasons, the silicone barrier should be checked regularly at the entry of
water. In case of discoloration, the silicon barrier ought to be changed (Item No 74146).

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 11 73018_E rev 1 8-Technical Manual.doc
Wash System
Check wash system for impurities, remove foreign objects and clean. Check and clean
water jets of wash arms and docking ports.
Function check of sleeves and retaining springs of water docking ports.
Make sure that bearing rings of wash arms are in good condition, replace if needed.
Check drain valve and re-circulation pump for proper function and leaks.
Cleaning of Wash Arms
The wash arms must be cleaned and bone rests removed after every maintenance ser-
vice. Possibly, the wash arm bearing must be removed in order to facilitate the proce-
dure and to have better access. The plastic bearing can be opened, as shown below,
counterclockwise to the wash arm.
Check valve
Does the check valve Opens?

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 12 73018_E rev 1 8-Technical Manual.doc
Door
Check gear belt of door, adjust by means of door spanner if needed.
Functional check of entire door system.
Use mild detergent to clean door seal, coat with Silicon grease.
Door pressure: check linear motor for proper function.
Periodic maintenance is highly recommended for reasons of operational safety. Profes-
sional disassembly is required (Customer Service Belimed). The collection trough of in-
ner door must be given special attention. Hoses of door drainage must periodically be
replaced.
Electric Installation
Check entire electric installation (burn and melt traces). Replace damaged components.
Make sure that all plug and clamp connections are in good shape, replace suspicious
connections.
Temperature Monitoring System
The sensors and limiters of the temperature monitoring system must be checked for
proper function. Damaged or visibly altered components must be replaced.
Find itemized maintenance. Thus, efficient and comprehensive maintenance service is
assured.
Remove housing and check
seal. Remove orange color
air hose and check for leaks
following several water cy-
l
Check leak water return
hose for brittleness .

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 13 73018_E rev 1 8-Technical Manual.doc
4. Service Programs
4.1 Input Modules for Servicing
4.1.1 General Key Functions Service Module
Legend
1- 4 <Arrow keys>
1. Print operational data such as program recipe
and setup data.
Activate self-disinfection ON / OFF
Activate Process verification IPD = ON / OFF
(If Option IPD is connected, verification may be
activated).
2. Beeper ON / OFF, at program end or in case of
error acoustic signal occurs.
3. Printer ON / OFF
4. Shift key programs P7 - 12
Program keys <PT> 1, 2, 3, 4, 5, 6
5. Selecting programs P 1-6, with shift P 7-12
6. Door button, door open / close.
With CS door open, beeper is activated with
door button
7. Reset and ON / OFF <IO> button respectively.
By pressing for 4 seconds, then releasing,
batch number and machine No. is shown.
Access to Service Module:
•5 push seconds <IO> 7 key then Query key sequence for 3-digit password (1 - 6)
Operations within the Input Modules:
•<Arrow keys> 1 and 2 effor cursor functions within the display window ◄►
•<Arrow keys> 3 and 4 dcfor scrolling within the respective input window ▼▲, at
time of exit, value is saved by means of cursor.
•With Door switch 6 to subsequent display No. or display window.
•Exit or move up to next level with IO 7.
4.1.2 Access Authorization
User Input Module Access
Dosing manufacturer 1 and 2 Password A
Hospital technician hospital 1, 2, 3, 4, 5.1 Password B
Service technician manufac-
turer
All modules Hardware Key

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 14 73018_E rev 1 8-Technical Manual.doc
4.1.3 Access to Service Module
Press <IO> 7 key for 5 seconds, followed by query key sequence for 3-digit
password (1-6)
Function Display / Input
Press IO key for 4 seconds, enter password
Keys 0-9, 3 digits
Password ?
XXX
Menu surface, over program key 1 - 6 access to
respective service module.
1. Analysis
2. Dosing
With Door key to next window
3. Access
4. Parameter
5. Configuration
4.1.4 Service assignments: Opening of both doors
Both doors may be opened by means of code input or by hardware key.
•Press <door switch> 6 of unclean side for 5 seconds in mode „Program
ready “.
•unclean side door opens
•Password is queried.
•Enter password while keeping door switch depressed
•Clean side door opens.
(Keep <door switch> depressed, even during password input)
When using hardware key, there is no password requirement.
W/out hard-
ware IO
press key for
4 seconds
Password ?
Input program
keys PT1 - PT6
1 Analysis
2 Dosage
3 Control
4 Parameter
5 Configuration
Password ?
Press Door
switch for 4 sec-
onds
Modem Connection
With hard-
ware key IO
press key for
4 seconds
6 Limits

