manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. bolid
  6. •
  7. Fire Alarm
  8. •
  9. bolid IPR 513-3M User manual

bolid IPR 513-3M User manual

Other manuals for IPR 513-3M

1

Other bolid Fire Alarm manuals

bolid ShPS-12 User manual

bolid

bolid ShPS-12 User manual

bolid S2000-SP2 User manual

bolid

bolid S2000-SP2 User manual

bolid S2000-IP-03 User manual

bolid

bolid S2000-IP-03 User manual

Popular Fire Alarm manuals by other brands

Simplex 4010ES Quick reference guide

Simplex

Simplex 4010ES Quick reference guide

Global Fire Equipment VALKYRIE AS manual

Global Fire Equipment

Global Fire Equipment VALKYRIE AS manual

Zeta Alarm Systems INFINITY ID2 installation manual

Zeta Alarm Systems

Zeta Alarm Systems INFINITY ID2 installation manual

System Sensor 22051TLE-RF-26 Installation and maintenance instructions

System Sensor

System Sensor 22051TLE-RF-26 Installation and maintenance instructions

Pittway Notifier AM2020 troubleshooting guide

Pittway

Pittway Notifier AM2020 troubleshooting guide

Ampac ZoneSense user manual

Ampac

Ampac ZoneSense user manual

Kidde VM-1 Technical reference manual

Kidde

Kidde VM-1 Technical reference manual

LST SIM016-3 Specification sheet

LST

LST SIM016-3 Specification sheet

Fireboy- Xintex FBD-MZ Owner's Manual & Installation Instructions

Fireboy- Xintex

Fireboy- Xintex FBD-MZ Owner's Manual & Installation Instructions

GST DI-9204 Installation

GST

GST DI-9204 Installation

Fire-Lite Alarms MS-2 instructions

Fire-Lite Alarms

Fire-Lite Alarms MS-2 instructions

hyfire HY5000 Series install guide

hyfire

hyfire HY5000 Series install guide

Radionics Radionics 9124 user guide

Radionics

Radionics Radionics 9124 user guide

UniPOS FD 7120 instruction manual

UniPOS

UniPOS FD 7120 instruction manual

Teletek electronics SensoMAG MRB50 installation instructions

Teletek electronics

Teletek electronics SensoMAG MRB50 installation instructions

FIREGUARD GLOBAL FG-S01_AP quick start guide

FIREGUARD GLOBAL

FIREGUARD GLOBAL FG-S01_AP quick start guide

Panasonic MEW01091 operating instructions

Panasonic

Panasonic MEW01091 operating instructions

Notifier UZC-256 installation manual

Notifier

Notifier UZC-256 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1
RESETTABLE MANUAL CALL POINT
IPR 513-3M
INSTRUCTION MANUAL
1TECHNICAL DATA
1.1 General
IPR 513-3M Resettable Manual Call Point (hereinafter referred to as the call point or the IPR 513-3M) is designed to be used in fire
alarm systems and fixed fire-fighting systems to manually release fire alarms or activate the system respectively.
The IPR 513-3M is to be powered through an alarm loop of such control and indicating equipment (hereinafter referred to as the
CIE) as S2000-4, Signal-20P, S2000-ASPT, Signal-10, Signal-20M or similar that provides a voltage up to 30 V within the alarm
loop and limits the current in the loop up to the level of 25 mA.
The flip transparent protective cover of the IPR 513-3M can be sealed with an intact control seal.
The manual call point is intended for round-the-clock operation and classified as a repairable and periodically maintained item.
1.2 Specifications 1.3 Scope of Delivery
1) Commuted Voltage -30 V max For a group delivery:
2) Commuted Current -25 mA max –IPR 513-3M -10 pcs.;
3) Current Consumed in Quiescent Mode -50 uA max –Instruction Manual -1 copy;
4) Ingress Protection Rating -IP40 –Special Housing Key -10 pcs.;
5) Operating Temperatures -Minus 30°C to +55°C –Woodscrew 1-4×30.20.019 GOST 1144-80
-20 pcs.;
6) Relative Humidity -Up to 93% at +40°C –Wall Plug 8×30 -20 pcs.;
7) Transportation / Storage Temperatures -Minus 30°C to +55°C –Unit Package -10 pcs.
8) Overall Dimensions -95 ×91 ×34 mm –Group Package -1 pc.
9) Weight 0.15 kg max
10) The content of precious materials: doesn’t require accountability for storage, retirement, and disposal.
11) The content of non-ferrous metals: does not require accountability for retirement and further disposal.
2OPERATION INSTRUCTIONS
2.1 Wiring
Figure 1 shows a typical diagram for connecting IPR 513-3M. While connecting a manual call point to a CIE, please be guided by
the user’s manual for the CIE in use and the diagram for connecting the manual call points to this CIE.
1– Control and indicating equipment (CIE),
2, 3– IPR 513-3M manual call points,
4– An end-of-line device (resistor, diode, etc.)
Figure 1
The quiescent mode of the IPR 513-3M is indicated by single flashing of its built-in LED
once per 4 seconds.
Once the manual call point is activated, its LED starts showing solid light confirming that the
CIE has received the signal from the IPR 513-3M. In this process the IPR 513-3M decreases
its internal resistance down to 500 Ohm max.
2.2 Mounting
