Bra Proxinet 36-76-192 User manual

INSTALLATION MANUAL
SECURITY ALARM CONTROL UNIT
36-76-192
English
EN
English
EN

p. 2- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
Index
1 SYMBOLS AND GLOSSARY .................................................................................PAG. 4
2 TERMS OF USE ............................................................................................PAG. 4
3 IMPORTANT FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAG. 4
2.1 INTENDED USE .....................................................................................................4
2.2 WARRANTY AND LIMITS TO LIABILITY ...............................................................................4
4 SYSTEM INSTALLATION....................................................................................PAG. 5
4.1 SYSTEM WIRING ....................................................................................................5
4.2 WIRING BUS RS-485.................................................................................................6
TRADITIONAL CABLING (enter - output) ...................................................................................................... 6
BRANCHED-OUT CABLING................................................................................................................... 6
DOUBLE-BRANCH CABLING ................................................................................................................. 7
BUS AMPLIFIER CABLING .................................................................................................................... 8
APPLICATIVE NOTES ON CABLING OF THE RS-485 BUS ........................................................................................ 9
CHOOSING THE CABLE SECTION FOR THE RS-485 BUS......................................................................................... 9
4.3 WIRING THE INPUTS ...............................................................................................11
5 INSTALLING THE CONTROL UNIT ...........................................................................PAG. 12
5.1 FEATURES .........................................................................................................12
5.2 COMPONENTS OF THE CONTROL UNIT..............................................................................13
5.3 CARD DESCRIPTION ...............................................................................................13
5.4 WALL MOUNTING..................................................................................................15
5.5 CABLING ..........................................................................................................15
230 Vac....................................................................................................................................15
BATTERY ..................................................................................................................................16
TAMPER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
BUS RS-485................................................................................................................................17
INPUTS....................................................................................................................................17
U1 PROGRAMMABLE OUTPUT (positive) ....................................................................................................17
U2, U3, U4 (Open Collector) PROGRAMMABLE OUTPUTS .....................................................................................17
GENERAL ALARM RELAY OUTPUTS RELAY 1 - RELAY 2 ........................................................................................18
PSTN TELEPHONE LINE .....................................................................................................................18
LANGUAGE UPDATE BOARD PXLNG for control unit..........................................................................................18
6 PXKWD KEYPAD ..........................................................................................PAG. 19
6.1 FEATURES .........................................................................................................19
6.2 CARD DESCRIPTION ...............................................................................................19
6.3 USER INTERFACE ..................................................................................................20
KEYPAD DISPLAY ..........................................................................................................................20
LIGHT WARNINGS ..........................................................................................................................20
ALPHANUMERIC KEYPAD...................................................................................................................21
6.4 KEYPAD MENU ....................................................................................................21
7 PXITXXXX INSERTERS .....................................................................................PAG. 22
7.1 FEATURES .........................................................................................................22
7.2 CARD DESCRIPTION ...............................................................................................22
7.3 USER INTERFACE ..................................................................................................22
LIGHT WARNINGS ..........................................................................................................................23
7.4 AIMING ...........................................................................................................23
7.5 KEYT KEY..........................................................................................................23
ACCEPTANCE ..............................................................................................................................23
CHECK KEY ................................................................................................................................23
8 EXPANSION MODULES ....................................................................................PAG. 24
8.1 PX8I (EXPANSION OF 8 INPUTS IN CONTROL UNIT) ..................................................................24
FEATURES .................................................................................................................................24
CARD DESCRIPTION........................................................................................................................24
INSTALLING ...............................................................................................................................24
8.2 PX8IR (8-INPUT EXPANSION ON BUS) ...............................................................................24
FEATURES .................................................................................................................................24
CARD DESCRIPTION........................................................................................................................25
ADDRESSING ..............................................................................................................................25
8.3 PX80R (8-INPUT EXPANSION).......................................................................................25
FEATURES .................................................................................................................................25
CARD DESCRIPTION........................................................................................................................26
ADDRESSING ..............................................................................................................................26
8.4 PXWRX (RADIO RECEIVER MODULE) ................................................................................26
FEATURES .................................................................................................................................26
DESCRIPTION OF BOARD ...................................................................................................................27
ADDRESSING ..............................................................................................................................27
9 ACCESSORIES .............................................................................................PAG. 27
9.1 PXV64 - PXV256 ...................................................................................................27
INSTALLATION .............................................................................................................................28

