1GENERAL INFORMATION
1.1 The Signal-20M Intrusion and Fire Alarm Panel (hereinafter referred to as Panel) is intended for use as a combined device to
monitor and control alarms in the following systems:
–Fire alarm and extinguishing systems
–Evacuation and alarm system of Type 1 and Type 2
–Intrusion detection and panic alarm system
–Auxiliary alarm systems
1.2 The Signal-20M supports conventional (nonaddressable) threshold wire-connected detectors.
1.3 The Signal-20M can operate as a processing module of rate-of-rise heat detectors and supports sensing elements (thermal cables)
detecting temperature threshold exceedance.
1.4 The Signal-20M automatically monitors communication lines with detectors, call points and actuating devices of fire protection
systems.
1.5 The panel is not a scalable system.
1.6 The panel supports connection to PC for control and programming functions.
1.7 The panel is designed for 24\7 continuous operation
1.8 The panel is a reparable device with periodic maintenance
1.9 The Panel is not designed for the use in aggressive, dust, explosive and fire-hazardous environments.
2SPECIFICATIONS Table 2.1 Panel specifications
No
Description
Value
2.1
DC supply voltage, V
10.2 … 28.0
2.2
Consumption current, mA, no more *
- in ‘Quiescent’mode
- in ‘Fire’ mode
* excluding current consumption of alarm devices
400
650
2.3
Power inputs
2
2.4
Startup time, s
5
2.5
Inputs
20
2.6
Voltage on unloaded input terminals, V
26.5 … 27.5
2.7
Input short-circuit current limitation, not more than, mA
26.5
2.8
Resistance of input terminal resistor, kΩ
4.7±5 %
2.9
Max. current consumption of all detectors in standby mode, mA
- Type 1 (Fire smoke) inputs
- Type 2 (Fire combined) inputs
3.0
1.2
2.10
Input resistance in various states
See Table 2.2
2.11
Maximum allowable resistance of the sensing element of a linear heat detector (thermal
cable), kΩ
1.5
2.12
Input communication line:
- max. wire resistance (excluding terminal resistor), Ω
- insulation resistance of wires, not less, mΩ
100
50
2.13
Input voltage reset time, s
3,0
2.14
Number of outputs:
- non-monitored, ‘dry contact’ (130 VAC / 170VDC, 0.1 A)
- monitored (10.2 ... 28.0 V, 2.5 A)
3
4
2.15
Rated load current of monitored output, mA
5 … 2500
2.16
Output terminal resistance, kΩ
4.7±5 %
2.17
Voltage (negative) on inactive output with the connected terminal resistor, mV
- 1100 … - 2200
2.18
Output line health check current (reverse), no more, mA
- 1.5
2.19
Ingress protection according to GOST 14254-2015
IP40
2.20
Mechanical tolerance according to OST 25 1099-83
Placement category 3

2
Table 2.1 Panel Specifications (continued)
No
Description
Value
2.21
Vibration load:
- Frequency range, Hz
-Accelerated up to
1 … 35;
0,5
2.22
Mechanical stability according to ОСТ 25 1099-83
О3
2.23
Operating temperatures, °С
–30 … + 55
2.24
Air humidity , % (at + 25 °С)
98
2.25
Weight , kg
0.5
2.26
Dimensions , mm
332 х 177 х 42
2.27
Mean time between failures in Quiescent mode, h
- no less than 80000
2.28
Probability of no-failure
- 0.98758
2.29
Average service life , years
10
2.30 The Panel meets the standards of industrial radio interference established for equipment of class V in accordance with GOST R
51318.22
2.31 The industrial radio interference tolerance of the panel meets requirements for Severity of Third Level of GOST R500009.
