
1 INTRODUCTION
1.1 Scope and definitions
This manual provides installation, operation and maintenance instructions for the BOC
Edwards Model 250 Water-Cooled Exhaust Trap. You must use the Exhaust Trap as specified in
this manual.
Read this manual before you install and operate the Exhaust Trap. Important safety information
is highlighted as WARNING and CAUTION instructions; you must obey these instructions. The
use of WARNINGS and CAUTIONS is defined below.
WARNING
Warnings are given where failure to observe the instruction could result in injury or death
to people.
CAUTION
Cautions are given where failure to observe the instruction could result in damage to the
equipment, associated equipment and process.
The units used throughout this manual conform to the SI international system of units of
measurement.
1.2 Description
1.2.1 General
Refer to Figure 1. The Exhaust Trap cools the exhaust gases from the pump and causes
particulates to collect in the Exhaust Trap. This prevents the collection of particulates in the
exhaust-system. The Exhaust Trap is designed for connection to a pump which is used in an
LPCVD nitride process using dichlorosilane or hexachlorodisilane and ammonia. The
Exhaust Trap is not suitable for connection to a pump which is used in other processes.
The Exhaust Trap is designed to fit BOC Edwards CDP and QDP dry pumps and Drystar MKI,
MKII and QMKII dry pumping systems. Your system must incorporate a pressure switch to
shut-down the pump if the exhaust system becomes blocked.
The Exhaust Trap has a main outer body (6) which is mounted on a baseframe (12). You can
adjust the height of the trap-body in the baseframe to fit the Exhaust Trap to different pumps.
The baseframe has castors (10) for ease of movement of the Exhaust Trap and levelling feet (9) so
that you can securely locate the Exhaust Trap in its operating position.
Model 250 Water-Cooled Exhaust Trap 1