Berner AHC10-1036 Installation instructions manual

-1-
READ AND SAVE
THESE INSTRUCTIONS
No. II-260
Date May, 2014
TABLE OF CONTENTS
I. UNCRATING.................................................................................................................................................................................................. 2
II. WALL MOUNTING - INDOOR INSTALLATION ........................................................................................................................................ 2
III. WALL PREPARATION ................................................................................................................................................................................3
IV. ATTACHING THE AIR CURTAIN TO THE MOUNTING PLATE................................................................................................................ 3
V. TOP MOUNTING - INDOOR INSTALLATION............................................................................................................................................4
VI. ELECTRICAL CONNECTIONS ..................................................................................................................................................................4
VII. ELECTRICALLY HEATED MODELS .................................... ....................................................................................................................4
VIII. STEAM OR HOT WATER HEATED MODELS .........................................................................................................................................5
IX. OPERATING INSTRUCTIONS ...................................................................................................................................................................5
X MAINTENANCE AND CLEANING...............................................................................................................................................................6
XI. SERVICE ................................................................................................................................................................................................... ..4
XII.WARRANTY ...............................................................................................................................................................................................8
TROUBLESHOOTING .................................................................................................................................................................................... .7
IMPORTANT INSTRUCTIONS
Saving energy and creating healthy, comfortable environments
Installation & Maintenance Instructions
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Read all instructions before installing or using this air curtain.
B. Use this unit only in the manner intended by the manufacturer and described in this manual. Any other use not recommended by the
manufacturer may cause re, electric shock, or injury to persons. If you have any questions, contact the manufacturer.
C. Before servicing or cleaning unit, switch power o at service panel and lock the service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
D. Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable national and local codes
having jurisdiction, including re-rated construction. See page 4, ELECTRICAL CONNECTIONS (NEC Code ANSI/NFPA No. 70).
E. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
F. To reduce the risk of re, do not store or use gasoline or other ammable vapors and liquids in the vicinity of the air curtain.
G. This air curtain is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture,
pillows, bedding, papers, clothes, etc. and curtains at least 1 inch from the top, back, front, sides and at least 6 feet from the discharge
of the air curtain.
H. Extreme caution is necessary when any air curtain is used by or near children or invalids, and whenever the heater is left operating
unattended.
I. Do not operate any air curtain after it malfunctions. Disconnect power at the service panel and have the air curtain inspected by a
reputable electrician before reusing.
J. To disconnect the air curtain, turn controls to "o", and turn o power to the air curtain circuit at main disconnect panel.
K. Do not insert or allow foreign objects to enter any ventilation or discharge opening as this may cause an electric shock or re, or
damage the air curtain.
L. To prevent a possible re, do not block the air intake or discharge of the air curtain in any manner.
M. The air curtain has hot and arcing or sparking parts inside. Do not use it in areas where gasoline, paint, or ammable vapors or liquids
are used or stored.
N. This heater may include an audible or visual alarm to warn that parts of the heater are getting excessively hot. If the alarm sounds
(or illuminates), immediately turn the heater o and inspect for any objects on or adjacent to the heater that may have blocked the airow
or otherwise caused high temperatures to have occurred. DO NOT OPERATE THE HEATER WITH THE ALARM SOUNDING (OR ILLUMINATING).
ARCHITECTURAL
High Performance 10
AIR CURTAIN SERIES AHC10

