Access Control Bus System
- the access control system with RS485 bus interface
- installation and configuration manual
- version 5

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
2
Table of contents
1INTRODUCTION.....................................................................................................................................................................................................4
1.1 General information.................................................................................................................................................................................4
1.2 System characteristics..............................................................................................................................................................................4
1.3Basic system functionality ........................................................................................................................................................................4
2BKT ACBS and BKT ACWS SYSTEMS.......................................................................................................................................................................5
3BKT ACBS SYSTEM COMPONENTS.........................................................................................................................................................................6
3.1 AC100 controller.......................................................................................................................................................................................6
3.2 AB101 secondary set................................................................................................................................................................................9
3.3 Card readers...........................................................................................................................................................................................12
3.4 Cabinet swinghandles............................................................................................................................................................................. 17
3.5 Door sensors........................................................................................................................................................................................... 19
3.6 Connection cables ..................................................................................................................................................................................20
3.7 System software.....................................................................................................................................................................................22
4BKT ACBS SYSTEM STRUCTURE ........................................................................................................................................................................... 22
4.1 System structure in a single cabinet.......................................................................................................................................................22
4.2 System structure in cold/hot aisle containment ....................................................................................................................................23
5INSTALLATION OF CABINET DOOR DEVICES........................................................................................................................................................ 24
5.1 AC100 controller installing .....................................................................................................................................................................24
5.2 AB101 secondary set installing...............................................................................................................................................................28
5.3 AR121, AR131 readers installing ............................................................................................................................................................ 30
5.4 AL200 swinghandle installing ................................................................................................................................................................. 31
5.5 AL300 swinghandle installing ................................................................................................................................................................. 33
5.6 Door sensors installing ........................................................................................................................................................................... 34
5.7 Installation of cabinet door wiring .........................................................................................................................................................35
5.8 Diagram of functional circuits for operating the cabinet door...............................................................................................................38
6INSTALLATION OF COLD/HOT AISLE CONTAINMENT SLIDING DOOR DEVICES ...................................................................................................39
6.1 AC100 controller installing .....................................................................................................................................................................39
6.2 AR122, AR132 readers installing ............................................................................................................................................................ 39
6.3 Installing exit button and emergency button .........................................................................................................................................39
6.4 Installing optional exit buttons...............................................................................................................................................................40
6.5 Installing sliding doors wiring................................................................................................................................................................. 40
6.6 Connection diagram of sliding kiosk door control devices ..................................................................................................................... 41
6.7 Diagram of functional circuits for operating the sliding door.................................................................................................................42
7DEVICE LOW LEVEL CONFIGURATION.................................................................................................................................................................43
7.1 Controller low level configuration..........................................................................................................................................................43
7.2 Card reader low level configuration ....................................................................................................................................................... 45
8SVC SOFTWARE...................................................................................................................................................................................................48
8.1 SVC software installation........................................................................................................................................................................48
8.2 SVC software configuration....................................................................................................................................................................49
9VISO ST SOFTWARE.............................................................................................................................................................................................52
9.1 VISO ST software installation .................................................................................................................................................................52
9.2 Database configuration ..........................................................................................................................................................................52
9.3 Controller configuration.........................................................................................................................................................................53
9.4 Data synchronising .................................................................................................................................................................................55
9.5 Cabinet door configuration ....................................................................................................................................................................56
9.6 Cold/hot aisle containment sliding door configuration.......................................................................................................................... 61
9.7 Permanent opening of the cold/hot aisle containment sliding door...................................................................................................... 64

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
3
9.8 Two user entry ....................................................................................................................................................................................... 67
9.9 Open door signalling with LED................................................................................................................................................................68
9.10 Tamper signalling ...................................................................................................................................................................................74
9.11 Emergency button use signalling............................................................................................................................................................81
9.12 Adding user group ..................................................................................................................................................................................87
9.13 Adding user to group.............................................................................................................................................................................. 88
10 DOCUMENT REVISIONS....................................................................................................................................................................................... 92

