Berner Maxair Installation and operating instructions

Installation & Maintenance Instructions
TABLE OF CONTENTS
I. UNCRATING..........................................................................................................................................................................................................2
II. GENERAL MOUNTING INSTRUCTIONS...........................................................................................................................................................2
III. WALL MOUNTING .............................................................................................................................................................................................2
IV. SUSPENDED MOUNTING ................................................................................................................................................................................3
V. ELECTRICAL CONNECTIONS ............................................................................................................................................................................4
VI. FIELD CONNECTIONS ......................................................................................................................................................................................6
VII. OPERATION INSTRUCTIONS ......................................................................................................................................................................... 6
VIII. MAINTENANCE AND CLEANING ................................................................................................................................................................. 7
IX. SERVICE ............................................................................................................................................................................................................ 7
INTELLISWITCH®...................................................................................................................................................................................................10
QUICK START OPERATION...........................................................................................................................................................................10
FAQ’s (FREQUENTLY ASKED QUESTIONS)................................................................................................................................................ 12
THE INTELLISWITCH® PROGRAMMING)....................................................................................................................................................14
X. TROUBLESHOOTING........................................................................................................................................................................................19
XI. WARRANTY ......................................................................................................................................................................................................20
www.intelli-how2.com 800-245-4455 www.berner.com
IMPORTANT INSTRUCTIONS
READ AND SAVE
THESE INSTRUCTIONS
No. II-470
Date August, 2013
Saving energy and creating healthy, comfortable environments
MAXAIR
AIR CURTAIN
/AIR DOOR
MADE IN THE USA
ZEPHYR
AIR CURTAIN
/AIR DOOR
MADE IN THE USA
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Read all instructions before installing or using this air curtain.
B. Use this unit only in the manner intended by the manufacturer and described in this manual. Any other use not recommended by the
manufacturer may cause re, electric shock, or injury to persons. If you have any questions, contact the manufacturer.
C. Before servicing or cleaning unit, switch power o at service panel and lock the service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
D. Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable national and local codes
having jurisdiction, including re-rated construction. See page 4, ELECTRICAL CONNECTIONS (NEC Code ANSI/NFPA No. 70).
E. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
F. To reduce the risk of re, do not store or use gasoline or other ammable vapors and liquids in the vicinity of the air curtain.
G. This air curtain is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture,
pillows, bedding, papers, clothes, etc. and curtains at least 1 inch from the top, back, front, sides and at least 6 feet from the discharge of
the air curtain.
H. Extreme caution is necessary when any air curtain is used by or near children or invalids, and whenever the heater is left operating
unattended.
I. Do not operate any air curtain after it malfunctions. Disconnect power at the service panel and have the air curtain inspected by a
reputable electrician before reusing.
J. To disconnect the air curtain, turn controls to "o", and turn o power to the air curtain circuit at main disconnect panel.
K. Do not insert or allow foreign objects to enter any ventilation or discharge opening as this may cause an electric shock or re, or damage
the air curtain.
L. To prevent a possible re, do not block the air intake or discharge of the air curtain in any manner.
M. The air curtain has hot and arcing or sparking parts inside. Do not use it in areas where gasoline, paint, or ammable vapors or liquids are
used or stored.
N. This heater may include an audible or visual alarm to warn that parts of the heater are getting excessively hot. If the alarm sounds (or
illuminates), immediately turn the heater o and inspect for any objects on or adjacent to the heater that may have blocked the airow or
otherwise caused high temperatures to have occurred. DO NOT OPERATE THE HEATER WITH THE ALARM SOUNDING (OR ILLUMINATING).

I. UNCRATING
Carefully examine the carton(s) for damage. If the carton
is damaged, immediately notify the shipping company. Do
not delay in ling claim. If the air door(s) were shipped on
wooden skids, remove protective wood and banding straps se-
curing the carton(s) to the skid. Open the carton(s) and remove
all protective packaging. Immediately verify that the electrical
rating nameplate located on the cover matches electrical power
supply available. Retain the shipping carton(s) until the air
door(s) are installed and properly operating.
ACCESSORIES: If the air door(s) were ordered with optional
electrical accessories, the accessories will be found in the carton
containing the air door or in a separate carton(s) accompany-
ing the air door(s). Check all of the cartons/skids for accessories
before discarding.
II. MOUNTING INSTRUCTIONS
(General)
INDOOR MOUNTING ONLY - Environmental/Insect/Dust Control
The MaxAir /Zephyr Air Door are designed to be an eective barrier
against cold drafts in the winter and hot air in the summer. To achieve
optimum protection, the air door should be mounted on the inside of
the building, ush to the wall and as close to the top of the door open-
ing as possible. To ensure peak performance, keep the air stream free
of obstructions.
The air door will not perform properly if negative air pressure ex-
ists in the building. Under these conditions, a means for makeup
air to the building must be provided so that the air pressure on
both sides of the opening is in balance.
Before mounting the air door, check the supporting structure to verify
that it has sucient load-carrying capacity to support the weight of
the air door(s). The mounting hardware (supplied by others) should be
capable of supporting a minimum of three (3) times the weight of the
air door.
See Table 1.
IMPORTANT: A minimum of 1” is required above the top of the
air door for the installation and removal of the cover housing.
A. When determining the mounting location for the
air door(s), make sure that nothing interferes with the
curtain of air developed when the discharge vanes
are directed from 0º to 20º toward the door opening.
TABLE 1 - Unit Weight FIGURE 1 - Mounting Location
MODEL Net Weight
Ambient (lbs)
Net Weight
Heated (lbs)
Net Weight
Steam/Hot
Water (lbs)
MAX/ZPR1030 33 40.5 39
MAX/ZPR1036 38 45.5 48
MAX/ZPR1042 43 50 55
MAX/ZPR1048 48 56 62
MAX/ZPR1060 57 75 75
MAX/ZPR1072 64 76.5 87
MAX/ZPR2084 86 100 113
MAX/ZPR2096 96 111.5 127
MAX/ZPR2120 124 145.5 163
If the air stream strikes any obstruction (the top edge
of the doorway, a door opening device, etc.), the
eectiveness of the air door will be greatly reduced.
See Figure 1.
B. For optimum performance, the bottom of the air door
(discharge nozzle) should be no more than 1” above
the top of the door opening with the air door(s)
mounted ush to the wall. If the air door must be
mounted higher, it must be spaced out from the
wall
³/₈” for every inch the air door is above the door
opening. See Figure 3. For optimum protection, any void
between the air door and the wall should be sealed along
the full length of the air door.
C. Electric heated air door(s) shall:
1. Have a minimum clearance of at least 1”
between the sides and top of the air door and
any combustible material.
2. Have a minimum clearance of at least 6’
between the bottom of the air door and the oor.
3. Be installed Indoors Only.
D. Proceed to either Section III - WALL MOUNTING
or Section IV - SUSPENDED MOUNTING
III. WALL MOUNTING
A. The MaxAir/Zephyr Air Door is equipped with two
¼” threaded inserts on the back of each air door (two
per module on air doors 84” and over). Insert and
tighten the shoulder bolts (provided in bag taped to the
wall plate) into these threaded inserts. A minimum of two
shoulder bolts are required; on air doors comprised of
modules, use the outer threaded inserts and a minimum of
one of the inner threaded inserts.
6’ minimum*
8’ maximum
20°
1" minimum
AIR
Discharge
Nozzle
1" minimum
side clearance
from combustible
material*
A
I
R
A
I
R
*Electrically Heated Units Only
INTERIOR
EXTERIOR
2

