Ground Fault Monitor RCM420
Insulation coordination acc. to IEC 60664-1 / IEC 60664-3
Rated insulation voltage 250 V
Rated impulse voltage / pollution degree 2.5 kV / III
Protective separation (reinforced insulation) between
(A1, A2) - (k / l, T / R) – (11, 12, 14) – (21, 22, 24)
Voltage test according to IEC 61010-1 2.21 kV
Supply voltage
Supply voltage USsee ordering details
Power consumption ≤ 3 VA
Measuring circuit
External measuring current transformer W - , WR - , WS - series
Load 68 Ω
Rated insulation voltage (measuring current transformer) 800 V
Operating characteristic acc. to IEC 62020 Type A
Rated frequency 42 - 2000 Hz
Measuring range 3 mA - 16 A
Relative percentage error 0 - - 20 %
Display accuracy ± 15 %
Response values
Rated residual operating current IΔn1 (prewarning) 50 - 100 % x IΔn2 (50 %)*
Rated resiudal operating current IΔn2 (alarm) 10 mA - 10 A (30 mA)*
Hysteresis 10 - 25 % (15 %)*
Specified time
Starting delay t 0 - 10 s (0,5 s)*
Response delay ton2 (alarm) 0 - 10 s (0 s)*
Response delay ton1 (prewarning) 0 - 10 s (1 s)*
Delay on release toff 0 - 99 s (1 s)*
Operating time tae at IΔn = 1 x IΔn1 / 2 ≤ 180 ms
Operating time tae at IΔn = 5 x IΔn1 / 2 ≤ 30 ms
Response time tan tan = tae + ton1 / 2
Recovery time tb≤ 300 ms
Number of restart cycles 0 - 100 (0)*
Cable lengths for current transformers
Single wire ≥ AWG 20 (0.75 mm2)0 . . . 3.2 ft (0 - 1 m)
Single wire, twisted ≥ AWG 20 (0.75 mm2)0 . . . 32.8 ft (0 - 10 m)
Shielded cable ≥ AWG 22 (0.5 mm2)0 . . . 131 ft (0 - 40 m)
Recommended cable (shielded, shield on one side connected
to terminal l of the RCM420, not connected to earth) J-Y(ST)Y min. 2 x 0.8
Connection screw terminals
Displays, memory
Display range, measuring value 3 mA - 16 A
Relative percentage error 0 - - 30 % / ± 2 digit
Measured-value memory for alarm value data record measured values
Password off / 0 - 999 (off)*
Latching behavior
ON / OFF / CON (Latching / Non-latching / Remains latched on return from power loss)
Inputs / outputs
Cable length for external test / reset button 0 - 32 ft (0 - 10 m)
Switching elements
Number of switching elements 2 SPDT contacts
Operating principle normally energized or normally deenergized(*)
Electrical service life under rated operating conditions 10.000 switching operations
Contact data acc. to IEC 60947-5-1
Utilization category AC-13 AC-14 DC-12 DC-12 DC-12
Rated operational voltage 230 V 30 V 24 V 110 V 220 V
Rated operational current 5 A 3 A 1 A 0.2 A 0.1 A
Minimum contact load 1 mA at AC / DC ≥ 10 V
Environment / EMC
EMC IEC 62020: 2003-11
Operating temperature - 25 °C - + 55 °C
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3) 3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) 2K3 (except condensation and formation of ice)
Long-time storage (IEC 60721-3-1) 1K4 (except condensation and formation of ice)
Classification of mechanical conditions IEC 60721
Stationary use (IEC 60721-3-3) 3M4
Transport (IEC 60721-3-2) 2M2
Long-time storage (IEC 60721-3-1) 1M3
Connection
Connection screw terminals
rigid / flexible AWG 24 - 12 / 24 - 14
Multi-conductor connection (2 conductors with the same cross section)
rigid / flexible AWG 24 - 14 / 24 - 14
Stripping length 8 - 9 mm
Tightening torque 0.5 - 0.6 Nm
Other
Operating mode continuous operation
Position of normal use any
Degree of protection, internal components (IEC 60529) IP30, NEMA 1
Degree of protection, terminals (IEC 60529) IP20, NEMA 1
Enclosure material polycarbonate
Flammability class UL94V-0
DIN rail mounting acc. to IEC 60715
Screw mounting 2 x M4 with mounting clip
Standards IEC 62020
Instruction leaflet TGH1410
Weight ≤ 150 g
( )* factory setting
Technical data