-2-
I. UNCRATING
Carefully examine the carton(s) for damage before opening. If
the carton is damaged, immediately notify the shipping com-
pany. Open the carton and remove all protective packing. Re-
move the unit by lifting vertically. Place the unit upside down
on end supports to avoid damage to the electrical junction
box. If the unit will be wall mounted, remove and save the two
(2) locking screws from the back corners and detach the wall
mounting plate. See Figure 1
ACCESSORIES: If the unit(s) were ordered with optional electrical acces-
sories (door switch, control panel, etc.), the accessories may be found in
the carton containing the unit or in a separate carton(s) accompanying
the unit(s). Check all of the cartons/skids for accessories before discard-
ing.
Figure 1
The ARCHITECTURAL HIGH PERFORMANCE 10 Air curtain is
designed to be an eective barrier against cold drafts in the
winter and hot air in the summer, ying insects and airborne
contaminants. To achieve optimum protection, the unit should
be mounted on the inside of the building, ush to the wall and as
close to the top of the door opening as possible. To ensure peak
performance keep air stream free of obstructions. See Figure 2.
II. WALL MOUNTING -
INDOOR INSTALLATION
Unit should be mounted no higher than 10’ above
the oor. For maximum eciency, the unit should be
mounted no higher than 8’.
1. Install the ARCHITECTURAL HIGH PERFORMANCE 10 Air
curtain so that nothing interferes with the curtain of air
when it is deected 20° to either side. If the air stream
strikes any obstruction, i.e. the top edge of the doorway, a
structural beam, a door opening device, etc., its eciency
will be greatly reduced. See Figure 2.
2. The lower lip of the mounting plate should be no more
than 1” above the door opening when the unit is mounted
ush to the wall. If the Air curtain must be mounted
higher, it must be spaced out from the wall 3/8”for every
inch the unit is above the door opening. For the best per-
formance, any void between the Air curtain and the wall
must be sealed (use foam, plastics or a similar packing).
See Figure 3.
3. Do not block the air ow to or from the unit since this
could cause overheating. On electrically heated units
there should be:
a. A minimum clearance of at least 4”between the side of
the unit and any combustible material if the unit is
enclosed in the ceiling or a decorative cover.
b. A minimum clearance of 8” between the top of the unit
and the ceiling in order to service the junction box(es).
c. Do not install less than six feet (or 1.8 meters) from the
oor to the unit. See Figure 2.
Figure 2
Figure 3
6' minimum
20˚
8" minimum
AIR
Discharge
Nozzle
4" minimum
side clearance
from combustible
material*
A
I
R
A
I
R
*Electrically Heated Units Only
INTERIOR
EXTERIOR
Locking Screws
Wall
Mounting
Plate
Packaging
Bottom of Unit
1" 2"
Lower Lip
3/8"
Mounting
Screws
Mounting
Plate
Mounting
Screws
FLUSH WALL
MOUNT
EXTENDED
WALL MOUNT
Spacer
Spacer
Seal

-3-
TABLE 1 - Weight Chart
III. WALL PREPARATION
1. Position and center the mounting plate over the door
opening. The mounting plate must be positioned with the
45° lip and the rubber vibration gasket on top. Drill mount-
ing holes on the mounting plate. See Figure 4.
2. Mark the wall in the center of each mounting plate hole.
The wall must provide sucient support for the Air curtain.
The mounting hardware (supplied by others) must be
capable of supporting a minimum of three times the net
weight of the Air curtain. See Weight Chart, Table 1. If
the location of the marks on the wall do not provide suit-
able support, mark and drill additional holes.
3. Drill the four holes as marked on the wall and attach the
mounting plate with anchors (if used) and the four mount-
ing screws (provided by others).
Figure 4 Figure 5
Table 2
MOTOR DATA
Model #Motors
@HP
120 V
1ø
208/240 V
1ø
460 V*
1 ø
Motor
Amps
Motor
Amps
Motor
Amps
AHC10-1036 1@½ 7.2 4.0 1.3
AHC10-1042 1@½ 7.2 4.0 1.3
AHC10-1048 1@½ 7.2 4.0 1.3
AHC10-2048 2@½ 14.4 8.0 2.6
AHC10-2060 2@½ 14.4 8.0 2.6
AHC10-2072 2@½ 14.4 8.0 2.6
AHC10-2084 2@½ 14.4 8.0 2.6
AHC10-2096 2@½ 14.4 8.0 2.6
AHC10-3096 3@½ 21.6 12.0 3.9
AHC10-3108 3@½ 21.6 12.0 3.9
AHC10-3120 3@½ 21.6 12.0 3.9
*Special 1/3 hp Two Speed Motor
1"
Doorway Opening
Recommended Mounting
Plate Holes
45º Lip and Rubber
Vibration Gasket
2 Locking Screws
(One In Each Corner)
Mounting
Plate
45˚ Lip and Rubber
Vibration Gasket
Discharge
Nozzle
IV. ATTACHING THE AIR CURTAIN TO THE
MOUNTING PLATE
1. Raise the unit over the door (air discharge nozzle facing
down) and on to the mounting plate. First, tilt the unit up-
ward matching the top recessed edge of the unit to the top
45° angled lip on the mounting plate. See Figure 5.
2. Lower the unit into place, allowing it to rest on the lower lip
of the mounting plate.
3. After the unit is securely attached to the mounting plate, re-
install the two (2) locking screws at the bottom corners.
See Figure 5.
WEIGHT IN POUNDS
Model Unheated Electric Steam/Hot Water
AHC10-1036 65 71 98
AHC10-1042 68 74 104
AHC10-1048 70 76 109
AHC10-2048 95 107 134
AHC10-2060 125 137 171
AHC10-2072 130 142 181
AHC10-2084 140 152 197
AHC10-2096 145 157 208
AHC10-3096 165 183 228
AHC10-3108 170 188 240
AHC10-3120 175 193 248