B. Determine the exact mounting location of the air door.
NOTE: A minimum of 1” is required above
the wall mounting plate to provide clearance
for installation and removal of the air door.
C. Remove the wall mounting plate from the unit to install.
The wall mounting plate (included) is designed to t ush
with the top of the MaxAir/Zephyr Air Door. Therefore the
location of the wall mounting plate will determine the nal
location of the top of the air door.
D. For Standard Flush Wall Mounting, position the center of
the wall mounting plate over the center of the door open
ing with the larger opening of the key hole slots facing up.
The wall mounting plate thickness provides a natural ¾”
space which allows for mounting it up to 4”above the
opening. For optimum performance, the bottom of the
mounting plate should be no more than 2” or less than
1” above the top of the door opening.
See Figure 2.
High Wall Mounting must be used if the wall mounting
plate must be mounted higher than 4”above the
door opening: the mounting plate must be spaced out
from the wall ³/₈ ” for every additional inch (over 4”) that
the air door is above the door opening (clearance height).
See Figure 3. For optimum protection, do not exceed the
recommended maximum mounting height of 8’ above
the nished oor. Any void between the mounting plate
and the wall should be sealed along the full length of the
mounting plate.
E. Determine which of the four holes provided in each of
the steel brackets of the wall mounting plate are located
where suitable support is available for the air door.
A minimum of one inside hole and one outside hole from
that are comprised of modules, remove the wiring tray
cover that is located closest to the electrical rating
nameplate. Remove the required knockouts and
attach the necessary electrical hardware. Save the wiring
diagram found inside of the wiring tray. See Figure 7.
I. There are two sets of keyhole slots on the wall mounting
plate. In low overhead installations, the air door may be
staged in the lower keyholes to provide clearance for
electrical wiring and then moved to the higher key holes
after completion. Raise the air door with the discharge
opening facing down toward the oor. While
holding the air door level, slide the heads of the
shoulder bolts into the larger hole of the keyhole
slots of the mounting plate. Lower the air door
into place, keeping both ends level, allowing it to rest ush
with the mounting plate. See Figure 4.
J. After attaching the air door to the mounting plate, ensure
that the air door is seated and ush with the mounting
plate on all four sides.
K. Proceed to Section V - Electrical Connections.
IV. SUSPENDED MOUNTING
(Ceiling Suspension)
A. When the air door is top mounted, the wall mounting plate
is designed to store on the back of the air door for future
use. See Figure 5.
B. Four (4) factory installed ¼” threaded inserts are located
on the top of the air door for top suspension mounting; on
air doors comprised of modules use the
outer threaded inserts.
To eliminate the slight deection of longer air doors, the
inner threaded inserts may also be used. See Figure 6.
C. Determine the exact mounting location of the air door.
D. The top of the air door is provided with two knock-
outs on each side allowing for a left or right hand
power connection. Remove the wiring tray cover;
on air doors that are comprised of modules, remove
the wiring tray cover that is located closest to the
electrical rating nameplate. Remove the required
knockouts and attach the necessary electrical hardware.
Save the wiring diagram found inside of the wiring tray.
See Figure 7.
E. Attach ¼”threaded rods or other suitable hardware to the
top mounted threaded inserts.
each bracket must be used for proper support.
Drill out the aluminum backing of the holes chosen
with a ¼” drill bit. If the provided holes on the
mounting plate are not located where suitable support
is available, drill new holes in the space provided on
the steel mounting brackets.
F. Mark the wall in the centers of the ¼”holes drilled on the
mounting plate.
G. Attach the mounting plate to the wall (hardware by others).
H. The top of the air door is provided with two knockouts on
each side allowing for a left or right hand power
connection. Remove the wiring tray cover; on air doors
FIGURE 2 - Standard Flush Wall Mounting
3/8" Spacers
(for each inch over 4")
Wall Mounting
Plate
Discharge Nozzle
AIR
AIR
NO Obstructions
in Air Stream
Clearance Height
FIGURE 3 - High Wall Mounting
3

be located outside of the air door. If the air door is unheated,
or the sensor will be left in the wiring tray, skip to step E,
otherwise continue.
1. Remove the ½”bushing taped to the back of the
wiring tray cover and set aside.
2. Determine mounting location of the temperature
sensor (do not mount at this time).
3. Choose end of the wiring tray that the sensor will exit
the air door based on the mounting location from
F. Proceed to Section V - Electrical Connections.
V. ELECTRICAL CONNECTIONS
All electrical wiring and connections MUST be performed by
qualied personnel in accordance with the National Electri-
cal Code ANSI/NFPA No. 70 (latest edition) or, in Canada, the
Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local
codes and regulations.
FIGURE 4 - Installing Air Door on Wall Mounting Plate
A. Check the rating nameplate on the top of the air door for
supply voltage and current requirements. See Figure 7.
A separate line voltage supply with a suitable branch circuit
protection device should be run directly from the main
electrical panel to the air door. A disconnect switch for each
branch circuit is a required part of this installation.
See Tables 2 & 3.
B. All eld wiring must be copper with a minimum insulation
of 60° C within approved conduit. If any of the wire
supplied with the air door must be replaced, it must be
replaced with copper wiring with a minimum insulation of
90° C.
C. Remove the wiring tray cover; on air doors that are
comprised of modules, remove the wiring tray cover that is
located closest to the electrical rating nameplate (if it has
not already been done).
D. Electric, steam and hot water heated air doors are factory
equipped with a air door mounted solid state temperature
sensor cable (for the Intelliswitch thermostat) located in
the wiring tray. Depending where the temperature is to be
measured, the sensor may be left in the wiring tray or it may
FIGURE 5 - Wall Mounting Plate Storage
FIGURE 6 - Suspended Mounting
4
Step 2.
4. Locate the /”hole on the wiring tray next to
the electrical knockout on the side determined in
Step 3.
5. Drill out the /” hole to ½”.
CAUTION: DO NOT DAMAGE EXISTING WIRES IN
THE WIRING TRAY WHEN DRILLING.
6. Maneuver the tip of the temperature sensor from
the inside of the wiring tray out through ½”hole.
7. Thread the tip through ½” bushing from Step 1 and
snap the bushing into the wiring tray.
8. Mount the temperature sensor. Do not put any clamps
on the rubber coated tip.
E. The top of the air door has two knockouts on each side of
the air door, allowing for a left hand or right hand power
connection. Remove the required knockout if it has not
already been done and connect the power supply to the
air door. Connect all supply and control circuit wires
according to the wiring diagram provided.
NOTE: For Electric heated air doors provided with the
optional remote thermostat, mount and wire the
thermostat according to instructions and wiring
diagram.
F. Master/Slave connection, if two or more units are to be
linked together for master/Slave operation continue, other-
wise skip to step G.

Electrical Knockouts
Wiring Tr ay Cover
Electrical Rating
Nameplate
Wiring Diagram and
Temperature Sensor
Inside
FIGURE 7 - Electrical Connections
NOTE: One Intelliswitch serial cable assembly (part #
505SC***INT485-A) is required for every unit that is to
be used as a master/slave.“***” denotes length of cable
in feet-“008” = 8 feet long.
For Master/Slave operation, a serial cable connection must
be made between the INTELLISWITCH GEN2 control boards
of each unit to be linked.
1. Disconnect power to all the units.
2. Access the wiring tray on top of each unit by removing
the screws that hold the cover in place.
3. Find the (RS485) phone jack couplers in the wiring
trays. There will be two short cables in the wiring
tray of each air curtain, each with a double ended
female phone jack coupler attached to the cable.
4. The serial cable ordered for each unit will be coiled up
in the wiring tray of the unit and connected to one of
the couplers.
Note: There may be one less serial cable than the
number of units ordered. e.g. Two units together will
need only one cable; three units together will need two
cables, etc. Any extra cables can be kept as spares.
5. Use one of the extra electrical knockouts to route serial
cable from one unit to the next. Be sure to protect the
edge of the knockout properly.
6. Plug (RS485) male phone jack on the end of the serial
cable into the empty coupler on the next unit.
7. Continue process for all units that are to be connected
serially.
8. Serial cable connections are capable of two way com
munication. It does not matter which coupler the
cables are connected to.
9. The rst and last air curtains in the group will each
have an empty coupler after all connections are made.
So if there are only two air curtains connected, each
will have an empty cable coupler.
MOTOR DATA
Model #Motors
@HP
120 V
1ø
208/240 V
1ø
Total Motor
Amps
Total Motor
Amps
MAX/ZPR1030 1@1/5 3.4 1.7
MAX/ZPR1036 1@1/5 3.4 1.7
MAX/ZPR1042 1@1/5 3.4 1.7
MAX/ZPR1048 1@1/5 3.4 1.7
MAX/ZPR1060 1@1/5 3.4 1.7
MAX/ZPR1072 1@1/5 3.4 1.7
MAX/ZPR2084 2@1/5 6.8 3.4
MAX/ZPR2096 2@1/5 6.8 3.4
MAX/ZPR2120 2@1/5 6.8 3.4
TABLE 2 - Motor Amp Draw
ELECTRIC HEATER DATA*
Add total motor amp draw from Table #2 to circuit #1 for air door total amp draw
MODEL KW
208V 1Ø
Amp Draw
Circuit 1 Circuit 2
240V 1Ø
Amp Draw
Circuit 1 Circuit 2
208V 3Ø
Amp Draw
Circuit 1 Circuit 2
240V 3Ø
Amp Draw
Circuit 1 Circuit 2
480V 3Ø**
Amp Draw
Circuit 1
600V 3Ø**
Amp Draw
Circuit 1
MAX/ZPR1030 5.4 26.0 N/A 22.5 N/A N/A N/A N/A N/A N/A N/A
MAX/ZPR1030 7.2 34.6 N/A 30.0 N/A N/A N/A N/A N/A N/A N/A
MAX/ZPR1036 10 48.0 N/A 41.7 N/A 27.8 N/A 24.1 N/A 12.0 10.0
MAX/ZPR1042 10 48.0 N/A 41.7 N/A 27.8 N/A 24.1 N/A 12.0 10.0
MAX/ZPR1048 14.4 34.6 34.6 30.0 30.0 40.0 N/A 34.6 N/A 17.3 14.6
MAX/ZPR1060 14.4 34.6 34.6 30.0 30.0 40.0 N/A 34.6 N/A 17.3 14.6
MAX/ZPR1072 20 N/A N/A N/A N/A 27.8 27.8 24.1 24.1 24.0 20.1
MAX/ZPR2084 20 N/A N/A N/A N/A 27.8 27.8 24.1 24.1 24.0 20.1
MAX/ZPR2096 28.8 N/A N/A N/A N/A 40.0 40.0 34.6 34.6 34.6 28.9
MAX/ZPR2120 28.8 N/A N/A N/A N/A 40.0 40.0 34.6 34.6 34.6 28.9
*Optional kW available. Check wiring diagram supplied with air door for kW and AMP draw if not listed above.
** Separate 120V, 208V or 240V single phase circuit required to operate motors rated in Table 2.
TABLE 3 - Electric Heater Amp Draw 5