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 15 73018_E rev 1 8-Technical Manual.doc
4.1.5 Overview Service Module
1. Analysis Module (1 Analysis)
The operating conditions can be analyzed with this mode.
•Query of a variety of current values (sensors, probes, inputs..), query only, no input
possible.
•Query last 10 error codes with respective date and program step.
•Interrogation no. of batches of programs 1-12.
•Operating hours air filter.
•Analysis possibility and water sample with step override.
•Testing rack recognition
2. Dosing Module (2 Dosage) for Dosing Unit
This mode is for the manufacturer of detergents.
•Display of recipes assigned to individual programs
•Input of dosing agent parameters in recipe
•Calibration Dosing pump and Impulse counter; query pulse values
3. Control Module (3 Control)
•Manual control of individual outputs.
4. Parameter Module (4 Parameter)
With this mode you can change or adjust the process parameter (program)
•Modification of recipe assisted by guiding mask (self-explanatory). The program se-
quence cannot be altered.
•Assignment of program name.
•Input of stored programs from program library.
•Modification of recipe: Program sequence may be chosen freely, i.e. any and all
combinations are possible. (not self-explanatory).
5.1 Configuration Modules 1 (5 Configuration)
With this mode you can change the Set Up attitudes of the machine.
•Self Disinfection

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 16 73018_E rev 1 8-Technical Manual.doc
•Service interval
•Operating hours air filter / resetting hour counter following replacement of air filter
•Modification of temperature unit (F or C)
•Time and date, unit
•Display and message in case of error such as „Tel No. Tech Service 154“
•Languages, German, French, Italian
•Signal K28 ON or OFF
•Pressing force of automatic door (only applicable with WD 250 and 290)
•DI boiler: input pre-heating and dwell time (option)
•1 or 2 door model (in case of wall installation)
•No draining in case of program interruption
•Automatic basket recognition ON or OFF (option)
•CS door opens automatic at program end on or off
•Door interlock for DS on or off
•User ID on or off
•Bach content Identification on or off
•Automatic rack ID by means of keypad on or off)
•CS door opens at program end
5.2 Configuration Module (only for service technicians manufacturer)
•Operating level wash pump
•Input empty level
•Duration drain pumping / draining following level 0.5 V until net step
•Definition door positioning (potentiometer values) only applicable with automatic
door
•Assigning potential-free output K28, K58, K59 (end of program, run, error, exhaust
flap)
•Assigning Bus No to ICS 8535 (communication to outside)
•Display type
•Post-cooling dryer
•Locking DI boiler ON / OFF (option)
•Dryer in case of steam / steam
•Drain water cooling ON / OFF (option)
•Altering password
•Input machine number
•Production date
•Last print exchange
•Input telephone number for modem connection
6. Limit Values Error Codes (only for service technicians manufacturer)
•Alteration of limit values

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 17 73018_E rev 1 8-Technical Manual.doc
4.2 Analysis Module (1 Analysis)
Function Display / Input
LED PT 1 illuminated
Software index, the automat may be started in this mode. With door
key, it is possible to continue selections in the current program. Us-
ing IO, the program is cut off, remaining in analysis module.
Analysis
Software index
V 1.0
4.2.1 Actual values temperature sensor NTC
NTC1 = Wash chamber NTC2 = Dryer
NTC3 = Empty (--- = empty) NTC4 = DI boiler (option)
T1= 45 °C T2= 25°C
T3= --- °C T4=---°C
According to Eur. Norm EN ISO 15883-1 (5.10.3), temperature indi-
cation must be independent of control system. NTC 5 = water wash
chamber is a monitoring sensor.
T5= 45 °C T6=---°C
Actual value temperature sensor 7- 10
PT 100 sensor (only with WD 270 / 290)
T7= 45 °C T8 =32 ° C
T9= 45 °C T10=32 ° C
4.2.2 Level sensor
L1, L2 actual values level sensors in V. Working level approx. 1.7V,
empty level 0.5V
PL, PR actual values in V
L1= 1.20V L2= 1.02V
PL= 0.00V PR= 0.00V
Actual values flow meter (optional)
Pulses
IMP1= 1234 IMP3=
1234
IMP2= 1234 IMP4=
1234
Display Input switch status (see chapter Inputs)
S 101 to S106 0 = open, 1 = closed
S1 01 02 03 04 05 06
1 0 0 1 0 1
Display Input switch status (see chapter Inputs)
S 107 to S112
S1 07 08 09 10 11 12
1 0 0 1 0 1
Display Input switch status (see chapter Inputs)
S 201 bis S206
S2 01 02 03 04 05 06
1 0 0 1 0 1
Display Input switch status (see chapter Inputs)
SA to SF
SA SB SC SD SE
SF
1 0 0 1 0 1
Call-up last 10 error codes with respective error code, program,
program step, date and time.
1: Error 111 P3 S2.1
13.12.2000 16:44
Error code
Error in program No.
In program step