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
4
1INTRODUCTION
1.1 General information
The specification is owned and copyrighted by BKT Elektronik Sp. z o.o. Information contained herein may be changed at owner’s discretion
without any notice. BKT Elektronik may not be held liable for any possible inaccuracies and discrepancies in this document.
1.2 System characteristics
The access control system is designed to limit the access of unauthorized persons to sensitive parts of data centers, smaller server rooms, as well
as to individual cabinets. BKT ACS (Access Control System) is a scalable access control system dedicated to 19'' frames. BKT Elektronik offers
cabinets that are factory-adapted to the installation of an access control system. These cabinets have doors equipped with appropriate openings
for mounting card readers and cable paths for arranging the wires. The BKT ACS system can also be applied to any teleinformation cabinets with
a 19'' frame. It is then required to make appropriate openings in the door for card readers and to fasten the cables with, for example, cable ties.
The BKT ACBS access control system (Access Control Bus System) uses devices (controllers and readers) that communicate using the RS485 bus.
The controllers are placed in 1U casings adapted to be mounted in 19'' cabinets. A single controller, depending on the version, can supervise the
operation of up to 16 doors. The number of controllers in the system is unlimited. In the same system, it is also possible to connect controllers
supporting readers with Wiegand interface - BKT ACWS system (Access Control Wiegand System). Both systems use Roger RACS5 devices. This
manual contains basic information sufficient to run the BKT ACBS access control system. More technical information about the devices used in
the system can be found at www.roger.pl/en.
1.3 Basic system functionality
•Supports unlimited number of cabinets.
•Supports unlimited number of users, subject to a maximum of 8192 per controller.
•Supports different card standards depending on the reader used.
•The system may grant access to the door by presenting a card or entering a PIN code (or may require both actions at the same time).
It is also possible to configure the so-called committee entry when two users have to present cards to open the door.
•Depending on the system, the readers may have an integrated keypad (BKT ACBS) or may be integrated in a cabinet handle (BKT
ACWS). It is also possible to use any reader with a Wiegand interface.
•Archiving of events in the MS SQL Server or MS SQL Compact database for small installations.
•Stand-alone operation of the system - without connection to a computer with a database. In such situation, up to 8 million events
can be saved to the controller's internal memory, which will be sent to the computer during the next connection.
•Independent monitoring of the door status and the status of the handle.
•Free VISO ST application for system configuration and monitoring.
•Encrypted communication on the Ethernet network and on the RS485 bus.
•Email notifications about any chosen event.
•The system devices meet the requirements of security Grade 2 according to the EN 60839-11-1: 2013 standard
•The devices are adapted to be mounted in a 19'' frame. They are 1U high.
•Ease and speed of making connections thanks to the use of RJ45 connectors.
•BKT 4DC cabinets are available in a version adapted to the installation of access control devices. They have appropriate openings for
the reader and dedicated cable paths on the door.

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
5
2BKT ACBS and BKT ACWS SYSTEMS
The BKT ACS access control system is available in two variants:
•BKT ACBS (Access Control Bus System) - system based on the RS485 bus, which is used by controller to communicate with card
readers.
•BKT ACWS (Access Control Wiegand System) - system that uses the Wiegand interface for communication between the controller and
card readers.
Both versions use the same Roger MC16-PAC controller, so they can work in the same system managed by the same VISO ST application. The
table below lists the main differences between the system variants.
System structure
Interface
between the
controller and
the reader
Supported
standard of
proximity cards
Possibility of
connecting a
handle with an
integrated reader
- AL301
Possibility of
connecting any
third party
reader with
Wiegand
interface
1 controller (1 IP
address) for
many cabinet
doors
BKT ACBS
Bus System
RS485 bus
UNIQUE 125kHz
or Mifare
13,56MHz
(Ultralight and
Classic)
Max 16 cabinet
doors
BKT ACWS
System with
Wiegand
interface
Wiegand
Any standard
dependent on
the reader
Max 2 cabinet
doors