Note: If a longer cable is required than was supplied,
it can be ordered from the factory or made by using
standard at telephone cable, phone jack connectors
and the proper crimping tool.
G. Remote mounted Display Faceplate - if operation of the
Intelliswitch is desired through a remote mounted display
face plate continue, otherwise skip to step H.
NOTE: Maximum mounting distance between the Dis-
play Faceplate and the unit is 20’.
The unit MUST be factory ordered with the remote mount-
ed faceplate option.
1. When the remote faceplate option is ordered from
the factory the air door comes equipped with the
blank faceplate and 12’ribbon attached. The Display
Faceplate is shipped loose ready for eld installation.
2. Locate the male end of the 14-conductor ribbon cable
in the wiring tray and run to the remote display loca
tion. The cable is minimum CL2 rated and should not
need to be in conduit.
3. Connect the ribbon cable to the 14-pin socket with red
stripe positioned on the top left when facing the front
of the display board.
4. Mount remote faceplate to the wall.
H. Reinstall the wiring tray cover.
I. For Electric, Steam and Hot Water air doors proceed to
Section VI - Field Connections otherwise proceed to
Section VII - Operation and Controls.
VI. FIELD CONNECTIONS
A. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by a remote
thermostat or manually through the Intelliswitch located
on the discharge side of the air door. Overheating
protection is provided by auto reset thermal
cutouts built into the heater coil assembly
(see the wiring diagram).
B. STEAM OR HOT WATER HEATED MODELS
Piping should be done in accordance with local
codes, regulations and standard practices.
Connect the building system supply and return to
the ¾” MPT nipples on the heating coil. See Figure 8.
FIGURE 8 - Steam/Hot Water Connections
6
VII. OPERATING INSTRUCTIONS
A. GENERAL OPERATION
Air curtain operation may be divided into four areas:
control package, fan activation, fan speed selection,
and heat activation. The air curtain must be properly
installed before it is used.
1. Control packages control the unit’s sequence of operation.
Unit modes/control packages are built into the unit and may
not be changed in the eld.. Refer to your wiring diagram
for specics about activation connections and sequence of
operation.
a. Basic Control Package – The unit is activated by a door
switch. The door switch may be line voltage or low
voltage (24V).
b. Deluxe Control Package – The unit is activated by a door
switch, but has a factory installed time delay allowing
the unit to keep running for a period of time after the
door closes.
c. Comfort Plus Control Package – Available only on heated
units, the unit is activated by the door switch OR by the
thermostat to provide supplemental heating.
2. Unheated units will have the fans activated by a door switch
or sensor. The unit may be single speed and require no fan
speed selector (On/O), or may have multiple fan speeds
which require either a unit or remote mounted switch
(O, High, Med, Low).
3. Heated units will have fans activated by a door switch or
sensor, but may also be activated by the thermostat in
Comfort Plus Mode. The unit may be single speed and
controlled by either a unit or remote mounted switch (Fan,
O, Heat), or may have multiple fan speeds which can be set
by either a unit or remote mounted switch (Low, Med, High,
O, Low heat, Med Heat, High Heat).
4. Heat activation is controlled by either a unit or remote
mounted thermostat, and a unit or remote mounted switch.
B. AIR STREAM ADJUSTMENT
1. With the air curtain operating and the door in its full open
position, check to see that nothing is obstructing the airow
at the discharge nozzle vanes.
2. Find the air stream split location. Hold a handkerchief by
its corners, approximately 12”above the oor. Gently move
the handkerchief back and forth in the doorway. Make sure
the air is being directed to both the inside and the outside.
See Figure 9. The split location is indicated where the
handkerchief is vertical with minimal or no uttering.
3. The split location should be approximately 3”outside the
doorway. If necessary adjust the discharge nozzle vanes by
de-energizing the unit, loosening the nozzle vane locking
screws and adjusting vanes.

IX. SERVICE
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power
whenever servicing unit. More than one disconnect may
be required to de-energize unit.
Any service performed on the MaxAir/Zephyr air door MUST be
done by qualied personnel.
Berner air doors require very little servicing. All parts are eas-
ily accessible for periodic inspection and maintenance. Units
should be cleaned at least twice a year. Your particular appli-
cation (the amount of dirt and dust in the air) and location of
the unit(s) will determine how often your unit(s) will need to
be cleaned and serviced. All motors have permanently lubri-
cated, sealed, sleeve bearings and require no maintenance.
See Figure 11
FIGURE 9 - Airow Adjustment
FIGURE 10- Intake Grill Removal
FIGURE 11 - Unit Components
7
VIII. MAINTENANCE AND CLEANING
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power
whenever servicing unit. More than one disconnect may
be required to de-energize unit.
Keep your air door operating at peak eciency by cleaning
the blower wheels, motor(s) and intake grille. Buildup of dust
on the blower wheels can cause vibration, noise and excessive
wear on the motor bearings. The frequency of cleaning will
depend on the environment where the unit is operating.
Dirty, dusty or greasy environments could require a
cleaning schedule of once every two months. If the envi-
ronment is not that dirty, the unit(s) should be scheduled
for cleaning a minimum of once every (6) months.
To access the interior of the unit:
A. Disconnect the power to the unit; remove the intake grille by
removing the locking screws on each end of the unit. Lift the
intake grille up and then towards you. See Figure 10.
B. Remove the bottom access panel by removing the phillips
head screws on the bottom of the unit.
C. Vacuum and scrape (if necessary) to remove the buildup of
dirt and debris. The motor(s) are permanently lubricated and
require no additional lubrication. Reinstall the cover and intake
grille.
D. Switch the power on after cleaning, reinstalling the cover and
intake grille.
CAUTION: STAND CLEAR OF THE UNIT OR WEAR SAFETY
GOGGLES AS LOOSE DEBRIS MAY BE PRESENT AND MAY
EXIT THE NOZZLE.

NOTE: GROUND RING TERMINAL MUST BE SITUATED OR
BEND SUCH THAT IT DOES NOT TOUCH ANY TRACES ON
THE CONTROL BOARD
11. Continue installing the new control board into the unit
by carefully sliding the two tabs at the top of the
control board into the two corresponding slots in the
unit frame. Attach with new plastic push-rivets
provided. Note: when the tabs of the board hit the unit
frame tip the board up and angle the tabs into the slots.
12. Reconnect all wires to the control board.
13. Reinstall display faceplate by attaching the ribbon
cable (with red stripe positioned on the top left) to
the back of display board. Place the face plate against
the mounting bracket, insert and tighten the two
Phillips head screws.
C. INTELLISWITCH SPEED SENSOR REPLACEMENT
1. Set Intelliswitch mode to o.
2. Disconnect power to the unit
3. Remove the intake grille by removing the locking
screws on each end of the unit. Lift the intake grille up
and then away from the unit.
4. Remove the bottom access panel by removing the
Phillips head screws on the bottom of the unit.
5. Remove the two Phillips head screws from the
Intelliswitch display faceplate.
6. Remove the faceplate from the unit by gently pulling it
away from the unit and unplugging the ribbon
cable from the back.
7. Disconnect the speed sensor from the control board by
locating the pin connection marked J5 and
labeled PROXIMITY. Grasp the socket and carefully pull
away from the control board.
8. Remove the 13 mm hex nut and washer closest to the
fan from the sensor.
9. Remove the sensor.
10. Connect the new sensor to the control board; secure all
loose wires from rotating parts.
11. Install new sensor into mounting bracket. Use the
13 mm nuts to position the tip of the sensor a
maximum of 1/16” (2 mm) away from the rotating
trigger located on the motor shaft. When the unit is
energized, the LED on the back of the sensor will illumi
nate when the trigger passes if the correct distance has
been set.
CAUTION: Do not mount the speed sensor too close to
the trigger, the sensor will be ruined if it is struck by the
trigger.
12. Reinstall display faceplate by attaching the ribbon
cable (with red stripe positioned on the top left) to the
back of display board. Place the face plate against the
mounting bracket, insert and tighten the two Phillips
head screws.
13. Reinstall remaining components in reverse order of
removal.
D. INTELLISWITCH SPEED SENSOR ADJUSTMENT
1. Set Intelliswitch mode to o.
2. Disconnect power to the unit
3. Remove the intake grille by removing the
locking screws on each end of the unit. Lift the intake
A. INTELLISWITCH DISPLAY BOARD REMOVAL
OR REPLACEMENT
CAUTION: Do not expose the bare board to static electricity,
water, extreme heat or extreme moisture.
1. Set Intelliswitch mode to o.
2. Disconnect power to the unit.
3. Remove the two Phillips head screws from the
Intelliswitch display faceplate.
4. Remove the faceplate from the unit by gently pulling it
away from the unit and unplugging the ribbon
cable from the back.
5. Flip the faceplate over and place it on a clean soft
surface.
6. Remove the two nuts, aluminum shield and at
washers holding the display board to the faceplate.
7. Lift display board o of the studs while leaving the
stand o spacers in place.
8. Install new display board onto faceplate studs, reinstall
washers with aluminum shield and attach with existing
nuts.
9. Reinstall display faceplate by attaching the ribbon
cable (with red stripe positioned on the top left) to the
back of display board. Place the face plate against the
mounting bracket, insert and tighten the two Phillips
head screws.
B. INTELLISWITCH CONTROL BOARD REMOVAL OR REPLACE-
MENT
CAUTION: Do not expose the bare board to static electric-
ity, water, extreme heat or extreme moisture.
NOTE: The Intelliswitch Control Board may be removed
without removing the bottom access cover or transverse.
However removal of the bottom access cover and trans-
verse will simplify the process.
1. Set Intelliswitch mode to o.
2. Disconnect power to the unit.
3. Remove the two Phillips head screws from the
Intelliswitch display faceplate.
4. Remove the faceplate from the unit by gently pulling it
away from the unit and unplugging the ribbon
cable from the back.
5. Mark and remove all wires connected to the control
board.
6. Remove the two plastic push-rivets that attach the
control board to the unit frame by gently prying
a screw driver under the metal bracket attached to the
control board.
7. Carefully maneuver the control board partially out of
the unit by sliding straight down. Avoid contact
between board components and the motor mount.
8. Remove the Phillips head screw that attaches the
control board to the mounting bracket and ground
wire and completely remove the control board from
the unit.
9. Attach mounting bracket to the new control board
with existing screw only on the side that does not
contain the ground wire.
10. Partially insert the board into the unit and attach the
second Phillips head screw and ground wire.
8