-4-
ELECTRIC HEATER DATA* Add total motor amp draw from Table #2 to circuit #1 for unit total amp draw
MODEL KW 208V 1Ø 240V 1Ø 208V 3Ø Amp Draw 240V 3Ø
Amp Draw
460V 3Ø**
Amp Draw
600V 3Ø**
Amp Draw
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 3 Circuit 1 Circuit 2 Circuit 1 Circuit 1
AHC10-1036 9.5 45.7 - 39.6 - 26.4 - - 22.9 - 11.4 9.5
AHC10-1042 9.5 45.7 - 39.6 - 26.4 - - 22.9 - 11.4 9.5
AHC10-1048 9.5 45.7 - 39.6 - 26.4 - - 22.9 - 11.4 9.5
AHC10-2048 12.5 20.0 40.1 17.4 34.7 34.7 - - 30.1 - 15.0 12.6
AHC10-2060 16.0 - - - - 44.4 - - 38.5 - 19.2 16.1
AHC10-2072 19.0 - - - - 26.4 26.4 - 22.9 22.9 22.9 19.1
AHC10-2084 19.0 - - - - 26.4 26.4 - 22.9 22.9 22.9 19.1
AHC10-2096 19.0 - - - - 26.4 26.4 - 22.9 22.9 22.9 19.1
AHC10-3096 25.0 - - - - 34.7 34.7 - 30.1 30.1 30.1 25.1
AHC10-3108 28.5 - - - - 26.4 26.4 26.4 22.9 45.7 34.3 28.6
AHC10-3120 28.5 - - - - 26.4 26.4 26.4 22.9 45.7 34.3 28.6
*Optional kW available. Check wiring diagram supplied with unit for kW and AMP draw if not listed above.
** Separate 120V, 208V or 240V single phase circuit required to operate motors.
Table 3
V. TOP MOUNTING -
INDOOR INSTALLATION
(CEILING SUSPENSION)
For top mounting suspension rods, four (4) factory installed
5/16” threaded inserts are located on the top of the unit.
See Figure 6.
1. Install the ARCHITECTURAL HIGH PERFORMANCE 10
Air curtain so that nothing interferes with the curtain of air
when it is deected 20° to either side. If the air stream strikes
any obstruction, i.e. the top edge of the doorway, a structural
beam, a door opening device, etc., its eciency will be greatly
reduced. See Figure 2.
2. Follow instructions 2 and 3 under INDOOR INSTALLATION:
WALL MOUNTING (on page 1) checking to assure the minimum
clearances are met.
3. Attach 5/16”threaded rods, or other suitable hardware to the
top mounted threaded inserts.
VI. ELECTRICAL CONNECTIONS
All electrical wiring and connections MUST be performed by
qualied personnel in accordance with the latest edition of the
National Electrical Code ANSI/NFPA No. 70 or, in Canada, the
Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local
codes and regulations. MAKE SURE THE CORRECT VOLTAGE AS
MARKED ON THE UNIT IS USED.
The ARCHITECTURAL HIGH PERFORMANCE 10 Air curtain is
internally wired to the junction box(es) on top of the of the unit.
1. Run the proper size cable from the source to the junction box
and connect the leads.
2. Wiring diagrams are located inside the junction box. For amp
rating, See Tables 2 or 3 and the name plate on the unit.
VII. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by a remote thermostat, a
built-in thermostat or a manual on/o heater switch located on
the discharge side of the unit. See Figure 7.
1. If a thermostat is used, connect the proper leads located in
the junction box to the leads of the thermostat. (See wiring
diagram located in the junction box)
2. If a manual heat on/o switch is used, factory wiring is supplied
from the heating coil to the unit mounted heat on/o switch.
Overheat protection is provided by thermal cutouts built
into the heater coil assembly. (See the wiring diagram
located in the junction box.)
Figure 6
5/16" Recessed Insert
Side View
Suspension Rods