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
6
3BKT ACBS SYSTEM COMPONENTS
3.1 AC100 controller
AC100 - Access controller in 1U 19'' enclosure, no power supply unit (122AA100015), no
controller pcb (122AC1020xx). Designed to support readers with RS485 interface.
The controller is the basic device of the system.
Requires the Roger MC16-PAC-x controller pcb. Depending on the used PCB of the
controller, it can support from 1 door (MC16 PAC-1) to 16 doors (MC16-PAC-16)
The controller has a 1U casing, adapted to be mounted in a 19'' cabinet.
The number of controllers in the system is unlimited.
The controller enables connection of two door sensors, two door readers, an
additional reader for cold/hot aisle containment sliding door, LAN network and RS485
bus connecting slave sets. All connections to the controller are made with cables with
RJ45 connectors.
The controller has two configurable LEDs, which for example, can indicate the status of
the front and rear doors of the cabinet.
Two-way power supply possible.
Requires one or two 12VDC 1.5A power supplies.
3.1.1 Technical data
Parameter
Value
Power supply voltage
Nominal 12V DC, allowed 12-15V DC
Average current consumption
(with controller pcb and no external devices)
110 mA
Connectors
8 x RJ45 (for peripheries), 2 x DC 5,5/2,1 (for power supplies)
Dimensions
482 x 132 x 44mm (W x D x H)
Weight
1100g
Package dimensions
265 x 165 x 70mm
Package weight
1200g
Operating conditions
Temperature: 5°C - 40°C, Humidity: 10% - 95% RH (no condensation)
Storage conditions
Temperature: 0°C - 60°C, Humidity: 0% - 95% RH (no condensation)
Housing material
Steel
Housing colour
Black, RAL 9005
Housing protection rating
IP20
Compliance with directives
2014/35/EU (LVD), 2011/65/EU (RoHS)
Part number
122AC001000

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
7
3.1.2 Dimensions
3.1.3 AC100 controller accessories
Product
Description
Part number
MC16-PAC-x - x door controller RACS5
122AC1020xx
GST18A12-P1J - Power supply 18W 12VDC 1.5A; AC socket C14; DC plug 5.5/2.1; no AC
cord
122AA100015
Power cord, plug IEC 320 C13 10A, plug DIN 49441(unischuko) 16A, 3x1,0 mm2, black, 2m
11480784.2
Power cord, plug IEC 320 C13 10A, plug IEC 320 C14 10A, 3x1,0 mm2 black, 2m
11480785.2

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
8
3.1.4 Controller wiring schematic

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
9
3.2 AB101 secondary set
AB101 - Access control secondary set for 2 doors in 1U 19'' enclosure, no power supply
unit (122AA100015). Works with the AC100 controller.
The kit includes a connection system for devices for handling 2 doors.
It has a 1U housing, suitable for mounting in a 19 "rack.
The set works only with controller AC100.
Designed for installation in subsequent cabinets.
It enables connection of two door sensors, two door readers and an additional reader
for cold/hot aisle containment sliding door, LAN network and RS485 bus connecting
slave sets. All connections to the controller are made with cables with RJ45 connectors
The controller has two configurable LEDs, which for example, can indicate the status of
the front and rear doors of the cabinet.
Two-way power supply possible.
Requires one or two 12VDC 1.5A power supplies.
3.2.1 Technical data
Parameter
Value
Power supply voltage
Nominal 12V DC, allowed 12-15V DC
Average current consumption
(with no external devices)
10 mA
Connectors
7 x RJ45 (for peripheries), 2 x DC 5,5/2,1 (for power supplies)
Dimensions
482 x 44 x 44mm (W x D x H)
Weight
800g
Package dimensions
265 x 165 x 70mm
Package weight
900g
Operating conditions
Temperature: 5°C - 40°C, Humidity: 10% - 95% RH (no condensation)
Storage conditions
Temperature: 0°C - 60°C, Humidity: 0% - 95% RH (no condensation)
Housing material
Steel
Housing colour
Black, RAL 9005
Housing protection rating
IP20
Compliance with directives
2014/35/EU (LVD), 2011/65/EU (RoHS)
Part number
122AB001011

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
10
3.2.2 Dimensions
3.2.3 AB101 secondary set accessories
Product
Description
Part number
GST18A12-P1J - Power supply 18W 12VDC 1.5A; AC socket C14; DC plug 5.5/2.1; no AC
cord
122AA100015
Power cord, plug IEC 320 C13 10A, plug DIN 49441(unischuko) 16A, 3x1,0 mm2, black, 2m
11480784.2
Power cord, plug IEC 320 C13 10A, plug IEC 320 C14 10A, 3x1,0 mm2 black, 2m
11480785.2

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
11
3.2.4 Secondary set wiring