14. Install the trigger bar on the replacement motor so
that it is not closer than 0.030” to the motor bearing
cap (including shaft movement).
15. Ensure the trigger does not contact the speed sensor.
Maximum gap distance between trigger and sensor is
1/16” (2mm).
16. Reinstall in reverse order of removal.
G. REPLACEMENT OF ELECTRIC HEATER ELEMENT
1. Disconnect power to the unit.
2. Remove the intake grille by removing the locking
screws on each end of the unit.
3. Lift the intake grille up and away from the unit.
4. Remove the bottom access panel by removing the
Phillips head screws on the bottom of the unit.
5. Remove and mark all wires from damaged element.
6. To remove damaged element from unit, drill out rivets
and remove screws.
7. Install new element and connect all wires.
8. Reinstall cover and intake grille.
grille up and then away from the unit.
4. Remove the bottom access panel by removing the
Phillips head screws on the bottom of the unit.
5. The speed sensor is held in with two 13 mm hex nuts
and a star washer.
6. Use the 13 mm nuts to position the tip of the sensor a
maximum of 1/16” (2 mm) away from the rotating
trigger located on the motor shaft. When the unit is
energized, the LED on the back of the sensor will
illuminate when the trigger passes if the correct
distance has been set.
CAUTION: Do not mount the speed sensor too close to
the trigger, the sensor will be ruined if it is struck by the
trigger.
7. Reinstall remaining components in reverse order of
removal.
E. INTELLISWITCH TEMPERATURE SENSOR REPLACEMENT
1. Set Intelliswitch mode to o.
2. Disconnect power to the unit.
3. Remove the wiring tray cover.
4. Cut necessary cable ties that may be holding the
brown temperature sensor lead.
5. Disconnect the temperature sensor from the socket.
6. Install new temperature sensor and all necessary
cable ties.
7. Reinstall remaining components in reverse order.
F. FAN AND MOTOR REMOVAL
1. Set Intelliswitch mode to o.
2. Disconnect power to the unit.
3. Remove the intake grille by removing the
locking screws on each end of the unit. Lift the intake
grille up and then away from the unit.
4. Remove the bottom access panel by removing the
Phillips head screws on the bottom of the unit.
5. Free the fan bearing retainer bracket(s) by loosening
the Phillips head screw lock located on the inside unit
end plate(s). Rotate them out of the way to allow the
fans to be removed.
6. Remove the transverse by removing the four (4) 5/16”
hex washer head bolts.
7. Rotate the speed sensor bracket away from the motor
by removing the Phillips screw farthest from the
motor and loosening the second Phillips screw. Do not
remove the speed sensor from the bracket.
8. Unplug motor harness from motor and remove
necessary wiring.
9. Using a 1/8” Allen wrench, loosen each set screw
attaching fan(s) to motor.
10. While holding the motor in place, loosen and remove
the motor clips.
11. Slide the fans toward the motor so that the ball bear
ings on the outer fan shaft are exposed.
12. Slowly roll the motor out of the motor mount cradle
forward and down. The hubs of the fans are exible
enough to allow the motor to move before the
fans’outer ball bearings pull out of the unit.
13. If the unit equipped with an Intelliswitch, remove the
trigger bar from the motor shaft with a 5/64” Allen
wrench.
9

How to operate your MaxAir & Zephyr Air Door
that comes with a factory installed digital programmable controller called the Intelliswitch™
INTELLISWITCH™ QUICK START OPERATION
Press the Down Arrow (Menu) button once.
NOTE: If the Down Arrow button is pressed
twice, the function will change from “Mode” to
“Fan Speed”.
Mode/Fan Speed indicator will light
Using either the Left or Right Arrow buttons,
scroll through the Modes of Operation until you
reach the desired mode.
See below to determine which mode is right for you.
OFF
OFF The unit will not run.
ON
ON The unit will run continuously unless a
start and stop time is programmed.
Mode of Operation:
AUTO
AUTO
For use with a door switch, the unit will operate
only when the door is open.
delu
“delu”
DELUXE
For use with a door switch, the unit will operate
only when the door is open with a minimum 1
minute delay before turning o when it closes.
When power is turned on to the Air Door, all of the lights on the display will light briey while the
Intelliswitch™ starts up. After startup the clock will then display. The Intelliswich is now ready to set.
NOTE: To adjust the clock, refer to section 4.5 Appendix A.
10
www.intelli-how2.com
To operate the air door:
The following modes can be customized see“Programming the Intelliswitch”for more info.
Once the Mode of Operation is selected, press
“OK” button to set and return to the clock or the
down arrow to select and adjust any of the other
available settings.
For detailed information of the Intelliswitch™ Navigation and Operation please refer to Appendix A (see pages 12-18)

PLUS
“PluS”
COMFORT
PLUS
For use on heated units only, requires a door
switch. When the temperature drops below the
thermostat set point and the door is closed, the
unit will activate on a low speed and provide
supplemental heating to the space. The unit will
change to normal speed when the door is open.
If the thermostat is still not satised when the
door closes the unit will return to low speed until
the set point is reached.
PRO1
“Pro1”
PROGRAM 1
Recommended for unheated units. This setting
will enable the air door to operate on Deluxe
mode with a 1 minute time delay, 24 hours a
day, 7 days a week.
See Appendix A page 18 for more detailed
information.
Modes of Operation continued:
PRO2
“Pro2”
PROGRAM 2
Recommended for heated units.
This setting will enable the air door to operate
on Deluxe mode with a 1 minute time delay from
8:00 am – 5:00 pm.
From 5:01 pm – 7:59 am, the unit will operate on
Comfort Plus with a 30 second time delay.
See Appendix A page 18 for more detailed
information.
PRO3
“Pro3”
PROGRAM 3
Recommended for heated units. This setting
will enable the air door to operate on Auto
mode with a 30 second time delay, 24 hours a
day, 7 days a week.
See Appendix A page 18 for more detailed
information.
11
The following modes can be customized see“Programming the Intelliswitch”for more info.

INTELLISWITCH™ FAQ’s (Frequently Asked Questions)
12
Q. Why can’t I change my settings?
A. The Intelliswitch™ may be locked. If the Lock light is illumi-
nated, the control is locked. To unlock, press and hold the left &
right arrows simultaneously for 5 seconds. The Lock mode can
also be protected with a PASScode. If the PASScode option is
on, an attempt to unlock the control will display PASS and then
a 0000 prompt. A four-digit code (available in the installation
instruction book Appendix) must then be entered to unlock
the control. Use the up and down arrows to select a number
and the left and right arrows to select the digit to edit. Press OK
when done. Note: If the AutoLock setting is on, the control will
re-lock if there is no activity after 5 minutes.
Q. Why won’t my heat work, even though fans are running?
A. The thermostat(s) or speed sensor may need adjusted or
replaced.
1.) Make sure that the thermostat probe and/or remote ther-
mostat are in the“On” position and set above ambient (room)
temperature.
2.) Check internal and external thermostat status in the Diag-
nostics Menu for a faulty thermostat. To do this, hold the right
arrow for ve seconds until DIAG appears, then arrow down to
the ts setting, if it displays “1”then the thermostat(s) is working
(there is a call for heat).
3.) If no external thermostat is used, check to see if the internal
probe is attached to the control board. Disconnect power to
the unit, remove the display board and check that the beige
sheathed cable is attached at both ends. If the thermostat(s)
and settings are correct and you are still not getting heat, then
check to see the fan speed. to do this, press the down arrow to
reach the Mode/Fan speed setting. Use the right and left arrow
to change the fan speed.
4.) Check to see if you can adjust the fan speed. If the speed
sensor is bad there will be no speed control and the Intel-
liswitch will not let the heat come on. If it is too dicult to de-
termine a change in speed, the speed sensor can be checked by
entering the DIAG menu and checking the rst error code. If ER
10 displays, the speed sensor is recognized by the Intelliswitch.
If the code ER 11 is displayed, the Intelliswitch does not recog-
nize the sensor, and it may be faulty or need adjusted closer to
the trigger bar. Turn o the power to the unit and remove the
screen to check the distance between the sensor and the trig-
ger located on the left side of the motor (use the bottom access
cover for steam/hot water heated units). The sensor should be
less than 1/16” from the trigger face. Check distance at both
ends of trigger. Adjust if necessary.
5.) If there is still no heat or speed control, you may need a new
speed sensor: consult factory.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Before servicing or cleaning unit, switch power o at service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag, to the service panel.
www.intelli-how2.com
Even though every MaxAir/Zephyr unit is individually tested at the factory before shipment,
on occasion improper functionality may be experienced. Here is a list of common questions:
Q. Why won’t the Intelliswitch light up?
A. There may not be power to the control.
1.) Check to see if the main power is turned on to the unit. Your
air curtain may have multiple disconnects, be sure all are turned
on.
2.) Verify that there is power to the board. NOTE: ONLY QUAIL-
IFED PERSONS SHALL CHECK POWER IN THE UNIT WITH THE
POWER ON. The power terminals are located directly behind
the display. Remove two Phillips screws from the Intelliswitch
display to expose the power terminals and check the line volt-
age at spade terminals L2 and 120, 208 or 240 (depending on
the voltage supplied to the unit).
3.) Check the ribbon cable connections to the display board for
a loose connector or improperly connected cable (see Installa-
tion Instructions for correct cable connection).
4.) If display still doesn’t light, unplug the speed sensor and
thermostat probe (if a heated unit) from the control board. If
the display lights, plug one component back in at a time to see
which one may be shorted. The faulty component will make
the display go blank again.
5.) If there is line voltage power at the board terminals, the
ribbon cable is correctly connected, the speed sensor and the
thermostat are working, and it is still not working, you may
need a new circuit board: consult factory.
Q. Why won’t my fans shut o?
A. The Intelliswitch may be in the wrong mode or mis-wired.
1.) Check to see if the control is in the “ON” mode, if it is, then
change the Mode to another setting.
2.) The T-Stat Mode may be set to the“both”setting and the
thermostat is calling for both Fan and Heat, change the T-Stat
Mode to “HEAT”.
3.) If there is a door switch and the unit is in a mode that is acti-
vated by it, there could be a short, mis-wiring or mixup in com-
ponents. Close the door and check the door switch status in the
Diagnostics menu. Hold the right arrow for ve seconds until
DIAG appears, then arrow down to the ds setting, if it displays
“1” then the door switch signal is closed (there is a call for fan). If
the door is closed, the signal should be“0” or open.
4.) There could be a short in the eld connections to the door
switch or the door switch leads could be mis-wired. To test,
disconnect the door switch connection at the unit. Opening the
wiring tray on top of the unit and be cautious of high voltage
connections. Disconnect the blue wires labeled 9 & 10 from the
eld wiring to the door switch or make sure they are not tied
together. There is no danger of getting shocked because the
signal is 5 volt dc. Be sure not to touch the blue wires to any-
thing metal (or grounded). The unit should shut o when it is in

