1.0 Description
The DS7432 is an Eight Input Remote Module that provides a
means of addressing up to eight input loops of conventional
contacts to the multiplex bus of the control.
2.0 Specifications
• Control Panel Requirements: The DS7432 is designed
to work with the following control panels:
• A DS7400, DS7400X, DS7400Xi, DS7400Xi Rev. 3 or
DS7400Xi Rev. 4.
• Up to 7 DS7432s can be used per DS7400 system.
• Up to 15 DS7432 modules are allowed on DS7400X,
Xi and Xi Rev. 3.
• The DS7400Xi Rev. 4 control panel can support up to
30 DS7432 modules.
• One DS7430, DS7436 or DS9431 Multiplex Expansion
Module is required in the system to use the DS7432
Remote Module.
• Current Draw: 10 mA Standby, 10 mA Alarm
•Minimum Bus Voltage For Operation: 8 VDC peak
• Wiring: Refer to the reference guide for the panel’s
multiplex expansion module for multiplex wiring
requirements. The length of the wire connected to the loop
inputs on the DS7432 must be less than 250 ft. (76 m) per
loop.
• The recommended wiring to the control is standard #18
(1.22 mm) or #22 (0.74 mm) AWG, quad (4-wire) cable.
Do not use shielded or twisted pair cable.
• For fire applications, #18 AWG (1.2 mm) wire is
required.
3.0 Installation
P3 of the DS7432 is for European application
only. Do not put a jumper here.
P2 of the DS7432 allows the tamper switch to be bypassed
with a jumper when testing or servicing.
Remove jumper P2 when testing or servicing
has been completed.
Use the mounting holes (upper left and lower right corners) to
mount. It can be mounted inside or outside of the control
enclosure.
Route wiring as necessary from the DS7430, DS7436 or
DS9431 in the control enclosure and from the remote devices
to the DS7432.
Connect wiring as shown in Figure 3.
If using separate powered detectors (other than
smoke detectors) with a DS7400 Series
Control/Communicator, the DS7432 can be
powered from the control panel auxiliary power
(terminals 7 and 8). The detector can be
connected to the DS7432 (see Figure 4). This
eliminates the need for home-run power wiring
from each detector to the control when the
DS7432 is mounted outside of the enclosure.
Be sure all wiring is unpowered before routing.
If the wiring is to enter through the rear of the enclosure, open
the DS7432's rear wire entrance. If the wiring is to run along
the surface of the enclosure, open the DS7432's surface wire
entrance. See Figure 2.
4.0 Programming
4.1 System Programming
Refer to the System Programming section in your panel’s
reference guide for Zone programming information.
4.1 DIP Switch Settings
The DIP switches select which zones will be activated by the
loop inputs. Set the DIP switches as shown in Table 1 (Page
2).
• No two DS7432s should be set the same.
• The DS7432 occupies eight zones when connected to the
control panel. The input loops of the DS7432 correspond
to the zones of the control as shown in Table 2.
Figure 1: DIP Switch Orientation
+ – + – 1 2 3 4 5 6 7 8
POWER BUS
Locking tab
Surface Wire Entrance
Rear Wire Entrance
Tamper Switch DIP switch
P2
P3
Figure 2: DS7432 Front View Without Cover
All manuals and user guides at all-guides.com
DS7432 Installation manual © Bosch Security Systems B.V., 2020 Page 2
DIP Switches
Zones 12345
9-16 Off Off Off Off On
17-24 Off Off Off On Off
25-32 Off Off Off On On
33-40 Off Off On Off Off
41-48 Off Off On Off On
49-56 Off Off On On Off
57-64 Off Off On On On
65-72 Off On Off Off Off
73-80 Off On Off Off On
81-88 Off On Off On Off
89-96 Off On Off On On
97-104 Off On On Off Off
105-112 Off On On Off On
113-120 Off On On On Off
121-128 Off On On On On
129-136 On Off Off Off Off
137-144 On Off Off Off On
145-152 On Off Off On Off
153-160 On Off Off On On
161-168 On Off On Off Off
169-176 On Off On Off On
177-184 On Off On On Off
185-192 On Off On On On
193-200 On On Off Off Off
201-208 On On Off Off On
209-216 On On Off On Off
217-224 On On Off On On
225-232 On On On Off Off
233-240 On On On Off On
241-248 On On On On Off
249-256 On On On On On
Table 1: DIP Switch Settings
Zone Number
DS7432 Input
Loop 12345678
Zones 9-16 910 11 12 13 14 15 16
Zones 17-24 17 18 19 20 21 22 23 24
Zones 25-32 25 26 27 28 29 30 31 32
Zones 33-40 33 34 35 36 37 38 39 40
Zones 41-48 41 42 43 44 45 46 47 48