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
12
3.3 Card readers
3.3.1 Dimensions
3.3.2 Card reader accessories
Product
Description
Part number
AW111 –Reader to controller connection cable, 5m
The cable is used to connect the reader AR121, AR122, AR131, AR132 to AC100
controller or AB101 secondary set.
Length: 5m, terminated with RJ45 and 10-pin female connectors.
244AW001110
AW113 - Reader to housing sliding door controller connection cable, 5m
The cable is used to connect the reader AR122, AR132 to sliding door controller
Length: 5m, terminated with RJ45 and 10-pin male connectors.
244AW001130
Electrical junction box 86mm x 86mm x 39mm, wall mount, black, IP55
122AA100006
RUD-1 - USB-RS485 interface/programmer
122AA101000
EMC-1 - UNIQUE EM 125 kHz thin proximity card
122AA101004
MFC-2 - MIFARE Classic 1k 13.56 MHz thin proximity card
122AA101011

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
13
3.3.3 AR121 Unique card reader with keypad
Product
Description
Part number
AR121 (MCT12E-IO) –Unique 125kHz card reader with keypad for cabinet door
Roger MCT12E-IO reader was used
Reader adapted to control the cabinet door. It has a 15cm long cable terminated with
multi-pin connectors to connect to the lock and cabinet controller.
It reads EM Unique 125kHz proximity cards, reading range up to 7 cm.
Three LED indicators, buzzer with adjustable sound level, keyboard with backlight, two
function buttons, detection of housing opening and detachment from the surface.
12V, 50mA power supply from a controller or a slave set.
Dimensions: 153 x 46 x 23 (HxWxD)
More information can be found at www.roger.pl
244AR001210
3.3.4 AR121 card reader wiring schematic
To controller
To cabinet swinghandle

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
14
3.3.5 AR122 Unique card reader with keypad
Product
Description
Part number
AR122 (MCT12E-IO) - Unique 125kHz card reader with keypad for cabinet housing sliding
doors
Roger MCT12E-IO reader was used
The reader is designed to control the sliding doors of the cabinet housing. It has a
40cm long cable terminated with multi-pin connectors to connect to the sliding door
controller and to the system controller. The wiring arrangement is different than in the
AR121 reader.
It Reads EM Unique 125kHz proximity cards, reading range up to 7 cm.
Three LED indicators, buzzer with adjustable sound level, keyboard with backlight, two
function buttons, detection of housing opening and detachment from the surface.
12V, 50mA power supply from a controller or a slave set.
Dimensions: 153 x 46 x 23 (HxWxD)
More information can be found at www.roger.pl
244AR001220
3.3.6 AR122 Card reader wiring schematic
To controller
To sliding doors
controller

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
15
3.3.7 AR131 Mifare card reader with keypad
Product
Description
Part number
AR131 (MCT12M-IO) - Mifare 13,56 MHz card reader with kepad for cabinet door
Roger MCT12M-IO reader was used
Reader adapted to control the cabinet door. It has a 15cm long cable terminated with
multi-pin connectors to connect to the lock and cabinet controller.
It reads Mifare 13.56MHz proximity cards, reading range up to 7 cm.
Three LED indicators, buzzer with adjustable sound level, keyboard with backlight, two
function buttons, detection of housing opening and detachment from the surface.
12V, 85mA power supply from a controller or a slave set.
Dimensions: 153 x 46 x 23 (HxWxD)
More information can be found at www.roger.pl
244AR001310
3.3.8 AR131 Card reader wiring schematic
To controller
To cabinet swinghandle

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
16
3.3.9 AR132 Mifare card reader with keypad
Product
Description
Part number
AR132 (MCT12M-IO) - Mifare 13.56MHz card reader with keypad for cabinet housing
sliding doors
Roger MCT12M-IO reader was used
The reader is designed to control the sliding doors of the cabinet housing. It has a
40cm long cable terminated with multi-pin connectors to connect to the sliding door
controller and to the system controller. The wiring arrangement is different than in the
AR121 reader.
It reads Mifare 13.56MHz proximity cards, reading range up to 7 cm.
Three LED indicators, buzzer with adjustable sound level, keyboard with backlight, two
function buttons, detection of housing opening and detachment from the surface.
12V, 85mA power supply from a controller or a slave set.
Dimensions: 153 x 46 x 23 (HxWxD)
More information can be found at www.roger.pl
244AR001320
3.3.10 AR132 Card reader wiring schematic
To controller
To sliding doors
controller