-5-
Figure 9
20˚
AIR
Discharge
Nozzle
A
I
R
INTERIOR
EXTERIOR
3"
12"
Handkerchief
A
I
R
2. Unheated units will have the fans activated by a door or
selector switch or sensor. The unit may be single speed and
require no fan speed selector (On/O), or
may have multiple fan speeds which require either a unit or
remote mounted switch (O, High, Med, Low).
3. Heated units will have fans activated by a door or selector
switch or sensor, but may also be activated by the thermo
stat in Comfort Plus Mode. The unit may be single speed
and controlled by either a unit or remote mounted switch
(Fan, O, Heat), or may have multiple fan speeds which can
be set by either a unit or remote mounted switch (Low,
Med, High, O, Low heat, Med Heat, High Heat).
4. Heat activation is controlled by either a unit or remote
mounted thermostat, and a unit or remote mounted switch.
B. AIR STREAM ADJUSTMENT
1. With the air curtain operating and the door in its full open
position, check to see that nothing is obstructing the airow
at the discharge nozzle vanes.
2. Find the air stream split location. Hold a handkerchief by
its corners, approximately 12” above the oor. Gently move
the handkerchief back and forth in the doorway. Make sure
the air is being directed to both the inside and the outside.
See Figure 9. The split location is indicated where the
handkerchief is vertical with minimal or no uttering.
3. The split location should be approximately 3” outside the
doorway. If necessary adjust the discharge nozzle vanes by
de-energizing the unit, loosening the nozzle vane locking
screws and adjusting vanes.
Figure 7
Figure 8
VIII. STEAM OR HOT WATER HEATED
MODELS
Piping should be done in accordance with local codes, regulations
and standard practice.
1. Connect the supply & return to the 1” MPT nipples on the
heating coil. See Figure 8.
2. Temperature controls to be supplied by others.
IX. OPERATING INSTRUCTIONS
A. GENERAL OPERATION
Air curtain operation may be divided into four areas: control
package, fan activation, fan speed selection, and heat
activation. Depending on the type of controls ordered one
or more of the following may be applicable. The air curtain
must be properly installed before it is used.
1. Control packages control the unit’s sequence of operation.
Unit modes/control packages are built into the unit and
may not be changed in the eld. Refer to your wiring
diagram for specics about activation connections and
sequence of operation.
a. Basic Control Package – The unit is activated by a door
or selector switch. Either switch may be line voltage or
low voltage (24V).
b. Deluxe Control Package – The unit is activated by a
door or selector switch, but has a factory installed time
delay allowing the unit to keep running for a period of
time after the door closes.
c. Comfort Plus Control Package – Available only on
heated units, the unit is activated by a door
or selector switch AND a thermostat to provide
supplemental heating.

