Bitzer BDC 152 (2F) (V) User manual

OPERATING INSTRUCTIONS
BITZER AUSTRALIA
BUFFALO TRIDENT HEAT EXCHANGE
BDC Series Air Cooled Condensers
Models: BDC 152 (2F) (V) BDC 152 (2F) (H) BDC 456 (6F)
BDC 228 (3F) (V) BDC 228 (3F) (H) BDC 608 (8F)
BDC 304 (4F) (V) BDC 304 (4F) (H) BDC 760 (10F)
BDC 380 (5F) (V) BDC 380 (5F) (H)
1. Important Recommendations
• BDC air cooled condensers are intended for installation only by Qualied Refrigeration Personnel
and are to be installed in accordance with the guidelines mentioned in this manual.
• All electrical work is to be carried out by Qualied Electrical Personnel and to be in accordance with
local electrical regulations.
2. Safety Recommendations
• Condensers are supplied with a Nitrogen Holding Charge. (Release pressure fully before accessing the
connection points).
• Electrical power is to be isolated prior to the commencement of any electrical work.
• During normal operation Pressurised Refrigerant is contained within the condenser. Extreme care
should be taken to avoid leakage, as personal injury may occur. (Avoid the use of sharp objects in
close proximity to refrigeration piping).
• Extensive gas loss in enclosed area may result in asphyxiation.
• Contact with refrigerant may cause personal injury (freeze burns).
• Normal operating conditions involve hot surfaces within the condenser. Extreme care should be taken
to avoid contact.
• Avoid contact with condenser ns as sharp edges may cause personal injury.
1. Important Recommendations ........................... 1
2. Safety Recommendations ................................ 1
3. Application Ranges .......................................... 2
4. Installation Guide ............................................. 2
5. Electrical Connections ..................................... 7
6. Wiring Diagram .................................................8
7. Commissioning Instructions ............................. 9
8. Maintenance Instructions ................................. 9
9. De-commissioning Instructions ........................ 9
10. Manufacturer ....................................................9
11. Service Address ................................................9
Contents
HXO-504-1 AUS

2
HXO-501-1 AUS
• Insertion of any object into condenser fans is to be avoided as this may result in personal injury and/or
equipment damage.
• Operating sound pressure levels may cause discomfort. Refer to catalogue for calculated sound levels
3. Application Ranges
• These condensers are intended for use in commercial refrigeration systems with a maximum operating
ambient temperature of approximately 60°C (special designs available on application).
• Recommended refrigerants: HFCs, HCFCs (also suitable for CFCs).
• This series of condenser is not suitable for use with NH3 (Ammonia), R410a or R744 (CO2).
• Standard condensers are not to be installed in hazardous/combustible environments.
4. Installation Guide
The BDC Series of Air Cooled Condensers are suitable for Vertical and Horizontal air ow.
a) Mounting - Vertical Air Flow
• Remove the condenser from its crate.
• Vertical air ow condensers are shipped without legs tted.
• Legs are supplied within each BDC Series condenser crate.
• Using an appropriate lifting device (refer Figure 1 for recommended lifting methods), attach the
legs to the condenser using the bolt kit supplied.
• Place the condenser into the installation position and secure using the mounting holes located in
the legs.
b) Mounting - Horizontal Air Flow
• Remove the condenser from its crate.
• Horizontal airow condensers are shipped with mounting feet tted in nal position.
• Using an appropriate lifting device (refer Figure 2 for recommended lifting methods).
• Place the condenser into the installation position and secure using the mounting holes located in
the feet.
NOTE:
• Minimum diameter of xing bolts is to be 12.70mm (½”)
• The use of lifting devices during installation is recommended where applicable
• Observe recommended condenser mounting locations as per Figure 2.1, parts 1 and 2
• Remove the transport brackets from the BDC Series condensers (vertical only)
• Ensure the condenser is installed level, to avoid liquid locking within the condenser
• Refrigeration piping connections should be carried out in accordance with the current Refrigeration
Code of Good Practice* (beware of HOT surfaces present during the welding procedure).

HXO-501-1 AUS
3
Fig. 1
No. of Fans (1 & 2 Module) A
2 3000
3 1500
4 3000
5 4500
4500
60
MAX
680 MIN
LENGTH
SPREADER BAR
DISCHARGE LINE
CONNECTION
LIQUID DRAIN
CONNECTION
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATE
DRAWN BY
BDC 5F-6R ASSY (WITH SPREADER)
1:40
A3
SHT.4 of 4
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
-
BDC 5F-6R V MAIN ASSY (WITH SPREADER)
T.CAVANAGH
23/8/17
REFER BOM / -
4500
2260
MIN LENGTH
60
MAX
SPREADER BAR
DISCHARGE LINE
CONNECTION
LIQUID DRAIN
CONNECTION
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATE
DRAWN BY
BDC 5F-6R-V-2M MAIN ASSY (WITH SPREADER)
1:30
A3
SHT.4 of 4
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
-
BDC 5F-6R-V-2M MAIN ASSY (WITH SPREADER)
T.CAVANAGH
-
26/5/17
-
Material <not specified> / -