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 18 73018_E rev 1 8-Technical Manual.doc
Batch Counter: display Batch number of programs 1-12 with
scroll keys cd. For example: with program 1, 5 batches were
processed.
Batch count
Prog. P1 5
Operating Hours: Display operating hours of air filter. Air filter
should be replaced after about every 500 operating hours (accumu-
lated drying time).
Op. Time Air Filter
15 h
Step Jump: Program selection with program keys PT1 - PT6
Selection of desired program step S1.1 to 4.2 with, scroll keys c
d, then start with c.
Step over
Program P1-P6 ?
Step over
S2.1 Start
4.2.3 Validating mode!
This module is suitable for validating the dosage. In this step the
actual dosing quantity is indicated in ml, which is to be tested while
validating.
Individual steps may be bypassed form the beginning.
By means of ↨door switch, draining action my be stopped, the door
opened to remove a water sample. Again using door key ↨, process
may be resumed.
The programmed dosage, the effectively proportioned amount addi-
tive in ml, the respective medium, target temperature and program
duration for respective step will be displayed.
P1 I▐▐▐▐____I 13
min
Cleaning 36 °C
Step over D1 = 124 ml
S2.1 M4 085°C
10min
Program step
Medium
Target temperature
Program duration

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 19 73018_E rev 1 8-Technical Manual.doc
4.3 Dosing Module (2 Dosage) for Dosing Agent Manufactur-
ers
Function Display / Input
Dosing Module LED PT 2 illuminated
Last change in dosing module
Dosage
Last mod. 13.06.2001
Display / Adjusting. Program selection P1-6 (7-12 with shift), then
dosing data input, otherwise jump dosing input by means of door
key. Jumps to display of calibration flow meter.
Display / Modify
Program Nr. P1-P6 ?
Display Program No. and Program Name Program No. 4
Instruments normal
Display of cleaning step 1.1, assignment dosing pump 1-5 and in-
put dosing agent volume in ml.
1.1 Pre-rinse 36 °C
00 min HT0 D15.0ml
Display of cleaning step 1.2, assignment dosing pump 1-5 and in-
put of dosing agent volume in ml.
1.2 Pre-rinse 36 °C
00 min HT0 D10.0ml
Display of cleaning step 2.1, assignment of dosing pump 1-5 and
input of dosing agent volume in ml.
2.1 Pre-rinse 00 °C
02 min HT0 D20.0ml
Display of cleaning step 2.2, assignment of dosing pump 1-5 and
input of dosing agent volume in ml.
2.2 Rinsing 60 °C
05 min HT0 D2 2.0ml
Calibration Dosing Pump 1. If no flow meters are connected,
Time must be set.
Calibration procedure see chapter 4.4 Calibration Dosing Pump
Start dosing pump for calibration with PT 1, dosing Pump runs 6
Minutes, Input measured amount of Liter.
Remaining time in seconds from 6 Minutes.
Doser 1Time
1.10 L/6Min 360
Calibration of Flow Meter 1. If flow meters are connected, Impulse
must be set.
Calibration procedure see chapter 4.5 Calibration Flow Meters
Start dosing pump for calibration with PT 1, if you reach 1 liter stop
with PT 1, push PT2 for transfer measured Impulses to control
Doser 1 Impulse
3700 Imp / L 2353
Actual values flow meters
Pulses saved
IMP1 1234 IMP3 1234
IMP2 1234 IMP4 1234
Testing automatic Rack Recognition Option:
This indication is active only in case of additional print.
In this mode, automatic rack recognition may be tested. Door opening is
enabled by button P1.
The display changes to „Rack No. –„ With door open, baskets may be in-
serted.
With „IO“ button, door may be closed again, operation reverts back to the
analytical mode.
Test Rack Ident Syst
Open Door with P1
Test Rack Ident Syst
Rack No. 12

Technical Manual WD 230 and WD 250
Rev. 1.8 PF Page 20 73018_E rev 1 8-Technical Manual.doc
4.3.1 Simultaneous dosing from several dosing units: Mix
dosing
Programming the programs:
Without Mix Dosing / Doser 1 = 2.6 ml/L
P1S2_035°00M-060°05M
F2M3_D1=2.6L-D1=0.0L
With Mix Dosing A = D1=5.0 ml D2=3.0 ml
P1S2_035°00M-060°05M
F2M3_DA=0.0L-D1=0.0L
Using Mix Dosing, per phase maximum 4 detergents may be dosed
with appropriate concentration.
If in doing unit D, instead of a number a letter from A – F is entered,
mix doing is activated. To each letter, a maximum of 4 concentra-
tions may be assigned. The software activates a maximum of 2
dosing units simultaneously (otherwise, max. safety is exceeded).
MIX D1:=5,0ml
D2=3,0ml
A D3= 0,0ml D4=
0,0ml
Other manuals for WD230
1
This manual suits for next models
1
Table of contents
Other BELIMED Rack & Stand manuals
Popular Rack & Stand manuals by other brands

ShelterLogic
ShelterLogic Rack-in-a-Box Ultra-Duty 90475 Assembly instructions

Vivo
Vivo Mount-E-FD55 instruction manual

American Recorder
American Recorder AllCast MULTI-FUNCTION MONITOR STAND manual

Hama
Hama 118490 operating instructions

HAGOR
HAGOR CON-Line FS Lift 55-75 installation manual

E.N.Z. Engineering
E.N.Z. Engineering Ricoo TS0211 Assembly instructions