heat should shut o when the wires are separated.
For more complex troubleshooting of either thermal cutouts or
heater contactors, please consult a qualied electrician or the
factory.
Q. Why didn’t the Intelliswitch save the changes I made to a
program?
A. If a program is active (a dot is illuminated by one of the
clock digits), changes can be made to any settings on the User
Menu. These changes however will only remain in eect until
the program changes to the next time zone. To make changes
permanent, settings must be changed in the program from the
Program Menu. Access the Program Menu by holding down the
left arrow for 5 seconds until “PRO” is displayed. Arrow down
to select programming and arrow left to select the program to
edit. Use the down arrow to step through the options and make
changes as desired. Continue to press the down arrow until Stor
is displayed. Press OK or down to keep or store the changes.
Q. How do I undo a change that I made to a program in the
Program Menu?
A. Changes to programs cannot be undone. The programs can
however be reset to the factory default settings. This must be
done on the Factory Menu. Access to the Factory Menu is at-
tained through the Diagnostics Menu. Press and hold the right
arrow for 5 seconds until “DIAG” is displayed. From the “DIAG”
display press and hold the up and down simultaneously for 10
seconds until “FACT” is displayed. Use the down arrow to select
“DEFn” on the display then use the right arrow to select “DEFP”.
Press “OK” to reset. The control display will go blank then blink
as conrmation.
Q. My air curtain won’t turn on?
A. Check the AM/PM setting on the Start and Stop times or the
clock (considering the AM indicator light whensetting values).
Note: set the start time and stop time to the exact time for the
unit to be active full time. Check to see if a program is active
that may have dierent start/stop times than those expected.
Q. My building has a Building Management System, can the
Intelliswitch work with a BMS?
A. The Intelliswitch can be controlled by a Building Manage-
ment System (BMS) but currently does not have the ability to
communicate with them. Dry contacts on the BMS may be used
to control the unit activation through the door switch connec-
tions (blue wires 9 & 10) and the heat activation thought the
remote thermostat connections (orange wires 6 & 7). Consult
factory.
any mode that is activated by the door switch.
5.) If the air curtain is heated, make sure that the thermostat
isn’t wired to the door switch leads. Door switch leads are blue
and labeled 9 & 10.
Q. How can I check the door switch to be sure it’s working?
A. The Intelliswitch may be in the wrong mode, be mis-wired or
have a faulty door switch.
1.) Test the wiring and controller function at the same time rst.
Locate the door switch and open its wiring compartment by re-
moving the two screws holding on the back cover. There should
be two wires connected to screws inside the switch. There is no
danger of getting shocked because the signal is 5 volt dc. Be
sure not to touch the wires to anything metal (or grounded).
Either disconnect both wires from the screws (noting which
screws the wires are under) and touch them together (with air
curtain in “Auto”mode) or make a short jumper wire and touch
the jumper to both screws at the same time to see if air curtain
comes on. If it does, the controller and wiring work.
2.) If the wiring and unit pass the function test, the problem
could be either misalignment or a faulty door switch. On a
magnetic reed switch check for magnet alignment, for plunger/
roller type switch, check contact engagement with door.
3.) If you have access to an electrical test meter, the door switch
contacts can be tested for continuity when the door switch
wires are disconnected from the unit.
Q. Why won’t my heat shut o?
A. The Intelliswitch may need adjusted, have been mis-wired or
have a faulty thermostat.
1.) Heat is activated by one of two thermostat connections.
To test the internal thermostat set the external thermostat to
OFF. The settings of the unit mounted thermostat probe are
accessed through the display. Press the down arrow until the
Temp Set indicator lights up; check if the temperature setting
and unit of measure are correct. Test to see if it shuts o by set-
ting the thermostat temperature to OFF or lower than the room
temperature.
2.) If an external thermostat is connected to the unit, there
could be a short in the eld connections or the thermostat
leads may be mis-wired. To test the external thermostat set the
internal thermostat to OFF. Disconnect the external thermostat
connections at the unit. Open the wiring tray on top of the unit
and be cautious of high voltage connections. Disconnect the
orange wires labeled 6 & 7 from the eld wiring to the thermo-
stat or make sure they are not tied together. There is no danger
of getting shocked because the signal is 5 volt dc. Be sure not
to touch the orange wires to anything metal (or grounded). The
INTELLISWITCH™ FAQ’s Continued (Frequently Asked Questions)
www.intelli-how2.com
13

Note: The OK button always saves the current entered
value and returns you to the User Menu display clock.
Section 1: Quick Start Reference
Section 2: Arrow Navigation
Section 3: Menu Structure
Section 4: User Menu
Section 5: Program Menu
Section 6: Diagnostic Menu
Section 7: Factory Menu
Section 8: External Connections
1. Quick Start Reference
1.1. Press the Menu button (down Arrow).
1.2. Using the left and right arrows, select the operating
Mode: O, On, Auto, Deluxe, Comfort Plus or Program
Number 1, 2 or 3.
1.3. Press OK.
2. Arrow Navigation
The up and down arrows select the menu options.
The left and right arrows change values for single-
level menu options (Mode, Speed, Temp Degree, Temp Set,
T-stat Mode and Day) or are used to enter into multi-level
menu options (Delay Time, Temp Set, Start Time, Stop Time
and Set Time).
Arrow sequence and available settings are illustrated under
each option.
2.1. Single Level Options
Single level options can change values directly with the left and
right arrows. No additional actions are necessary to access these
option settings.
2.2. Multi-level Options
Multi-level options require additional actions to access an op-
tions setting. The right or left arrow is required to enter into an
option.
If the multi-level option has one value to edit it may be
changed directly with the up and down arrows.
If the multi-level menu option has two values (such as a time
value) the rst option value ashes upon selection. Use the left
or right arrow to select which value to change and then use the
up and down arrows to change the option value. See the Menu
Options section for the option increment i.e. hours/minutes,
minutes/seconds.
To leave a multi-level option, use the left or right arrow to cycle
through the option value until it stops ashing. The up or down
arrow may now be used to navigate to the other options.
3. Menu Structure
The Intelliswitch™ has four menus:
• UserMenu(Section4)
• ProgramMenu(Section5)
• DiagnosticMenu(Section6)
• FactoryMenu(Section7)
The User Menu is the top level menu where values for each op-
tion is entered based on the Mode selected. Each option is iden-
tied by a green light when selected. The clock display is the
default home position for the User Menu when OK is selected or
there is no activity for 15 seconds.
Note: Access to all Secondary Menus must originate from
the User Menu. Secondary Menus are identied by the
menu title upon successful entry, e.g. PRO, DIAG and FACT.
The Program Menu is used to edit all program option param-
eters.
The Diagnostic Menu is used to diagnose and troubleshoot
errors with the Intelliswitch™.
The Factory Menu is only to be used when directed to reset or
change factory default settings.
4. User Menu
To enter into the User Menu press the down arrow (menu) or up
arrow. Use the down or up arrow to step through each option.
Each option is identied by a green light when selected.
Options available from the User Menu are:
• Mode
• FanSpeed
• DelayTime
• Thermostatdegreetype
• ThermostatSetPoint
• StartTime
• StopTime
• ThermostatControlMode
• TimeSet
• DaySet
• Lock/PASScode
4.1. Mode: single-level
NOFF-ON-AUTO-DELU-PLUS-PRO1-PRO2-PRO3O
Use left or right arrows to select the desired Mode of Operation.
Press “OK to accept selection.
• OFF – air door o.
• ON – air door will run when start/stop time is satised.
A. PROGRAMMING THE INTELLISWITCH™
To reduce the risk of injury and ensure proper operation all
Notes and instructions shall be read!
Note: The STOP button is available at all times and im-
mediately stops the unit for an emergency situation. The
Intelliswitch® will display STBY for Stand By when selected.
To release the control from STBY press STOP again. When
the control is released from STOP it will be in the OFF Mode.
Press the left or right arrows to select new Mode or OK to
return to the clock.
Note: When changing options, if there is no activity for 15
seconds, the control will save changes and default back to
the User Menu display clock.
Appendix -14
STOP