Zones 49-56 49 50 51 52 53 54 55 56
Zones 57-64 57 58 59 60 61 62 63 64
Zones 65-72 65 66 67 68 69 70 71 72
Zones 73-80 73 74 75 76 77 78 79 80
Zones 81-88 81 82 83 84 85 86 87 88
Zones 89-96 89 90 91 92 93 94 95 96
Zones 97-104 97 98 99 100 101 102 103 104
Zones 105-112 105 106 107 108 109 110 111 112
Zones 113-120 113 114 115 116 117 118 119 120
Zones 121-128 121 122 123 124 125 126 127 128
Zones 129-136 129 130 131 132 133 134 135 136
Zones 137-144 137 138 139 140 141 142 143 144
Zones 145-152 145 146 147 148 149 150 151 152
Zones 153-160 153 154 155 156 157 158 159 160
Zones 161-168 161 162 163 164 165 166 167 168
Zones 169-176 169 170 171 172 173 174 175 176
Zones 177-184 177 178 179 180 181 182 183 184
Zones 185-192 185 186 187 188 189 190 191 192
Zones 193-200 193 194 195 196 197 198 199 200
Zones 201-208 201 202 203 204 205 206 207 208
Zones 209-216 209 210 211 212 213 214 215 216
Zones 217-224 217 218 219 220 221 222 223 224
Zones 225-232 225 226 227 228 229 230 231 232
Zones 233-240 233 234 235 236 237 238 239 240
Zones 241-248 241 242 243 244 245 246 247 248
Zones 249-256 249 250 251 252 253 254 255 256
Table 2: Loop/Zone Number Relationship
Points 249-256 are not available for DS9400
use.
All manuals and user guides at all-guides.com
DS7432 Installation manual © Bosch Security Systems B.V., 2020 Page 3
+ – + – 1 2 3 4 5 6 7 8
NO
NC NC
NO NO
NC NC
NO NO
NC NC
NO NO
NC NC
NO
POWER BUS
47KΩ47KΩ47KΩ47KΩ47KΩ47KΩ47KΩ47KΩ
To control panel 12VDC power terminals:
DS7400, terminals 7 and 8, Fig. 4
DS9400, terminals RA and BA, Fig. 5
To DS7430, DS7436 or DS9431 MUX
BUS Terminals (see Figure 4 or 5)
Input Loops
To separate powered detectors (other than smoke detectors)
+
-
+
-
Burg. EOL resistor: DS P/N: 26069 (included)
Fire EOL resistor: DS P/N: 28010 (sold separately)
When used with a DS9431 , power is
connected to the option bus power terminals
(RA or RB = +, BA or BB = -). Connection to
other (24V) sources will damage the DS7432.
For UL Listed fire installations, Normally
Open (N/O) contacts must be used.
Initiating circuits are Class B
Figure 3: Wiring the DS7432 with Separate Powered Detectors
Auxiliary
Power -
Smoke
Detector
Smoke
Detector
EOL
Relay
EOL
Resistor
P/N: 28010
DS7400Xi Control/Communicator PCB
DS7430 MUX
Expansion Module
Power
DS7432 8-Input Remote Module
+ – 2 3 4 5 6 7 8
Smoke Power -
Smoke Power +
Example: DS250 in an
MB4W base.
Example: EOL200
Bus +
Either BusAor BusB, or both, may be used
for MUX connections when using the
DS7436 MUX Expansion Module. See the
panel’s reference guide for information.
Smoke
Power -
Auxiliary
Power +
Smoke Power -
BUS 1+ –
POWER
Bus
NFPA 72 does not allow redundant/duplicate
ground paths, do not connect wiring to the
BUS (-) terminal on this module for fire
applications. Only the BUS (+) needs to be
connected.
PO2 If Programmed
or
Any LP+ Terminal
Figure 4: 4-Wire Smoke Detector Wiring for the DS7432 and DS7400Xi Control/Communicator.
All manuals and user guides at all-guides.com
© Bosch Security Systems B.V., 2020 2020.05
Torenallee 49 5617 BA, Eindhoven, Netherlands DS7432 Installation manual
P/N: F01U262013-02 Page 4
21 3
4 5 6
7 8 9
#
Cmnd
0
Prog
*
Clear
Disable
Drill
Test
History
Reset
Silence
Trouble
Silenced
Power
Alarm
+ – 2 3 4 5 6 7 8
POWER
12V Power (-)
12V Power (+)
EOL
Resistor
P/N: 28010
Smoke
Detector
Smoke
Detector
EOL
Relay
Bus (+)
Power + may be connected to RA or RB
on the FACP Option Bus terminal strip.
Power - may be connected to BA or BB on
the FACP Option Bus.
Bus + and Bus - are connected to
MUX A terminals for addresses 9 -
128. MUX B terminals are for
addresses 129 - 255.
Example:
DS250 in a MB4W base
Example: EOL200
DS9400 FACP
DS9431Multiplex Expansion Module
I/O Module for the
DS9431 Multiplex
Expansion Module
DS7432 Eight Input Remote Module
1-
L+
2-
3-
L+
4-
AUX-
AUX+
24V Smoke Power (-)
24V Smoke Power (+)
+ –
BUS
1
SMK-
SMK+
NFPA 72 does not allow redundant/duplicate
ground paths, do not connect wiring to the
BUS (-) terminal on this module for fire
applications. Only the BUS (+) needs to be
connected.
Figure 5: 4-Wire Smoke Detector Wiring for the DS7432 and DS9400 Series FACP
For UL Listed fire installations, Normally Open (N/O) contacts must be used.
All manuals and user guides at all-guides.com

