GENERAL INSTRUCTIONS
Adjustment of burner
The burner is from the factory pre-set
to an average value that must then be
in accordancewith boilermanu-facturers
instructions. These must include the
average water temperature and CO2
or O2concentration.
General instructions
The installation of the gas burner
must be carried out in accordance
with current regulations and standards.
The installers of gas burners should
therefore be acquainted with all regu-
lations and ensure that the installation
complies with the requirements. The
should be made with the greatest
care and only the correct gas should
be used.
Operating instructions
The operating instructions accom-
panying the burner should be left
in a prominent position in the boiler
room.
Instructions
The user should be thoroughly
instructed in the function of the gas
burner and the whole installation.
The supplier must instruct the user.
Inspection and maintenance
Daily inspection is advisable.
Start up
the boiler and the electric connection,
the leakage control, the venting and
the electric function test have been
carried out, the burner will be ready
for start-up.
Howerer, study the sections dealing
-
bustion air and combustion head.
Open the ball valve and switch on the
main switch. If the burner starts the
Adjustment of burner head
-
ment device changing the position of
the brake plate in the burner head. This
drop over the combustion device in
order to obtain a good pulsation free
combustion.
Which position to use depends on
input and overpressure in the boiler.
172 305 28 07-01
A general rule is that the lower capacity
the smaller the opening between
brake plate and combustion device.
Commissioning of installation
Control of the combustion. The com-
bustion quality is checked by means
in accordance with the table. Check
gas volume on the gas meter so that
the correct input is achieved.
Service
Service should only be carried out
parts should be of the same make and
approved by the same authorities as
the original. If the burner is converted
re-commissioned. If town gas is to be
to suit (e.g.a larger gas armature or a
different spring in the governor may
be required).
Gas quality CO2
lambda 1,2
02max. CO2
Natural gas 10,0 3,5 11,9
LPG 11,5 3,5 13,9
172 445 05 08-01
ELECTRIC EQUIPMENT
Alarm control table LME ....
signal lamp (LED))
Possible causes
Flashing 2 x
- Defective or obscured fuel valves.
- Poor burner installation.
- Defective ignition unit.
Flashing 3 x
Flashing 4 x
Flashing 5 x
Flashing 6 x
Free
Flashing 7 x
- Poor burner installation.
- Defective or obscured fuel valves.
Flashing 8x
Free
Flashing 9x
Free
Flashing 10 x
Connection fault or internal fault, outgoing contacts
or other fault.
Flashing 14 x
CPI contact not closed.
During alarm trigger diagnostics, control outputs are to be disconnected
from all power.
- The burner is disconnected.
The burner is only to be reconnected after it is reset.
- Press the reset button 0.5...3 s.
A1 = LME
Q1=AGQ 3...
br bl rt sw
sw
GP
R/W
bl
QRA
LN
12 211 1
Interface diagnostics
To switch to interface mode, hold the reset button depressed for more than
3 s. To return to normal mode, hold the reset button depressed for more
reset button 0.5...3 s.
5(5)