active for AUTO, DELU and PLUS Mode.
Note: to turn o this feature the Start Time must be set
equal to Stop Time (including am/pm).
4.8. Thermostat Mode: single level
NHEAT-BOTH O
Select the control mode for the built-in and remote thermo-
stats. The HEAT mode only cycles the heater on call for heat
from either internal or external thermostats when the fan is run-
ning. BOTH mode cycles both the fan and the heater on a call
for heat from either internal or external thermostats.
Note: This option is only available for electric heated air
doors with built-in thermostat or air doors with external
remote mount thermostat connected between terminals 6
& 7.
4.9. Set Time: multi-level – hours/min
Select option with right arrow, use up & down arrows to set the
clock. Note: time does not adjust for daylight savings time.
4.10. Set Day: single level
NDAY1-DAY2-DAY3-DAY4-DAY5-DAY6-DAY7 O
Use left & right arrows to select day of the week, where Sunday
= DAY1, Monday = DAY2, etc. Used as a reference by programs.
4.11. Lock/Unlock
The Intelliswitch™ can be locked to prevent unauthorized
tampering of the settings.
When locked, only the options on the User Level may be
viewed. Only the Mode can be changed between OFF and the
Mode that was active when it was locked, all other options may
NOT be changed.
To lock or unlock, press and hold the left and right arrows simul-
taneously for 5 seconds, the Locked light will illuminate.
If the PASScode option is ON, an attempt to unlock the control
will display PASS and then a 0000 prompt to enter a four digit
unlock code. Use the up & down arrows to change the numbers
and the left & right arrows to move between positions.
Note: When the AutoLock option is set to ON in the Pro-
gram Menu, the Intelliswitch™ will automatically lock after
5 minutes without any activity. Default setting – OFF. See
Section 5.2
Note: When the PASScode option is set to ON in the Factory
Menu, the Intelliswitch™ will require a code be entered to
unlock the control. Default setting – OFF. See Section 7.4.
5. Program Menu
To enter into the Program Menu hold down the left arrow for 5
seconds. PRO will display when the Program Menu is available.
Use the Program Menu to set the following options:
•Program1,2&3settings
•AutoLocksetting
•ComfortPluslowspeedsetting
•Master/SlaveStandBysetting
NPRO-AULC-PLUS-STBY O
Program Menu – single level
Use left & right arrows to select the option to change.
5.1. Program
The Intelliswitch™ can store up to three Dual-Tine Zone pro-
grams. Use the Program option to select and save User Menu
settings to be recalled at anytime.
A time zone is the period of operation dened by the use for
the unit to be active. Both zones may operate one after the
other or have gaps between them.
• AUTO – air door will run when terminals 9 & 10 are
connected through a switch (i.e. doorswitch) and the
start/stop time is satised, ALL menu options available.
• DELU – air door will run when terminals 9 & 10 are
connected through a switch (i.e. doorswitch) and the
start/stop time is satised, MUST set time delay from
1-10 minutes, T-Stat Mode NOT available.
• PLUS - air door will run when terminals 9 & 10 are
connected through a switch (i.e. doorswitch) and
the start/stop time is satised, when door is closed and
temperature drops below the set point the air door
will run on low speed with heat (low speed set on the
Program Menu), air door will run at higher user level
set speed when the door opens.
• PRO1 – Runs Program #1; see Program Menu Section,
1st digit indicator light when active.
• PRO2 – Runs Program #2; see Program Menu Section,
2nd digit indicator light when active.
• PRO3 – Runs Program #3 see Program Menu Section,
3rd digit indicator light when active.
NOTE: When Program Modes are selected changes can only
be made to the Mode, Time Delay, Temperature, Time and
Day settings. Changes will only remain in aect until the
program changes between active time zones.
NOTE: AutoLock, Comfort + Low Speed and PASSCode are
global options and their settings are the same for any Mode
selected. They will not change when the Mode or Program
changes.
4.2. Fan Speed: single-level
SP N1-2-3-4-5-6-7-8-9-10 O
Use left & right arrows to select fan speed from 1 to 10. (1=low,
10 = high)
4.3. Delay Time: multi-level – min/sec
NOFF – 00:01 thru 10:00 O
Select option with right arrow, use up & down arrows to set the
amount of time that the air door will delay shutting o after
terminals 9 & 10 or doorswitch are opened.
4.4. Temp Set (air doors): single level
N°F – °CO
Use left & right arrows to select the temperature degree type,
Fahrenheit or Celsius, for thermostat set point.
Note: This option is only available for heated units with a
built-in thermostat.
4.5. Temp Set : single level
NOFF – 34°F thru 90°F O
or
NOFF – 1°C thru 32°C O
Use left & right arrows to select the temperature set point when
the heat is to be activated.
Note: This option is only available for heated air doors with
built-in thermostat.
4.6. Start Time: multi-level – hours/min
Select this option with right arrow, use up & down arrows to set
the time that the unit is to turn on in the ON Mode or become
active for AUTO, DELU and PLUS Modes
Note: To turn o this feature the Start Time must be set
equal to Stop Time (including am/pm).
4.7. Stop Time: multi-level – hours/min
Select this option with right arrow, use up & down arrows to set
the time that the unit is to turn o in the ON Mode or become
Appendix - 15

The Program menu allows parameters for the following options
to be set:
•NumberofZones:1or2
•Daysoftheweektooperateperzone
•Mode(O-On-Auto-Deluxe-Plus)
•Speed
•TimeDelay
•ThermostatSetPoint
•StartTime
•StopTime
•ThermostatMode
To enter into the Program menu press the down arrow (menu
button) at the PRO display. Use the left & right arrows to select
the program to be edited.
NPRO1-PRO2-PRO3 O
Note: After setting the number of zones and active days all
parameters are set the same as the User Menu. Use the Up
and Down arrows to accept changes and OK to return to
User Menu.
5.1.1. Zone: single level
NZn 01-Zn 02 O
Select the number of Zones for the program. If one zone is
selected a prompt will ask to save settings after the last option.
If two zones are selected, Zone1 parameters will be set rst and
then parameters for Zone2 will be set. A prompt will ask to save
settings after the last option of Zone2.
5.1.2. Day: multi-level
Nday-day1-day2-day3-day4-day5-day6-day7 O
Select the days of the week that the program is to operate for
each zone.
When day is displayed, press the right arrow to enter into the
day parameters.
Once in the day parameters each day is identied by the day
number, use the right or left arrows to select yes to active a day
or no to deactivate a day.
Ndy 1n-dy 1yO
i
Ndy 2n-dy 2y O
i
Ndy 3n-dy 3y O
Use the up and down arrows to move to the next day or skip
days until day is displayed.
From this point enter right to re-enter day settings or down to
continue.
Note: The top seven LED’s will light from the top down rep-
resenting days 1 thru 7 that have been activated.
5.1.3. Mode: single level
Select operating mode for Zone. Only O, On, Auto or Plus are
available.
5.1.4. Fan Speed: single level
Select the fan speed for the time zone being programmed.
5.1.5. Time Delay: multi-level
Set the time delay for the time zone being programmed.
5.1.6. Temperature Set: single level
Set the temperature set point for internal thermostat for Zone
being programmed. Degree type is based on degrees selected
on the User Menu.
5.1.7. Start Time: multi-level
Set start time for zone program to activate including am/pm.
Note: Zone 1 has priority over Zone 2 and if conicting
times are entered Zone 1 will always activate and take pre-
cedence over Zone 2.
5.1.8. Stop Time: multi-level
Set stop time for zone program to activate including am/pm.
Note: Zone 1 has priority over Zone 2 and if conicting
times are entered Zone 1 will always activate and take pre-
cedence over Zone 2.
5.1.9. Thermostat Mode: single level
Set thermostat mode for Zone.
5.1.10. Store: single level
Nstr y-str n O
Use the right or left arrows to select yes to save program or no
to abandon changes.
A single zone program will prompt to save all options after the
rst set of parameters; a dual zone program will prompt to save
after the second set of parameters.
Note: upon saving, the LED on the digit light corresponding
to the program number will blink.
5.2. AutoLock: multi-level
NON-YES O
To enter into the AutoLock menu press the down arrow (menu
button) at the AULC display. Use the left or right arrows to se-
lect ON to have control automatically lock if there is no activity
for 5 minutes or OFF to deactivate.
5.3. Comfort Plus (fan speed): multi-level
SP N1-2-3-4-5-6-7-8-9-10 Osee Note*
To enter into the Comfort Plus low speed setting, press the
down arrow (menu button) at the PLUS display. Use the left or
right arrows to select the fan speed for the PLUS mode, when
the door is closed and the thermostat set point is reached.
*Note: The speed range is limited to be equal to of less than
that of the User Menu speed setting.
5.4. Master/Slave Stand By: multi-level
Nind-ALL n O
To enter into the Master/Slave stand by setting press the down
arrow at the STBY display. Use the left or right arrows to select
the STOP button behavior when units are connected together
in a Master/Slave conguration. Select “ind”or independent to
stop only the unit where STOP is pressed. Select “ALL” to stop all
connected units.
6. Diagnostic Menu
To enter into the Diagnostic Menu hold down the right arrow
for 5 seconds. DIAG will display when the Diagnostic Menu is
available.
The Diagnostic Menu is used to diagnose and troubleshoot In-
telliswitch™ errors. Only “live”parameter settings are displayed,
there are no options to change.
Appendix -16

