BR RABC Series User manual

www.bevent-rasch.com
Bevent Rasch
- Fire -
RABC
05/01/2018
Circular fire damper RABC
• Fire resistance class E60/E120S
• Sizes from 100 mm to 630 mm
• Prefitted safety actuator 24V or 230V
• Installation in ducts
• Available in MagiCAD
• CE-marked building product according to
15650:2010

2BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper RABC E60 / E120
Installation
RABC is installed in horizontal or vertical ducts that pass
through fire cell separating building elements, according to
the adjoining installation instructions.
Actuator
RABC is always supplied with an electric safety actua-
tor with spring return complete with thermal sensor with
pushbutton for local manual operating test. The sensor
disconnects the power to the actuator if the temperature
exceeds 72°C inside or outside the damper. 24V actuators
are always used in connection with the MRB monitoring
system. Dampers can also be supplied with electric actua-
tor 230V.
Note that the RABC damper is always supplied with an
actuator.
Activation
According to Boverket’s Building Regulations smoke de-
tectors must be verified according to SS-EN 54-7 to acti-
vate dampers. The mandatory thermal sensor closes the
damper at 72 °C according to ISO 10294-4.
Control and monitoring
When the damper is used to prevent the spread of fire and
combustion gases it must be closed via impulses from the
smoke detector. This must be fitted in the ventilation duct
in the proximity of the damper or in another suitable loca-
tion. Smoke detectors are monitored by means of Rasch’s
MRB system or the like. The MRB monitoring system also
performs automatic operating checks on the damper every
48 hours and is designed so that faults are indicated im-
mediately and the damper closes.
See www.bevent-rasch.se for further details.
Quick facts
• Fire resistance class E60/E120S
• Sizes from 100 mm to 630 mm
• Prefitted safety actuator 24V or 230V
• Installation in ducts
• Available in MagiCAD
• CE-marked building product according to 15650:2010
Use
Damper in combination with walls or joist systems for
fire separation of heating, ventilation and air conditioning
installations in buildings. In accordance with the harmo-
nised European standard EN 15650:2010. In designs ac-
cording to associated documents, installation instructions
and when the damper is used in combination with smoke
detectors and monitoring system (MRB), or the like, the
spread of combustion gases is prevented. No further ac-
tion against the spread of combustion gases is required.
Performance
EC certificate according
to EN 15650:2010
402-CPD-SC0058-13
Classification of fire resistance
according to EN 13501-3
E120 (ve i <–> o) S*)
E120 (ve ho i <–> o)*)
E60 (ve ho i <–> o)
For complete classification,
see the Declaration of Performance.
*)Fire class E120 shall be specified when ordering.

3BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper RABCE60 / E120
Size Ø100-630 mm
Design
RABC is supplied complete with factory mounted, mainte-
nance-free, 24V electric safety actuator with thermal sen-
sor featuring built-in signal contacts to indicate the damper
position. Spiral duct connections.
Material and surface finish
Casing and components of aluzink AZ185 according to
environmental class C4 in sizes 100 mm-315 mm. Casing
and components of galvanized steel sheet according to
environmental class C3 in sizes 400 mm-630 mm. Fabric
seals. EPDM spiral duct connections.
Accessories
RCKB Connection box
RCDU MRB system, max 2 dampers
RCBK4 MRB system, max 4 dampers
RCMU8 MRB system, max 8 dampers
RCKD/-RD Smoke detectors
RCTU/RCTC MRB3 system, max 236 dampers
Example:
Fire damper RABC - 400 - 1 - 1
Size, nom. diameter ØD mm
Material
Galvanized sheet steel = 1
Stainless AISI 3041 – EN 1.4301 = 2
Stainless AISI 316L – EN 1.4404 = 3
Actuator
Electric 24V with thermal sensor = 1
Electric 230V with thermal sensor = 3
Electric 24V incl. RCTU = 5
Note. Factory fitted actuator always included.
Specification

4BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper RABC E60 / E120
Dimensions and weight
Actuator - damper sizes
Actuator BFL-T is supplied to damper sizes Ø100-315 mm.
Actuator BF-T is supplied to damper sizes Ø400-630 mm.
Electrical data (values in brackets refer to 230V)
Actuator type BF... BFL...
Sizing, max ...................... 10 VA (12.5 VA) 4 VA (6,5 VA)
Running time:
– motor opening, max ..... approx. 120 s 60 s
- spring return, max ........ approx. 20 s 20 s (-10 to +55°C)
60 s (-30 to -10°C)
Protection class .............. IP 54
Power supply .................. 24V~ ±20%, 50/60Hz
24V= ±10%
(220-240V~ , 50/60Hz)
Ambient temperature ....... -30° to +50°C
Safety temperature .......... -30° to +75°C
(24 hrs. guaranteed safety)
Trigger temperature thermal sensor .................
72°C
End position contacts
- load ≤ 300 mW ..... min 1 mA/5V=, max 100 mA/250V~
After exceeding the above values it applies:
- load > 300 mW ..... min 100 mA, max 3 A/250~
Sound level when opening approx 45 dB(A)
Sound level when closing approx 62 dB(A)
Chart indicates in
the de-energized
state
Tf1 Tf2 BAE72-S
Actuator
C
O
N
L1
M
1
2
1
2
3
4
5
6
5°
80°
Thermal
sensor
Actuator
d = Swedish Standard SS 2609 (spiral connection)
Size
Ø mm
Spiral
C
Weight,
kg
A B
100 120 200 – 2.8
125 120 200 – 3
160 120 200 – 3.2
200 120 200 – 3.5
250 120 200 30 4
315 120 200 60 4.9
400 210 290 60 8.4
500 210 290 110 10.3
630 210 290 180 13.4
Connection to RCTU
Smoke detector
Actuator
Actuator
Actuator
Smoke detector
Actuator
Actuator
Actuator
BFL24, BF24
Wiring diagram RABC
Ød
max 55
max 200
BC
A
max
65 50

5BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper RABCE60 / E120
Size chart
Sound effect level
LWt , dB
Air flow, l/s
5
4
3
2
1
10
30
20
40
50
100
200
Total pressure drop, Pa
10 20 30 40 50 100 200 300 500 1000 2000 3000 10.000
125 160 200 250 315Size 100 400
630
500
40 dB
45 dB
50 dB
55 dB
60 dB
Correction of sound power level, LWok, in octave band
Lwok = Lw+ Kok
Sound data
Correction, Kok
Size
Ø mm
Centre frequency Hz
63 125 250 500 1000 2000 4000 8000
100 -3 -7 -12 -19 -29 -27 -33 -32
125 -4 -5 -8 -13 -21 -25 -31 -35
160 -3 -4 -7 -13 -18 -22 -29 -37
200 -2 -8 -14 -20 -24 -28 -35 -41
250 -2 -9 -14 -19 -19 -28 -35 -42
315 -3 -8 -12 -12 -18 -24 -31 -35
400 -5 -7 -11 -6 -15 -22 -27 -28
500 -2 -10 -15 -13 -18 -24 -22 -31
630 0 -17 -3 -5 -10 -15 -22 -30
Tol. ± dB 2 4 5 7 10 10 9 7

6BORÅS Tel +46 (0)33 - 23 67 80 STOCKHOLM Tel +46 (0)8 - 54 55 12 70
Fire damper RABC E60 / E120
13-0183_ENG / Jan. 2018 teamfront.se
Options 1 and 2
1. Secure the damper in the duct and seal with fire
stopping sealant, e.g. Intumex AN.
2. Install the duct system according to applicable require-
ments. Between the damper and the penetrated build-
ing element the maximum spacing between hangers
is 1500 mm. Use M10 drop rods and cradles or
equivalent.
3. Install the thermal sensor with the sensor body in the
air stream without obstructing the movement of the
damper blade.
EC certificate SC0058-13
Option 1
Damper’s fire resistance class:
E60
(ve ho i <–> o)
E120
(ve ho i <–> o)
E120
(ve i <–> o) S
Option 2
Damper’s fire resistance class:
E60
(ve ho i <–> o)
E120
(ve ho i <–> o)
Installation instruction
Seal with fire
stopping sealant,
e.g. Intumex AN
Suspension as
set out in point 2
RABC/RABCR/RABC-VAP
Repair using
an approved
method that
meets the fire
class e.g.
caulking and/or
fire stopping
sealant. Repair using
an approved
method that
meets the fire
class e.g.
caulking and/or
fire stopping
sealant.
Suspension as
set out in point 2
Seal with fire
stopping sealant,
e.g. Intumex AN
RABC/
RABCR/
RABC-VAP
• Minimum distance between dampers must be 100 mm.
• Minimum distance to joist structure/wall must be 75 mm.
• No openings between dampers and fire separating
building elements.
• Optional installation of the damper spindle.
This manual suits for next models
1
Table of contents
Popular Fire Alarm manuals by other brands

Potter
Potter PFC-6075RB Installation, operation, & programming manual

Microm
Microm MPS-800 Series quick start guide

Klaxon
Klaxon Klaxalarm Terrier 18-980181 installation instructions

Teletek electronics
Teletek electronics SensoMAG B12L/U installation manual

Brooks
Brooks RFS1 V2 Operation & installation manual

Secutron
Secutron MRM-800 Series quick start guide