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
17
3.4 Cabinet swinghandles
3.4.1 AL200 swinghandle
Product
Description
Part number
AL200 - Electronic locking & monitoring swinghandle with mechanical override
Installation in a standard 150x25mm cut out.
Can be installed in a single and multi-point locking system.
Three-color LED signalling the operation status of the swinghandle.
Monitoring the status of the handle and the ability to transfer information to the
access control system.
Emergency key override.
Nominal current consumption during lock operation: 250mA
Quiescent current consumption: 90mA
Dimensions: 177 x 37 x 51 (H x W x D)
122AL002000
3.4.2 AL200 Dimensions
3.4.3 AL200 connectors
8-pin socket (53047-0810)
1
GND
Power supply input: GND.
2
+12V
Power supply input: +12V.
3
STATUS
Handle status (active low, when handle open)
4
CTRL
Handle control (+12V or GND to open the handle)
5
SENSOR
Do not connect
6
GND
Do not connect
7
CANL
Do not connect
8
CANH
Do not connect
4-pin socket (53047-0410)
1
GND
Do not connect
2
+12V
Do not connect
3
WIEGAND 0
Do not connect
4
WIEGAND 1
Do not connect
3.4.4 AL200 accessories
Product
Description
Part number
AW212 - AL200 swinghandle to AR121 or AR131 reader connection cable, 0.55m
The cable is used to connect the reader AR121, AR131 to AL200 swinghandle.
Length: 0.55m, terminated with 10-pin male and 8-pin female connectors.
122AW002120

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
18
3.4.5 AL300 swinghandle
Product
Description
Part number
AL300 (H3-EM-60-100) - Electronic locking & monitoring swinghandle with mechanical
override
Standard 150x25mm mounting cutout.
Supports single and multi-point locking.
Opening signalled by a built-in LED.
Monitored status of the handle and the ability to pass information to the access
control system.
The lock can be opened with a key in the event of a power failure.
Nominal current consumption during lock operation: 200mA
Quiescent current of the handle: 50mA
Dimensions: 168 x 37 x 50 (HxWxD)
122AL103001
3.4.6 AL300 Dimensions
3.4.7 AL300 connectors
1 –Power supply GND
2 - Power supply +12V
3 –N/C
4 –Control (+12V, to open handle)
5 –Electrical status (active low, when handle is open)
6 –Mechanical status (active low, when handle is open)
3.4.8 AL300 accessories
Product
Description
Part number
AW112 –AL300 swinghandle to AR121 or AR131 reader connection cable, 0.55m
The cable is used to connect the reader AR121, AR131 to AL300 swinghandle.
Length: 0.55m, terminated with 10-pin male and 6-pin female connectors.
244AW001120
6-pin male socket
AL300

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
19
3.5 Door sensors
3.5.1 AD101 Single leaf door sensor
Product
Description
Part number
AD101 –Single leaf door reed sensor with 5m cable
Sensor normally open (NO)
5m long wire terminated with an RJ45 plug to connect to the controller.
The set has a metal bracket that fixes the reed switch to the cabinet frame.
244AD001010
3.5.2 AD101 Door sensor wiring
3.5.3 AD102 - Double leaf door sensor
Product
Description
Part number
AD102 –Double leaf door reed sensor with 5m cable
Sensors normally open (NO)
5m long wire terminated with an RJ45 plug to connect to the controller.
The set has a two metal brackets that fixes the reed switches to the cabinet frame.
244AD001020
3.5.4 AD102 Door sensor wiring

www.bkte.pl
BKT ACBS - installation and configuration manual of the access control system with RS485 bus interface
20
3.6 Connection cables
3.6.1 AW111 cable
Product
Description
Part number
AW111 –Reader to controller connection cable
The cable is used to connect the reader AR121, AR122, AR131, AR132 with the AC1xx
controller.
5m long, terminated with RJ45 plug and a 10-pin female connector.
244AW001110
3.6.2 AW111 cable wiring
3.6.3 AW113 cable
Product
Description
Part number
AW113 - Reader to housing sliding door controller connection cable
The cable is used to connect the reader AR121, AR122, AR131, AR132 with the
cold/hot aisle containment sliding door controller.
5m long, terminated with RJ45 plug and male 10-pin connector.
244AW001130
3.6.4 AW113 cable wiring
This manual suits for next models
1
Table of contents