Table 2.2Input Resistance in Different States
Type
Input States
Type 1 –Fire
Smoke
Short-Circuit
Activation of two and
more smoke detectors
Activation of one
smoke detector
Normal
Open Circuit
R < 100 Ω
0.15…1.56* kΩ
1.1*…2.0 kΩ
2.4…5.4 kΩ
R > 6.6 kΩ
* –Depends on the current consumed by
detectors in quiescent mode
Type 2 –Fire
Combined
Short-Circuit
Activation of smoke
detector
Normal
Activation of heat
detector
Open Circuit
R < 100 Ω
0.15…1.8 kΩ
2.2…5.4 kΩ
6.6…14.4 kΩ
R > 16 kΩ
Type 3 –Fire
Heat
Short-Circuit
Normal
Activation of one heat
detector
Activation of two or
more heat detectors
Open Circuit
R < 1.8 kΩ
3.0…5.4 kΩ
6.6…11 kΩ
12.5…22.5 kΩ
R > 25 kΩ
Type 4 –
Intrusion
Normal
Intrusion Alarm
2.2…10 kΩ
R < 1.8 kΩ or R > 12 kΩ.
or resistance jump of more than 10 %
Type 5 –
Intrusion and
Tamper
Normal
Intrusion Alarm
Tamper Alarm
2.2…5.4 kΩ
R < 1.8 kΩ or
R > 6.6 kΩ
or jump exceeding 10
%
6.6…9.0 kΩ;
R > 20 kΩ;
R < 100 Ω
Type 6 –
Auxiliary
Aux Input Normal
Aux Input Activated
2.2…5.4 kΩ
R < 1.8 kΩ or R > 6.6 kΩ
Type 7 –Lobby
Normal
Intrusion Alarm (Lobby)
2.2…5.4 kΩ
R < 1.8 kΩ or R > 6.6 kΩ.
jump of more than 10 %
Type 11 –Panic
Normal
Panic (Attack)
2.2…5.4 kΩ
R < 1.8 kΩ or R > 6.6 kΩ.
jump of more than 10 %
Aux
Programmable
State 1*
State 2*
State 3*
State 4*
State 5*
Lees than R1*
R1* to R2*
R2* to R3*
R3* to R4*
More than R4*

3
Table 2.2 Input Resistance in Different States
Type 16 –Fire
Manual
Short-Circuit
Fire2
Normal
Fire2
Open Circuit
R < 100 Ω
0.15…1.8 kΩ
2.2…5.4 kΩ
6.6…14.4 kΩ
R > 16 kΩ
Type 17 –
Flood Alarm
Flooding Detected
Flood Detector Normal
Open Circuit
R < 1.8 kΩ
2.2…5.4 kΩ
R > 6 kΩ
Type 18 –
Manual Release
Short-Circuit
RCU Activation
RCU Activation
RCU Activation
Open Circuit
R < 100 Ω
0.15…1.8 kΩ
2.2…5.4 kΩ
6.6…14.4 kΩ
R > 16 kΩ
3STANDARD DELIVERY
Reference No.
Description
Qty
АЦДР.425513.017
Signal-20M Intrusion and Fire Alarm Control Panel
1
Set of spare parts and accessories :1
Resistor 0.5 W –4.7 kΩ
(MF 1/2W-4K7±5% or MF 1/2W-4K7±1% or similar )
24
Screw 1- 3х25.016 GOST 1144-80
4
Wall plug 6х30
4
Documents:
АЦДР.425513.017 РЭ
Signal-20M Operation Manual 2)
1
Note:
1) DS1990A dongles are optional delivery.
2) The User Guide can be downloaded at the product page at www.bolid.ru
4DESIGN, INSTALLATION AND CONNECTION
Design, installation and connection procedures are described in full detail in the User Guide (full version) downloadable on the
Signal-20M page at www.bolid.ru .
5DESCRIPTION AND OPERATION
The description of the product and its operation are provided in in full detail in the User Guide (full version) downloadable on the
Signal-20M page at www.bolid.ru .
6FUNCTIONALITY CHECK
The functionality check instructions are provided in full detail in the User Guide (full version) downloadable on the Signal-20M
page at www.bolid.ru .
7MAINTENANCE AND REPAIR
7.1 The maintenance shall be provided by persons qualified for Safety of Class II at least.
The Product maintenance shall be preventive and scheduled providing for annual scheduled maintenance. Routine maintenance activities
include:
–checking the external state of the device;
–checking the reliability of the device fastening, the condition of external installation wires, contact connections;
–functionality check in accordance with para 6 of this manual.