Appendix - 17
Er 51 – Status of this error is not available. It only appears when
there has been an event that has corrupted the settings in
memory. When corrupted settings are identied the control
will reset all settings (except for Speed Range) back to Factory
default values. Because some speed ranges are not compat-
ible with all motors, the proper value cannot be automatically
set and therefore requires user input. This is prompted by the
scrolling “Set FACt SPEEd” on the display.
Solution – press the “OK” button. This will open the range set-
ting identied by “rn”. Select the correct speed range (see Sec-
tion 7.1) based on the Series/Model. Press“OK” button.
6.11.6. Error Code 6 – Incompatible Speed Range for Mas-
ter/Slave Operation
Er 61 – Status of this error is not available. It only appears when
unit are connected in a Master/Slave conguration that do not
have identical Speed Range settings.
If two units are connected without equivalent speed ranges,
every time a button is pressed on the Master unit (the unit used
to make setting selections) the Slave unit will display an“Er 61”
and the Slave will ignore the command to protect the control
from damaging the motor.
Solution – Enter the Factory Menu to select the proper Speed
Range (See Sections 7 and 7.1)
Note: This error does not monitor if the correct speed range
has been selected for a Series/Model. Only that two or more
units have been connected that do not have equivalent
speed ranges.
Note: Once the correct speed ranges are selected and the
controls accept commands from one another, the controls
should be synchronized by simply cycling through all of the
settings on the User Menu using the up or down arrows.
None of the settings need to be changed.
7. Factory Menu – Service Personnel Only
The Factory Menu must be entered from the DIAG header. To
enter into the Factory Menu hold down the right arrow for 5
seconds. DIAG will display when the Diagnostic Menu is avail-
able. From the DIAG display, press and hold the up and down
arrows simultaneously for 10 seconds. FACT will display when
the Factory Menu is available.
Note: When the Factory Menu is accessed it automatically
shut the unit o by changing the Mode to OFF.
The Factory Menu is used to change or reset core settings to
change base functions or resolve Intelliswitch™ errors.
The Factory Menu allows parameters for the following options
to be set:
•SpeedRangeSetting
•RestoreFactoryDefaultSettings
•RebootSoftware
•PASScode
•SupplyVoltageFrequency
To enter into the Factory Menu from the header press the down
arrow. Use the left & right arrows to change setting values. Use
the OK button select action and return to the User Menu.
7.1. Speed Range: single level
rn N0 – 1 – 2 – 3 – 4 – 5 – 6 – 7 – 8 – 9 – 10 -11 – 99 O
Select the fan speed range from 0 to 11 using the left or right
arrows. The speed range for each unit is located on the unit wir-
ing diagram called out in a box in the Intelliswitch® schematic
by “SPEED rn __”.
The Diagnostic Menu displays the following parameters:
•Softwareversionrelease
•SpeedRangeSetting
•InternalThermostatreading–Celsius
•InternalThermostatreading–Fahrenheit
•Motorrpmreading
•SupplyVoltageFrequency
•DoorSwitchstatus
•ExternalThermostatstatus
•HeaterRelaystatus
•ErrorCode1–SpeedSensor
•ErrorCode2–LineFrequency
•ErrorCode3–PowerIssue
•ErrorCode4–MotorOFault
6.1. Software Release Version – Format: rX.XX
6.2. Fan Speed Range – rn XX (see Section 7.1)
6.3. Thermostat Probe – Pr XX (see Section 7.2)
6.4. Internal Thermostat – ºC (np = no probe)
6.5. Internal Thermostat – ºF (np = no probe)
6.6. Motor RPM – measured speed in rpm
6.7. Supply Voltage – measured frequency in Hz
6.8. Door Switch Status – 0=open, 1=closed
6.9. External T-stat Status – 0=open, 1=closed
6.10.Heater Relay Status – 0=open, 1=closed
6.11.Error Codes
The Intelliswitch has six error codes, 1 through 6, to help
troubleshooting. The status of 1-4 can be observed from the
Diagnostic Menu. The format for displaying the error code is the
“Er” descriptor and a two digit code. The rst digit is the error
number and the second digit is the status using international
convention. 0 = inactive, 1 = on or active.
6.11.1. Error Code 1 – Speed Sensor
Er 10 – Prox Sensor or Speed feedback exists
Er 11 – NO Prox Sensor or Speed feedback
Solution – check to see if the proximity sensor (located next
to the motor) is connected to the control board and check
distance between tip and trigger bar is approximately 1/16 of
an inch.
6.11.2. Error Code 2 – Line Frequency
Er 20 – power supply line frequency exists
Er 21 – undetermined supply line frequency
Solution – The Intelliswitch automatically senses line fre-
quency. In the event that it can not determine the proper line
frequency, it will run at full speed and ash error. Manually set
the line frequency in the FACT menu. See Section 7.5.
6.11.3. Error Code 3 – Zero Cross/Power Issues
Er 30 – clean power exists
Er 31 – poor power exists, electrical noise
Solution – When the control encounters “noise”in the electrical
power supply it will run at full speed and ash error code. There
are no internal changes available. Have the electrical system
checked for problems.
6.11.4. Error Code 4 – Speed Feedback
Er 40 – proper motor and sensor operation
Er 41 – Motor o but receiving prox/speed sensor feedback
Solution – this is usually the result of a failing motor control
component on board that cannot be serviced. A replacement
board is required.
6.11.5. Error Code 5 – Corrupted Memory Setting

Appendix - 18
8.2. Heat Mode Activation
When terminals 6 and 7 in the junction box are connected
(closed), the Heat Mode is activated for all Operating (On, Auto,
Deluxe, Plus and Programmable) Modes. The Intelliswitch™ uses
a low 5 volt DC voltage signal to monitor contact closure.
If the internal thermostat is left on, the external heat mode
will operate in parallel to contact closure, allowing either one
to activate the heat. If the internal thermostat is turned o the
external heat mode will activate independently to activate the
heat.
8.2.1. External Thermostat
An external (remote) thermostat connection can be used to
sense temperature independent of the built-in thermostat.
Connect thermostat to terminals 6 and 7 in the air door
junction box.
8.2.2. Building Management System
A building management system or dry contact closure can be
used to activate the Heat Mode for all Operating Modes. Con-
nect applicable contacts to terminals 6 and 7 in the air door
junction box.
8.3. Master/Slave Operation
For Master/Slave Operation a serial cable connection must be
made between all Intelliswitch™ controls of each air door to be
linked.
Once air doors are linked all Menu settings made through any
air door display or remote control will transfer to all other linked
air doors.
Parameter changes made on any linked air door will update all
other boards “live”upon menu selections.
9. Infra-red Remote Control
The handheld infra-red remote control buttons, layout and
operation are the same as that on the Intelliswitch™ air door
display (including multiple button presses) with one exception,
the Lock Button.
There is no need for multi-button press and hold for lock/unlock
activation. The Lock Button will lock/unlock display in one press.
Note: Selecting the incorrect speed range can damage the
motor(s) beyond repair and potentially create abnormally
high temperatures.
Speed ranges are dependent upon the air curtain Series, motor
type and heat option.
MAX/ZPR (1/5 hp) – all voltages use ranges 0-2
Available ranges are:
0 = ambient – variable 10-speed, 600 rpm to full
1 = ambient – variable 10-speed, 1050 rpm to full
2 = heated – variable 10-speed, 1250 rpm to full
3 = ambient – full on, no adjustment
4 = heated – full on, no adjustment (monitored)
5 = heated – full on, no adjustment (not monitored)
6 = ambient – multiple 3-speed, ITC relay control
7 = heated – multiple 3-speed, ITC relay control
8 = ambient – variable 3-speed, 1250 rpm to full
9 = heated – variable 3-speed, 1250 rpm to full
10 = ambient – multiple 2-speed, ITC relay control
11 = heated – multiple 2-speed, ITC relay control
99 = lock out – scrolling request for user input
7.2. Thermostat Probe Mode: single level
In “St” (Standard) mode the lowest operating point for the
thermostat probe is 34°F (1°C). Below this temperature there
will be no call for heat and“nP” (no Probe) will display on the
diagnostics menu.
In “Cd” (Cold) mode the thermostat will operate below 34°F
(1°C) but disables the “nP” (no Probe) feature and will call for
heat on a probe failure or if it is disconnected.
St - Standard mode, locks out below 34°F (1°C). Cd - Cold
mode, works below 34°F (1°C).
7.3. Restore Factory Default: single level
DEF Nn – U – P – A – tO
If it is necessary to restore any of the controls settings back to
the factory defaults, select DEF using the down arrow. Select
the factory setting restore type using the left or right arrows.
This will reset the option settings back to the factory default
settings. Available selections are:
DEFn – no changes
DEFU – reset User Menu ONLY settings
DEFP – reset Programs ONLY settings
DEFA – reset ALL settings (user and program)
DEFt – set controller to factory TEST parameters
7.4. Reboot Software: single level
Nreb y – reb n O
If an error occurs that can be xed by rebooting the control
software, select REB using the down arrow. Select YES or NO to
reboot the control.
7.5. PASScode multi-level
NPAS y – PAS n O
Select y to enable the PASScode feature and n to disable. When
active, the PASScode feature requires that a four digit code be
entered to unlock the control. The code is: 2376
7.6. Line Frequency: single level
NFr Au – Fr 60 – Fr 50 O
The Intelliswitch® default is to automatically sense the line volt-
age frequency. If it cannot be determined automatically, the
line frequency may be manually selected.
Au – Automatically Sense
60 – 60 Hz power supply
50 – 50 Hz power supply
8. External Connections
There are three types of external connections available on the
Intelliswitch™.
•DoorSwitch
•ExternalThermostat
•SerialConnection
8.1. Auto Mode Activation
When terminals 9 and 10 in the junction box are connected
(closed), the Auto, Deluxe, Plus and Programmable Modes are
activated. The Intelliswitch™ uses a low 5 volt DC voltage signal
to monitor contact closure.
8.1.1. Door Switch (limit switch)
The door or limit switch is used in conjunction with the Auto,
Deluxe, Plus and Programmable Modes to signal that the door
is open. Connect the door or limit switch to terminals 9 and 10
in the air door junction box.
8.1.2. Building Management System
A building management system or dry contact closure can be
used to activate the air door through the Auto, Deluxe, Plus and
Programmable Modes. Connect applicable contacts to termi-
nals 9 and 10 in the air door junction box.