Other Bosch I/O System manuals

Bosch FLM-420-I2-W User manual

Bosch

Bosch FLM-420-I2-W User manual

Bosch Rexroth IndraControl S20 User manual

Bosch

Bosch Rexroth IndraControl S20 User manual

Bosch FLM-420-O1I1-E User manual

Bosch

Bosch FLM-420-O1I1-E User manual

Bosch Rexroth IndraControl S67 Series User manual

Bosch

Bosch Rexroth IndraControl S67 Series User manual

Bosch segmil D7044M User manual

Bosch

Bosch segmil D7044M User manual

Bosch Rexroth IndraControl S67 Series User guide

Bosch

Bosch Rexroth IndraControl S67 Series User guide

Bosch DS9432B User manual

Bosch

Bosch DS9432B User manual

Bosch FLM-420-I2-D User manual

Bosch

Bosch FLM-420-I2-D User manual

Bosch Rexroth Inline Series Instruction Manual

Bosch

Bosch Rexroth Inline Series Instruction Manual

Bosch B208 User manual

Bosch

Bosch B208 User manual

Bosch B308 User manual

Bosch

Bosch B308 User manual

Bosch B208 User manual

Bosch

Bosch B208 User manual

Bosch FLM-420-I2-E User manual

Bosch

Bosch FLM-420-I2-E User manual

Bosch PC600 User manual

Bosch

Bosch PC600 User manual

Bosch Rexroth IndraControl S20 User guide

Bosch

Bosch Rexroth IndraControl S20 User guide

Bosch D7044 User manual

Bosch

Bosch D7044 User manual

Bosch B308 User manual

Bosch

Bosch B308 User manual

Popular I/O System manuals by other brands

United Electronic Industries PowerDNA DIO-403 user manual

United Electronic Industries

United Electronic Industries PowerDNA DIO-403 user manual

VTI Instruments EMX-75 Series user manual

VTI Instruments

VTI Instruments EMX-75 Series user manual

WAGO I/O SYSTEM 750 manual

WAGO

WAGO I/O SYSTEM 750 manual

Assa Abloy OneSystem IO-Modul N5950 Installation and mounting instructions

Assa Abloy

Assa Abloy OneSystem IO-Modul N5950 Installation and mounting instructions

Wavecom GR64 Application note

Wavecom

Wavecom GR64 Application note

Titan SER-4485-SI-M user manual

Titan

Titan SER-4485-SI-M user manual

Argus Security TAURUS TW-MI-S-01 quick start guide

Argus Security

Argus Security TAURUS TW-MI-S-01 quick start guide

B&R Industries X20 System user manual

B&R Industries

B&R Industries X20 System user manual

WAGO 750-344 manual

WAGO

WAGO 750-344 manual

jablotron JB-110N user manual

jablotron

jablotron JB-110N user manual

Advanced Mxp-537 manual

Advanced

Advanced Mxp-537 manual

Burkert ME24 quick start

Burkert

Burkert ME24 quick start

ADLINK Technology DAQe Series user manual

ADLINK Technology

ADLINK Technology DAQe Series user manual

Rockwell Automation Allen-Bradley 1769-ASCII user manual

Rockwell Automation

Rockwell Automation Allen-Bradley 1769-ASCII user manual

Winbond SpiFlash W25Q256FV manual

Winbond

Winbond SpiFlash W25Q256FV manual

Contec DIO-48D2-PCI user guide

Contec

Contec DIO-48D2-PCI user guide

turck TBEN-LL Series Instructions for use

turck

turck TBEN-LL Series Instructions for use

WAGO I/O System 750 XTR 750-495/040-010 manual

WAGO

WAGO I/O System 750 XTR 750-495/040-010 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.