Global Fire Equipment ZEOS-AD-S User manual

ZEOS-AD
ANALOGUE ALGORITHMIC
ADDRESSABLE FIRE DETECTOR
MANUAL 210729
MADE IN PORTUGAL - EU
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560
Email: info@globalfire-equipment.com | Technical Support: techs@globalfire-equipment.com | www.globalfire-equipment.com
TECHNICAL SPECIFICATIONS
SUPPLY VOLTAGE
Loop Powered - 17V to 30V DC
CURRENT - QUIESCENT / SURGE
450uA max.
CURRENT - DEVICE IN ALARM
4 mA - Alarm LED illuminated
SENSITIVITY / CABLE SIZE
According to EN54-5 and EN54-7 / 0.5-2.5 mm²
RESET/START-UP TIMES
20 seconds max.
COLOUR / CASE MATERIAL / MAX. HUMIDITY
White / ABS / 95% RH Non-Condensing
NORMAL / TRANSIENT OPER. TEMPERATURE
0°C to 50°C / -10°C to 85°C
DIMENSIONS / WEIGHT
100 (D) x 50 (H) mm included base / 92g without base & 144g inc. base
For EN54-13 compliance, please check the control panel manual specifications.
ORDER CODE
DESCRIPTION
CERTIFICATE
ZEOS-AD-S
ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR
1328-CPR-0521
ZEOS-AD-H
ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR
1328-CPR-0520
ZEOS-AD-SH
ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR
1328-CPR-0519
ZEOS-AD-SI
ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH ISOLATOR
1328-CPR-0607
ZEOS-AD-HI
ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR WITH ISOLATOR
1328-CPR-0610
ZEOS-AD-SHI
ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR WITH ISOLATOR
1328-CPR-0492
INSTALLATION
INSTALLING THE BASE - To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against terminals and
fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard electrical junction boxes.
INSTALLING THE HEAD - Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on base. Fit the
detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and activate the detection loop. Test the detectors as
described below.
TESTING - All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at the conclusion of testing.
SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When sufficient smoke has entered, the detector will
signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make sure to clear smoke out of the chamber before resetting in order to keep the detector at
its current sensitivity setting.
HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can be met by some domestic hair dryers.
Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several cms, direct the airflow at the guard protecting the thermistor. The
detector should alarm within 60 seconds. Upon alarm immediately remove the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to
activate within 60 seconds, confirm connections and programming.If necessary, replace the unit.
NOTE: After testing, check that the system is returned to normal operation.Notify the appropriate authorities that the testing procedure has been completed and the system is
active again.
MAINTENANCE - The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low power
vacuum cleaner.
DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR.
DETECTOR BASE - LOOP CONNECTIONS
NOTE:
Positive terminal
of remote indicator
should be connected
to terminal 4
(+ Loop IN/OUT).
MECHANICAL SPECIFICATION
BASE LOCK
To unlock detector from its base
push provided unlock key
through hole available on the
base side wall as shown.
D.I.L. SWITCHES CONFIGURATION
Switches 1-7
Used to configure the module’s address.
Switch 8
Not used.
Address Switches binary weights
1 ON =1 4 ON =8 7 ON =64
2 ON =2 5 ON =16
3 ON =4 6 ON =32
ADDRESS PROGRAMMING
MORE INFO >> GLOBALFIRE-EQUIPMENT.COM

This manual suits for next models

5

Other Global Fire Equipment Fire Alarm manuals

Global Fire Equipment MPX-SNDR-DG - 4 V2 User manual

Global Fire Equipment

Global Fire Equipment MPX-SNDR-DG - 4 V2 User manual

Global Fire Equipment ZEOS-C User manual

Global Fire Equipment

Global Fire Equipment ZEOS-C User manual

Global Fire Equipment VALKYRIE AS User manual

Global Fire Equipment

Global Fire Equipment VALKYRIE AS User manual

Global Fire Equipment JUNIOR V3 Manual

Global Fire Equipment

Global Fire Equipment JUNIOR V3 Manual

Global Fire Equipment ZEOS C User manual

Global Fire Equipment

Global Fire Equipment ZEOS C User manual

Global Fire Equipment ORION Instruction manual

Global Fire Equipment

Global Fire Equipment ORION Instruction manual

Global Fire Equipment ORION EX MINI-REP User manual

Global Fire Equipment

Global Fire Equipment ORION EX MINI-REP User manual

Popular Fire Alarm manuals by other brands

Summit SFC-102 Series installation instructions

Summit

Summit SFC-102 Series installation instructions

Nittan NHD-G series instruction manual

Nittan

Nittan NHD-G series instruction manual

Notifier RP-1001 installation manual

Notifier

Notifier RP-1001 installation manual

Honeywell C7015A product manual

Honeywell

Honeywell C7015A product manual

MORLEY-IAS FW9003 Range installation manual

MORLEY-IAS

MORLEY-IAS FW9003 Range installation manual

usi UNIVERSAL 5304CN instructions

usi

usi UNIVERSAL 5304CN instructions

Siemens SFPO-11 Installation instructions manual

Siemens

Siemens SFPO-11 Installation instructions manual

UniPOS IFS7002 instruction manual

UniPOS

UniPOS IFS7002 instruction manual

EMS FIRECELL Programming manual

EMS

EMS FIRECELL Programming manual

Electro Detectors Zerio Plus EDA-C5000 installation manual

Electro Detectors

Electro Detectors Zerio Plus EDA-C5000 installation manual

Vigilant FP0539 Operating & installation instructions

Vigilant

Vigilant FP0539 Operating & installation instructions

Simplex SafeLINC 4020 Installation and Configuration Procedures

Simplex

Simplex SafeLINC 4020 Installation and Configuration Procedures

Isimet FLA Series Installation, Operations, Start-up and Maintenance Instructions

Isimet

Isimet FLA Series Installation, Operations, Start-up and Maintenance Instructions

Bosch D1256 installation instructions

Bosch

Bosch D1256 installation instructions

ELRO RM335 user manual

ELRO

ELRO RM335 user manual

Teknim TFS-3191 Installation & operating guide

Teknim

Teknim TFS-3191 Installation & operating guide

White Rodgers 3098-134 installation instructions

White Rodgers

White Rodgers 3098-134 installation instructions

Siemens Synova FC330A operating manual

Siemens

Siemens Synova FC330A operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.