7.2 Maintenance is recommended to be carried out using the methodological manual ‘Maintenance of fire alarm systems and SOUE
type 1-2 in Orion ISS that can found at: bolid.ru.
4.1 . Failure of the product as a result of non-compliance by the consumer with the installation or operation rules is not a basis for a
complaint and warranty repair.
4.2 If any issues are encountered during product operation, it is recommended to contact technical support by multi-line phone +7
4.3 The inoperative equipment should be sent to: ZAO NVP ‘Bolid’, Russia, 141070, Moscow region, Korolev, st. Pionerskaya,
4.Tel./fax: +7 (495) 775-71-55 (multichannel), e-mail: info@bolid.ru.
Attention!
Removing the panel print circuit board from the enclosure will automatically void the manufacturer's warranty.

4
8Shipment, storage, and disposal
8.1 The product can be shipped and stored in the shipment container at ambient temperatures of -50 to +55 С and relative humidity up
to 95% at a temperature of +35 С.
8.2 In consumer packaging, storage is allowed only in heated rooms at temperatures from +5 to +55 С and relative humidity up to
80% at a temperature of +20 С.
8.3 The device is disposed of taking into account the absence of toxic components in it.
8.4 Content of precious materials: does not require accounting during storage, write-off and disposal (clause 1.2 of GOST 2.608-
78).
8.5 Content of non-ferrous metals: does not need to be taken into account when writing off and further disposal of the product.
9MANUFACTURER WARRANTY
9.1 The manufacturer guarantees that the Signal-20M panel meets with technical requirements if the user follows the instructions for
shipment, storage, installation, and usage.
9.2 Warranty period is 18 months but no more than 24 months from the manufacturer's date of issue
10 CERTIFICATION
10.1 The Signal-20M fire alarm control panel complies with the requirements of the 'Technical Regulations on Fire Safety Requirements'
(Federal Law No. 123-FZ) and has a certificate of conformity No. RU C-RU. CHS13.V.00155 / 19 issued by the certification body OS
'POZHTEST' FGU VNIIPO EMERCOM of Russia, 143903, Moscow region, Balashiha, md. VNIIPO, 12.
10.2 The Signal-20M fire and intrusion alarm control panel meets the requirements of the Customs Union Technical Regulations
‘Electromagnetic Compatibility of Technical Means’ (TR TS 020/2011). Has a declaration of conformity: EAC No. RU D-
RU.HP15.B.06633 / 20.
10.3 The Signal-20M fire and intrusion alarm control panel is a part of the Orion addressable fire alarm system which has a certificate of
conformity No. BY / 112 02.01.033 00573, issued by the Institution 'Republican Center for Certification and Expertise of Licensed
Activities 'Ministry of Emergency Situations of the Republic of Belarus, 220088, Minsk, st. Zakharova, 73a.
10.4 9.4 The Signal-20M fire and intrusion alarm control panel is a part of the Orion fire alarm and control system which has a certificate
of conformity No. BY / 112 02.01.033 00845, issued by the Institution ‘Republican Center for Certification and Expertise of Licensed
Types of Activities’ Ministry of Emergency Situations of the Republic of Belarus, 220088, Minsk, st. Zakharova, 73a.
10.5 9.5 The Signal-20M fire and intrusion alarm control panel has certificates of conformity of technical means of ensuring transport
security with the requirements for their functional properties No. MVD RF.03.000036 and No. MVD RF.03.000037.
10.6 9.6 The production of devices has a certificate of conformity GOST R ISO 9001. The certificate of conformity is posted on the
website bolid.ru in the section ‘ABOUT THE COMPANY’.
11 ACCEPTANCE CERTIFICATE
The Signal 20-M Intrusion and Fire Alarm Control Panel Serial No________ manufactured and accepted in accordance with the
requirements of national standards and applicable technical documentation is approved as ready for use and packaged by the Bolid
Company.
Responsible for the acceptance and package
QCD _________________________________ _____________________________
Name Date/month/year
Note!
The equipment must be submitted for repair assembled and clean, in the complete set as specified in the technical
documentation.
Claims are accepted only if there is an attached claim with a description of the malfunction.