-6-
XI. SERVICE
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power
whenever servicing unit. More than one disconnect may
be required to de-energize unit.
Any service performed on the ARCHITECTURAL HIGH PERFOR-
MANCE 10 Series air door MUST be done by qualied personnel.
Berner air doors require very little servicing. All parts are eas-
ily accessible for periodic inspection and maintenance. Units
should be cleaned at least twice a year.Your particular applica-
tion (the amount of dirt and dust in the air) and location of the
unit(s) will determine how often your unit(s) will need to be
cleaned and serviced. All motors have permanently lubricated,
sealed, sleeve bearings and require no maintenance.
Figure 11
X. MAINTENANCE AND CLEANING
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power
whenever servicing unit. More than one disconnect may
be required to de-energize unit.
Keep your air door operating at peak eciency by cleaning
the blower wheels, motor(s) and intake grille. Buildup of dust
on the blower wheels can cause vibration, noise and excessive
wear on the motor bearings. The frequency of cleaning will
depend on the environment where the unit is operating.
Dirty, dusty or greasy environments could require a cleaning
schedule of once every two months. If the environment is
not that dirty, the unit(s) should be scheduled for cleaning a
minimum of once every (6) months. To access the interior of
the unit:
1. Disconnect the power to the unit.
2. Remove the intake grille by removing the locking screw on
each end of the unit. Lift the intake grille up and then towards
you. See Figure 11.
3. Remove the bottom access panel. Remove Phillips head
screws on the bottom of the unit. Vacuum and scrape (if
necessary) to remove the build-up of dirt and debris. The
motor(s) are permanently lubricated and require no additional
lubrication. Re-install the cover and intake grille.
4. Switch the power on after cleaning. CAUTION: STAND CLEAR
OFTHE UNIT ORWEAR SAFETY GOGGLES AS LOOSE DEBRIS
MAY BE PRESENT AND MAY EXIT THE NOZZLE.
Intake Grill
Grill Locking Screws

-7-
• Air stream too weak
• Air steam hits obstruction
• Negative pressure
• Shaft rotating inside fan
• One motor not operating
• Nozzle not angled out far enough
• Unit too powerful
• Air movement too cold
• Pushing air outside building
SEE AIR IS NOT HITTING FLOOR SYMPTOMS
• Switch turned to “ON” position
• Thermostat not set properly
• Coils burned out due to lack of air
• Automatic reset thermal cutout failed in open position
• Manual reset thermal cutout tripped (if supplied)
• Adjust nozzle to proper position, adjust motor speed;
see installation instructions
• Remove obstruction or reposition air curtain (move out
3/8” for every 1” up from the door)
• Relieve negative pressure by providing makeup air
• Tighten set screws
• Repair or replace motor
• Adjust nozzle angle to outside
• Adjust motor speed
• Add auxiliary heat to overcome wind chill factor
• Adjust discharge angle back into building, adjust motor
speed
• Replace switch or check wiring
• Change thermostat setting
• Correctairowproblem;replacecoils
• Replace automatic thermal cutout
• Reset manual thermal cutout
AIR IS NOT HITTING
FLOOR
UNEVEN AIR
EXCESSIVE AIR
MOVEMENT AT DOOR-
WAY
ELECTRICALLY HEATED MODELS
NO HEAT
MINIMAL HEAT
EXCESSIVE HEAT
STEAM/HOT WATER HEATED UNITS
EXCESSIVE HEAT
MINIMAL HEAT
NO AIR • Power supply line open (no power)
• Fuse blown/circuit breaker tripped
• Motor overload tripped
• Failed switch
• Check power source, check method of control in ON
position
• Replace fuse(s)/reset breaker
• Internally protected motor - should reset automatically
after cool-down, if not, replace motor.
• Replace switch
MOTOR RUNNING/FANS ARE NOT ROTATING
MINIMUM AIR
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
TROUBLESHOOTING
SYMPTOMS REMEDY
CAUSE
• Brokenordamagedexiblehub
• Shaft rotating inside fan
• Selector switch is in off position
• Door limit switch not operating
• Air directional discharge vanes mis-adjusted
• Inadequate intake clearance
• Blower motor operates below speed
• Fan rubbing against housing
• Fan wheels clogged with dirt
• Fan in backwards
• Replace fan sleeve/reengage coupling
• Tighten set screws/tighten fan on shaft
• Turn switch to “ON” position
• Repair or replace limit switch
• Adjust vanes to proper position, see instructions
• Move air curtain or remove obstruction
• Provide adequate space for air curtain
• Improper voltage
• Free fan from housing
• Clean and vacuum fan wheels
• Check fans for blade curve toward discharge
• Thermostat in wrong location - thermostat too
close to discharge
• Improper voltage
• Thermostat not set properly
• Incorrect speed range
• Thermostat in wrong location
• Thermostat not set properly
• Insufcientairovercoil
• Improper voltage
• Too high steam/hot water pressure
• Inadequateairow,nspluggedup,dirtycoils
• Insufcientremovalofcondensation(steam)
• Not enough steam pressure/water temperature too
low
• Intake air below design temperature
• Move thermostat away from air stream
• Supply proper voltage
• Change temperature setting
• Set dip switch to electric heated speed range
• Move the thermostat closer to air stream
• Change temperature setting
• Remove restriction on intake
• Supply proper voltage
• Reducesteampressure/hotwaterow
• Clean intake and coils
• Increase trap size
• Raisepressureforsteam/increasewaterow
• Increasesteampressure/increasewaterow