4
HXO-501-1 AUS
4500
60
MAX
800 MIN
LENGTH
SPREADER BAR
DISCHARGE LINE
CONNECTION
LIQUID DRAIN
CONNECTION
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATE
DRAWN BY
BDC 5F-6R-H MAIN ASSY (WITH SPREADER)
1:20
A3
SHT.3 of 3
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
1076.32
BDC 5F-6R-H MAIN ASSY (WITH SPREADER)
T.CAVANAGH
-
01/08/17
-
REFER BOM / -
No. of Fans A
2 3000
3 1500
4 3000
5 4500
Fig. 2

HXO-501-1 AUS
5
RECOMMENDED MOUNTING LOCATIONS FOR VERTICAL AIR FLOW CONDENSERS
Note: All clearance dimensions listed below are calculated with standard issue BUFFALO TRIDENT condenser
legs tted.
Condensers installed on a solid deck
Model/s
(Dimensions in mm)
BDC 152
(2F)
BDC 228
(3F)
BDC 304
(4F)
BDC 380
(5F)
BDC 456
(6F)
BDC 608
(8F)
BDC 760
(10F)
A 970 1250 1390 1680 1390 1810 2080
B 1530 1810 2080 2440 2080 2640 3050
C 1250 1530 1810 2140 1810 2220 2500
D 1940 2360 2910 1680 2910 3470 4020
E1250 1530 1810 2140 1810 2220 2500
Model/s
(Dimensions in mm)
BDC 152
(2F)
BDC 228
(3F)
BDC 304
(4F)
BDC 380
(5F)
BDC 456
(6F)
BDC 608
(8F)
BDC 760
(10F)
A 970 1250 1390 1680 1390 1810 2080
B 1110 1390 1530 1680 1530 1940 2220
C 1250 1530 1810 2140 1810 2220 2500
D 1530 1810 2080 2440 2080 2640 3050
E1530 1940 2220 2600 2220 2780 3190
Condensers installed on an open mesh platform 0.5m high from a solid deck
Condensers installed on an open mesh platform 1.0m high from a solid deck
Model/s
(Dimensions in mm)
BDC 152
(2F)
BDC 228
(3F)
BDC 304
(4F)
BDC 380
(5F)
BDC 456
(6F)
BDC 608
(8F)
BDC 760
(10F)
A 970 1250 1390 1680 1390 1810 2080
B 700 970 1110 1220 1110 1390 1530
C 1250 1530 1810 2140 1810 2220 2500
D 970 1250 1390 1680 1390 1810 2080
E1940 2360 2640 2900 2640 33330 3750

6
HXO-501-1 AUS
Figure 2.1 - Part 1/2
Installation with solid air restriction to 1 side of platform For a multiple condenser:
Installation with solid air restriction to 1 side of 1
end of platform
For an individual condenser:
Installation with solid air restriction to 1 side of 1 end of platform

HXO-501-1 AUS
7
"Y"
"Y"
"X"
"X"
5000
1600
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATE
DRAWN BY
BDC 5F-6R-H MAIN ASSY
1:50
A3
SHT.4 of 4
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
971.93
BDC 5F-6R-H MAIN ASSY (INSTALLATION)
T.CAVANAGH
-
01/08/17
-
REFER BOM / -
"Y"
"Y"
"X"
"X"
5000
1600
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATE
DRAWN BY
BDC 5F-6R-H MAIN ASSY
1:50
A3
SHT.4 of 4
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
971.93
BDC 5F-6R-H MAIN ASSY (INSTALLATION)
T.CAVANAGH
-
01/08/17
-
REFER BOM / -
"Y"
"Y"
"X"
"X"
5000
1600
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATE
DRAWN BY
BDC 5F-6R-H MAIN ASSY
1:50
A3
SHT.4 of 4
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
971.93
BDC 5F-6R-H MAIN ASSY (INSTALLATION)
T.CAVANAGH
-
01/08/17
-
REFER BOM / -
Figure 2.1 - Part 2/2
* Maximum height of solid air restriction from condenser platform is 2.8m.
**Avoid obstructions within 2 x Diameter of fan above condenser
For alternative condenser deck arrangements, please contact BITZER Australia.
Model/s
(Dimensions in mm)
BDC 152
H (2F)
BDC 228 H
(3F)
BDC 304
H (4F)
BDC 380
H (5F)
X 1050 1575 2100 2625
Y 1500 2250 3000 3750
* Avoid horizontal air discharge installation where prevailing wind
would create additional static load on fans, especially at low fan
speeds (< 680 RPM)
5. Electrical Connections
• EC Fan motors are suitable for 400 Volt ±10%, 50 Hz operation.
• All three phase motors are pre-wired to an independent isolation switch within an IP56 rated electrical
junction box mounted on the condenser.
• These motors are to be wired in accordance with Fig. 3 (wiring diagram R55000117 shown over the page).