• Airstreamtooweak
• Airsteamhitsobstruction
• Negativepressure
• Shaftrotatinginsidefan
• Onemotornotoperating
• Nozzlenotangledoutfarenough
• Unittoopowerful
• Airmovementtoocold
• Pushingairoutsidebuilding
SEEAIRIS NOT HITTING FLOORSYMPTOMS
• Switchturnedto“ON”position
• Thermostatnotsetproperly
• Coilsburnedoutduetolackofair
• Automaticresetthermalcutoutfailedinopenposition
• Manualresetthermalcutouttripped(ifsupplied)
• Speedsensornotdetectingtriggerrotation
• Withoutspeedadjustment,failedspeedsensor
• Adjustnozzletoproperposition,adjustmotorspeed;
seeinstallationinstructions
• Removeobstructionorrepositionaircurtain(moveout
3/8”forevery1”upfromthedoor)
• Relievenegativepressurebyprovidingmakeupair
• Tightensetscrews
• Repairorreplacemotor
• Adjustnozzleangletooutside
• Adjustmotorspeed
• Addauxiliaryheattoovercomewindchillfactor
• Adjustdischargeanglebackintobuilding,adjustmotor
speed
• Replaceswitchorcheckwiring
• Changethermostatsetting
• Correctairowproblem;replacecoils
• Replaceautomaticthermalcutout
• Resetmanualthermalcutout
• Adjustgapbetweensensorandtrigger
• Replacespeedsensor
AIR IS NOT HITTING
FLOOR
UNEVEN AIR
EXCESSIVE AIR
MOVEMENT AT DOOR-
WAY
ELECTRICALLY HEATED MODELS
NO HEAT
MINIMAL HEAT
EXCESSIVE HEAT
STEAM/HOT WATER HEATED UNITS
EXCESSIVE HEAT
MINIMAL HEAT
NO AIR • Powersupplylineopen(nopower)
• Fuseblown/circuitbreakertripped
• Motoroverloadtripped
• Failedswitch
• Checkpowersource,checkmethodofcontrolinON
position
• Replacefuse(s)/resetbreaker
• Internallyprotectedmotor-shouldresetautomatically
aftercool-down,ifnot,replacemotor.
• Replaceswitch
MOTOR RUNNING/FANS ARE NOT ROTATING
MINIMUM AIR
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
X. TROUBLESHOOTING
SYMPTOMS REMEDY
CAUSE
NO SPEED
ADJUSTMENT
• Speedsensornotdetecting
triggerrotation
• Adjustgapbetweensensor&trigger/
replacesensor
• Brokenordamagedexiblehub
• Shaftrotatinginsidefan
• Selectorswitchisinoffposition
• Doorlimitswitchnotoperating
• Airdirectionaldischargevanesmis-adjusted
• Inadequateintakeclearance
• Blowermotoroperatesbelowspeed
• Fanrubbingagainsthousing
• Fanwheelscloggedwithdirt
• Faninbackwards
• Replacefansleeve/reengagecoupling
• Tightensetscrews/tightenfanonshaft
• Turnswitchto“ON”position
• Repairorreplacelimitswitch
• Adjustvanestoproperposition,seeinstructions
• Moveaircurtainorremoveobstruction
• Provideadequatespaceforaircurtain
• Impropervoltage
• Freefanfromhousing
• Cleanandvacuumfanwheels
• Checkfansforbladecurvetowarddischarge
• Thermostatinwronglocation-thermostattoo
closetodischarge
• Impropervoltage
• Thermostatnotsetproperly
• Speedsensornotdetectingtriggerrotation
• Incorrectspeedrange
• Thermostatinwronglocation
• Thermostatnotsetproperly
• Insufcientairovercoil
• Impropervoltage
• Toohighsteam/hotwaterpressure
• Inadequateairow,nspluggedup,dirtycoils
• Insufcientremovalofcondensation(steam)
• Notenoughsteampressure/watertemperaturetoo
low
• Intakeairbelowdesigntemperature
• Movethermostatawayfromairstream
• Supplypropervoltage
• Changetemperaturesetting
• Adjustgapbetweensensor&trigger/replacesensor
• Setdipswitchtoelectricheatedspeedrange
• Movethethermostatclosertoairstream
• Changetemperaturesetting
• Removerestrictiononintake
• Supplypropervoltage
• Reducesteampressure/hotwaterow
• Cleanintakeandcoils
• Increasetrapsize
• Raisepressureforsteam/increasewaterow
• Increasesteampressure/increasewaterow
19

XI. WARRANTY
Berner International (“The Company”) warrants all new equipment to be free of defects in workmanship and material for a period
of ve years (5 years) on unheated models and two years (2 years) on heated models from the original date of shipment, provided
the equipment has been properly cared for, installed and operated in accordance with the limits specied on the nameplate and The
Company’s instructions.
The Company will correct by repair or replacement, at its option and expense, any proven defects in said apparatus, subject to the above
conditions, provided that immediate written notice of such defects is given to The Company. The warranty does not include any labor
incurred for the removal or installation of defective part(s). The Company reserves the right to inspect, or have inspected by a qualied
representative, any apparatus at the place of installation before authorizing repair or replacement. Repair or replacement will be made
F.O.B. factory with any applicable transportation charges to be borne by the customer. Merchandise not of The Company’s manufacture
supplied in piece, or in component assemblies, is not covered by the above warranty, but The Company will give the customer the benet
of any adjustment as made with the Manufacturer.
This warranty is void if the apparatus has been tampered with in any way or shows evidence of misuse.
The Company will not assume any expense or liability for repairs made outside its factory without proper written consent from its service
manager, nor for any transportation charges on apparatus returned to the factory without written authorization by The Company.
Nothing in the above warranty provisions, however, shall impose any liability or obligation of any type, nature or description upon Berner
International if Berner has not received payment in full for the apparatus in question.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HERE OF INCLUDING
THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
LIMITATION OF DAMAGES
Notwithstanding anything to the contrary above, customer’s exclusive remedy for any and all losses or damages resulting
from the sale of The Company’s equipment under this agreement, including but not limited to, any allegations of breach of
warranty, breach of contract, negligence or strict liability, shall be limited, at The Company’s option, to either the return of
the purchase price or the replacement of the particular equipment for which a claim is made and proved. In no event shallThe
Company be liable for any special, consequential, incidental or indirect losses or damages from the sale of The Company’s
equipment under this agreement.
BERNER INTERNATIONAL CORPORATION
New Castle, Pennsylvania
724-658-3551 • 1-800-245-4455 • www.berner.com • airdoors@berner.com
© Copyright 2013 Berner International Corporation MADE IN U.S.A.
Berner reserves the right to alter specifications without prior notice.
20
SERIAL NUMBER MODEL NUMBER DATE PURCHASED
This manual suits for next models
19
Table of contents
Other Berner Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Daikin
Daikin FXHQ32MVE installation manual

Koldwave
Koldwave K6CC10BEA2AA00 owner's manual

Mitsubishi Electric
Mitsubishi Electric MXZ-8C60NA installation manual

Armstrong
Armstrong HWC PREMIER 122 Service reference manual

Sharp
Sharp AH-A07CR Operation manual

hecht
hecht 3909 TRANSLATION OF ORIGINAL INSTRUCTIONS FOR USE