-8-
BERNER INTERNATIONAL CORPORATION
New Castle, Pennsylvania
724-658-3551 • 1-800-245-4455 • www.berner.com • airdoors@berner.com
© Copyright 2014 Berner International Corporation MADE IN U.S.A.
Berner reserves the right to alter specifications without prior notice.
XII. WARRANTY
Berner International ("The Company") warrants all new equipment to be free of defects in workmanship and material for a period of
ve years (5 years) on unheated models and two years (2 years) on heated models from the original date of shipment, provided the
equipment has been properly cared for, installed and operated in accordance with the limits specied on the nameplate and The
Company’s instructions.
The Company will correct by repair or replacement, at its option and expense, any proven defects in said apparatus, subject to
the above conditions, provided that immediate written notice of such defects is given to The Company. The warranty does not
include any labor incurred for the removal or installation of defective part(s). The Company reserves the right to inspect, or have
inspected by a qualied representative, any apparatus at the place of installation before authorizing repair or replacement. Repair or
replacement will be made F.O.B. factory with any applicable transportation charges to be borne by the customer. Merchandise not of
The Company’s manufacture supplied in piece, or in component assemblies, is not covered by the above warranty, but The Company
will give the customer the benet of any adjustment as made with the Manufacturer.
This warranty is void if the apparatus has been tampered with in any way or shows evidence of misuse.
The Company will not assume any expense or liability for repairs made outside its factory without proper written consent from
its service manager, nor for any transportation charges on apparatus returned to the factory without written authorization by The
Company.
Nothing in the above warranty provisions, however, shall impose any liability or obligation of any type, nature or description upon
Berner International if Berner has not received payment in full for the apparatus in question.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HERE OF INCLUDING
THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
LIMITATION OF DAMAGES
Notwithstanding anything to the contrary above, customer’s exclusive remedy for any and all losses or damages resulting
from the sale of The Company’s equipment under this agreement, including but not limited to, any allegations of breach
of warranty, breach of contract, negligence or strict liability, shall be limited, at The Company’s option, to either the return
of the purchase price or the replacement of the particular equipment for which a claim is made and proved. In no event
shall The Company be liable for any special, consequential, incidental or indirect losses or damages from the sale of The
Company’s equipment under this agreement.
SERIAL NUMBER MODEL NUMBER DATE PURCHASED
This manual suits for next models
10
Table of contents
Other Berner Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Mitsubishi Electric
Mitsubishi Electric MS-GK36VAT operating instructions

LG
LG LMU180CE owner's manual

Technibel
Technibel KPAFP165R5IA Series installation manual

CLIMAVENETA
CLIMAVENETA i-ACCURATE i-AX Installation manual - user and maintenance

DEVOLA
DEVOLA DVCO60P user manual

Nortek
Nortek AB 225 Installation and operating manual

Mitsubishi Electric
Mitsubishi Electric CITY MULTI PKFY-P-VBM-E installation manual

Bryant
Bryant 14 SEER Service manual

Frico
Frico AD100 Original instructions

Mitsubishi Electric
Mitsubishi Electric MSZ-A09/A12YV Series installation manual

LG
LG LW1221IVSM owner's manual

Panasonic
Panasonic S-20LM3HPQ Installation and operation manual