The IPR 513-3M is to be mounted using the two screws provided to a flat vertical surface in
line with Buildings Codes and Regulations.
The wires which pass under the IPR 513-3M should not be clamped by the
IPR 513-3M
housing.
Figure 2 shows the view of the IPR 513-3M (without the protective flip cover):
1: Hole to insert the housing key to reinstate the activated call point;
2: Holes to insert the housing key to release the front part of the call point housing;
3: The housing key to reset activated IPR 513-3M / to open its housing;
4: Place to apply an intact control seal.
4
+ - + -
3
–
+
+ - + -
2
1
Figure 2
2
2.3 Testing
2.3.1. For the period of testing, please disconnect executive outputs of CIE and appliances that control the fixed fire
suppression system. Notify the proper authorities that the system is undergoing maintenance.
2.3.2. By means of the network controller arm the CIE input the manual call point is connected to.
2.3.3. Activate the manual call point by pressing the operating element. The IPR 513-3M shall enter the Fire2 Alarm
condition: observe LED’s showing solid light and network controller’s displaying the Fire2 Alarm message from the input the call
point is connected to.
2.3.4. Reposition the operating element to the quiescent mode by inserting the housing key. Ensure the call point LED starts
flashing once per 4 s. Then, with the help of the network controller issue a comand to reset the alarm on the CIE input the call point
is connected to. If no Fire2 Alarm message is registered by the network controller or the call point’s LED operates in a way which
differs from the one stated in this manual, the manual call point is unhealthy and should be replaced.
2.3.5. Perform steps 2.3.2 – 2.3.4 at least triply.
2.3.6. When testing is completed, make sure that the manual call point is ready for normal operation. Reconnect control and
indicating equipment and control appliances with fixed fire suppression equipment and notify the proper authorities that the system
is back in normal operation.
Test the operability of the manual call point at least once per three months.
All the equipment used in testing must be known functioning!
3MAINTENANCE
The manual call point shall be maintained throughout a year by specialists whose electrical safety level is not lower than 3
rd
and as
per the schedule presented below.
Quarter I
Quarter II
Quarter III
Quarter IV
Checking conditions of the call point housing, ensuring that the manual call
point is fastened properly and its connecting wires and contact joints are in
good conditions

Removing dust, debris, and corrosion from the contact joints and housing

Testing operability of the manual call point in line with instructions of
Section 2.3 of this manual




4MANUFACTURER’S WARRANTY
4.1. The expected lifetime of the IPR 513-3M is 10 years.
4.2. The warranty period is 18 months since putting the product into operation but no more than 24 months from the
manufacturer’s date of production.
4.3. In case of any issue related to setting or operation of the product, please contact the technical support: +7 (495) 775-71-55
or e-mail support@bolid.ru.
4.4. For warranty return of the product, a reclamation report describing the failure shall be applied to it.
Claims shall be submitted to the following address:
NVP BOLID, #4 Pionerskaya Str., Korolyov, Moscow Region, 141070, Russia
Tel./fax: +7 (495) 775-71-55 (PBX), 777-40-20, 516-93-72.
E-mail: [email protected]u,Technical Support: support@bolid.ru, https://bolid.ru.
5CERTIFICATION INFORMATION
5.1 IPR 513-3M meets the requirements of “Technical Regulations on Fire Safety Requirements” (Federal Law No.123-FZ of
July 22, 2008) and is covered by Conformity Certificate No. C-RU.ЧС13.В.00845.
5.2 IPR 513-3M meets the requirements of Technical Regulations of Custom Union TR CU 020/2011 “Electromagnetic
Compatibility of Technical Equipment” and is covered by Conformity Declaration ЕАЭС №RU Д-RU.НР15.В.06593/20.
5.3 IPR 513-3M meets the requirements of Technical Regulations TR EAEU 037/2016 “On the restriction of the use of
hazardous substances in electronic and radio electronic equipment” and is covered by Conformity Declaration ЕАЭС №RU Д-
RU.РА01.В.82301/19.
5.4 The production of IPR 513-3M is awarded with Conformity Certificate GOST R ISO 9001. The Certificate is available on
the website https://bolid.ru in the section ABOUT.
6ACCEPTANCE AND PACKAGING CERTIFICATE
IPR 513-3M resettable manual call points (serial numbers are located on labels inside their housings) are accepted in line with
mandatory requirements of national standards and applicable technical documentation, approved as ready for use, and packaged by
the Bolid Company.
Responsible for acceptance and packaging
QCD ________________________________ ________________________
Name Date/Month/Year