Technical data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage ......................................................400 V
Overvoltage category/ pollution degree..............................4 kV /III
Protective separation (reinforced insulation) between................
............................... (A1, A2) - (E/KE) - (11, 12, 14) - (21, 22, 24)
Voltage test acc. to IEC 61010-1
(E, KE) - [(A1-A2), (11-12-14)]........................................ 3.32 kV
(E, KE) - (21-22-24) ........................................................ 2.21 kV
(A1- A2) - (11-12-14) - (21-22-24)................................. 2.21 kV
Supply voltage
GM420-D-1
Operating range US...................... AC 16…72 V / DC 9.6…94 V
Frequency range US...........................................DC, 42…460 Hz
GM420-D-2
Operating range US........................................ AC/DC 70…300 V
Frequency range US ............................................... 15…460 Hz
Power consumption.......................................................≤ 3.5 VA
Measuring circuit
Loop resistance Rm
Measuring range Rm.................................................. 0…100 Ω
Measuring current Im....................................................DC 20 mA
Measuring voltage Um............................................... ≤ DC 24 V
Extraneous voltage Uf
Measuring range Uf................................................. AC 0…50 V
Nominal frequency fn ............................................ 42…460 Hz
Disconnection of the measuring loop Uf......................... ≥ 12 V
Reclosing of the measuring loop .....................................≤ 10 V
Permissible extraneous voltage Uf.................................≤ 440 V
Permissible extraneous DC voltage,
without influence on the measurement ......................... DC 0 V
Switching elements
Number of switching elements............ 2 x 1 changeover contact
Operating principle...........N/C operation / N/O operation (N/O)*
Electrical endurance.........................10000 switching operations
Contact data acc. to IEC 60947-5-1
Utilisation category ....... AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Rated op. voltage ................230 V / 230 V / 24 V / 110 V / 220 V
Rated op. voltage UL............200 V / 200 V / 24 V / 110 V / 200 V
Rated op. current............................ 5 A / 3 A / 1 A / 0.2 A / 0.1 A
Minimum contact load
(relay manufacturer's reference) 1...........................0 mA/5 V DC
( )* = factory setting
Ordering information
Mounting clip for screw mounting
(1 piece per device, accessories) ............................... B98060008
Technische Daten
Isolationskoordination nach IEC 60664-1/IEC 60664-3
Bemessungsspannung .......................................................400 V
Bemessungs-Stoßspannung/Verschmutzungsgrad.........4 kV /III
Sichere Trennung (verstärkte Isolierung) zwischen .....................
............................... (A1, A2) - (E/KE) - (11, 12, 14) - (21, 22, 24)
Spannungsprüfung nach IEC 61010-1
(E, KE) - [(A1-A2), (11-12-14)]........................................3,32 kV
(E, KE) - (21-22-24) ........................................................2,21 kV
(A1- A2) - (11-12-14) - (21-22-24).................................2,21 kV
Versorgungsspannung
GM420-D-1
Arbeitsbereich US........................AC 16…72 V / DC 9,6…94 V
Frequenzbereich US......................................... DC, 15…460 Hz
GM420-D-2
Arbeitsbereich US......................................... AC/DC 70…300 V
Frequenzbereich US.......................................... DC, 15…460 Hz
Eigenverbrauch .............................................................≤ 3,5 VA
Messkreis
Schleifenwiderstand Rm
Messbereich Rm........................................................ 0…100 Ω
Messstrom Im..............................................................DC 20 mA
Messspannung Um..................................................... ≤ DC 24 V
Fremdspannung Uf
Messbereich Uf....................................................... AC 0…50 V
Bemessungsfrequenz fn ........................................ 42…460 Hz
Abschaltung der Messschleife bei Uf.............................. ≥ 12 V
Wiedereinschaltung der Messschleife .............................≤ 10 V
Zulässige Fremdspannung Uf.........................................≤ 440 V
Zulässige DC-Fremdspannung
ohne Beeinflussung der Messung .............................. DC 0 V
Schaltglieder
Schaltglieder ........................................................2 x 1 Wechsler
Arbeitsweise .............. Ruhestrom/Arbeitsstrom (Arbeitsstrom)*
Elektrische Lebensdauer ............................... 10000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ........AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Bem.betriebsspannung .......230 V / 230 V / 24 V / 110 V / 220 V
Bem.betriebsspannung UL...200 V / 200 V / 24 V / 110 V / 200 V
Bem.betriebsstrom ........................ 5 A / 3 A / 1 A / 0,2 A / 0,1 A
Minimale Kontaktbelastung
(Referenzangabe des Relais-Herstellers)................10 mA/5 V DC
( )* = Werkseinstellung
Bestellangaben
Montageclip für Schraubmontage
(1 Stück je Gerät, Zubehör)........................................B98060008
GM420_D00112_00_Q_DEEN/10.2023 7
LINETRAXX® GM420