8
HXO-501-1 AUS
SCALE
PART No.
COPYRIGHT DRAWING: The information contained herein is the property of BITZER Australia. & shall not be copied, reproduced,
used for manufacture or for any other purpose without the prior written permission of BITZER Australia.
DATEDRAWN BY
EC BLUE WIRING DIAGRAM
N.T.S
A3
SHT.1 of 1
BITZER
AUSTRALIA
Pty Ltd
A.B.N. 70 057 670 023
3rd ANGLE
PROJECTION
DATE
APPROVED BY
INSPECTION DIMENSIONS
XXXXX
DECIMAL : ± 1.0mm
ONE DECIMAL : ± 0.5mm
TWO DECIMAL : ± 0.2mm
ANGLE : ± 0.5°
U.N.O TOLERANCES
MASS (kg)
MATERIAL & FINISH
NAME
DO NOT SCALE
ALL DIMENSIONS ARE IN mm
UNLESS OTHERWISE SPECIFIED.
DRAWING STANDARD AS1100
-
R55000117
T.CAVANAGH
A.SESTITO
27/02/17
-
/-
REV. ECN DESCRIPTION DRN APPD DATE
REVISIONS
0 566
GENERIC EC BLUE WIRING DIAGRAM
TC
6/4/2017
6/4/2017
AS
Figure 3
EC wiring diagram - R55000117
Wiring diagram applicable to all 800mm and
910mm EC fans, for one or multiple fans
6. Wiring Diagram

HXO-501-1 AUS
9
7. Commissioning Instructions
• Leak testing should be carried out in accordance with the current Refrigeration Code of Good
Practice*.
• Following leak testing, the system should be evacuated using accepted refrigeration practices. The
vacuum pump should be connected to both the high and low pressure sides of the system with all shut-
o valves open.
• Refrigerant charging should be carried out in accordance with the current Refrigeration Code of Good
Practice*.
• Extreme care should be taken to avoid direct contact with liquid refrigerant (freeze burns).
• Ensure the electrical wiring is in accordance with local electrical regulations and ensure fan motor
direction is correct.
8. Maintenance Instructions
• Bualo Trident condensers require low maintenance apart from regular cleaning of the n face.
Frequency is dependent upon the operating environment of the condenser.
• It is recommended that n surfaces are cleaned using a soft bristle brush and/or low pressure water,
taking care to avoid all electrical components (electrical power must be isolated prior to cleaning).
• All fan motors contain bearings and are maintenance free.
9. De-commissioning Instructions
• Pump down refrigeration system into the receiver or suitable container. (As per Refrigeration Code of
Good Practice *)
• Isolate power and remove electrical wiring (remove earth wire last) and associated components where
necessary.
• Disconnect refrigeration piping and seal both the system and condenser connections (ensure that
positive/negative pressure does not exist in condenser prior to disconnection).
• Condenser can now be removed from location (the use of lifting devices during removal is
recommended where applicable).
* Code of Good Practice produced in conjunction with AFCAM.
10. Manufacturer
Our products are manufactured in compliance with applicable international standards and regulations. If you have
any questions about how to use our products or if you are planning special applications please contact:
BITZER Australia Pty Ltd
Bualo Trident Division
25 Strzelecki Avenue
Sunshine VIC 3020, Australia
Tel.: +61 (0)3 8326 8200
Fax: +61 (0)3 9310 2520
www.bitzer.com.au
11. Service Address
For local support please refer to our website www.bitzer.com.au for your nearest branch oce.

BITZER Australia Pty Limited
134 Dunheved Circuit,
St Marys, NSW 2760
Australia
tel +61 (2) 8801 9300
fax +61 (2) 9673 4698
Victoria
tel +61 (3) 8326 8200
fax +61 (3) 9310 2520
Queensland
tel +61 (7) 3725 1360
fax +61 (7) 3274 3621
South Australia
tel +61 (8) 8345 6110
fax +61 (8) 8268 4555
Western Australia
tel +61 (8) 6350 6297
fax +61 (8) 9359 2077
BITZER New Zealand
BITZER Australia Pty Ltd
Unit 5, 5-7 Henry Rose Place
Albany 0632
Auckland
New Zealand
tel +64 9 415 2030
www.bitzer.com.au
In the interest of continuous improvement BITZER reserves the right to change the specifications or design of any of its
products without notice. The BITZER Symbol, Name BITZER and model numbers are registered trade marks. All products
manufactured are pending design and specification registration and must not be copied or duplicated in any way.
Note: The ISO standard only applies to the BITZER NSW and VIC branches
09.2017