p. 3- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
9.2 IGSM ..............................................................................................................28
CARD DESCRIPTION........................................................................................................................28
INSTALLING ...............................................................................................................................28
10 STARTING UP THE SYSTEM ...............................................................................PAG. 28
10.1 FIRST START UP ..................................................................................................29
PRELIMINARY CHECKS .....................................................................................................................29
SYSTEM UNDERGOING MAINTENANCE / OPERATIONAL ......................................................................................29
CHANGE CONTROL UNIT LANGUAGE........................................................................................................29
CONTROL UNIT POWER ON .................................................................................................................29
OPENING/CLOSING THE CONTROL UNIT .....................................................................................................29
10.2 USING THE LCD KEYPAD ..........................................................................................30
ALPHANUMERIC KEYPAD...................................................................................................................30
ACCESSING THE TECHNICAL MENU..........................................................................................................30
SELECTING NUMBERS GREATER THAN 9 .....................................................................................................30
10.3 PROGRAMMING MODE (EASY, NORMAL, ADVANCED) ..............................................................30
EASY MODE ...............................................................................................................................31
NORMAL MODE............................................................................................................................31
ADVANCED MODE .........................................................................................................................32
10.4 AIMING AND ACQUIRING PERIFERALS.............................................................................32
ACQUIRING KEYPADS ......................................................................................................................32
ACQUIRING INSERTERS.....................................................................................................................33
ACQUIRING THE EXPANISION MODULE IN THE CONTROL UNIT................................................................................33
ACQUIRING INPUT EXPANSION MODULES ON BUS ...........................................................................................34
ACQUIRING OUTPUT EXPANSION MODULES ON BUS.........................................................................................35
ON BUS RADIO RECEIVER MODULE ACQUISITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.5 DEFINITION OF SYSTEM AREAS ...................................................................................37
10.6 PROGRAMMING SCENARIOS ......................................................................................38
CREATING SCENARIOS .....................................................................................................................38
ASSOCIATING SCENARIO VIA KEYPAD .......................................................................................................40
ASSOCIATING SCENARIOS AND INSERTERS ..................................................................................................41
10.7 PROGRAMMING INPUTS ..........................................................................................42
10.8 LEARNING RADIO INPUTS.........................................................................................43
10.9 PROGRAMMING OUTPUTS ........................................................................................43
10.10 PROGRAMMING TELEPHONE CALLS AND SMS TEXT MESSAGES (PSTN/GSM) .......................................44
PROGRAMMING THE PSTN - GSM PRIORITY .................................................................................................44
PROGRAMMING THE TELEPHONE NUMBERS.................................................................................................44
RECORD COMMON VOICE MESSAGE FROM PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
RECORD VOICE MESSAGES ASSOCIATED WITH INPUTS, AREAS, OUTPUTS AND SCENARIOS FROM PC ...........................................46
SEND VOICE MESSAGES ....................................................................................................................46
10.11 CREATING USER CODES..........................................................................................46
10.12 ACQUIRING KEYS................................................................................................47
10.14 SYSTEM TEST ...................................................................................................49
FROM KEYPAD .............................................................................................................................49
11 PC – CONTOL UNIT CONNECTION..........................................................................PAG. 50
11.1 LOCALLY PROGRAMMING THE RS-232 .............................................................................50
12 RESTORE SYSTEM ........................................................................................PAG. 51
12.1 RESTORING CODES AND KEYS.....................................................................................51
12.2 FACTORY SETTINGS ..............................................................................................52
13 DECLARATION ...........................................................................................PAG. 55

p. 4- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
2.1 Intended use
1 Symbols and glossary
This symbol means the parts which describe safety issues.
This symbol shows parts which must be read with care.
Permanently on warning light.
Warning light off.
Rapidly flashing warning light.
INSTALLER: any person or business responsible for designing and installing the system.
USER: any persons using the security alarm system.
●
●
2 Terms of use
The security alarm control unit of the PROXINET series (Proxinet 36, Proxinet 76, Proxinet 192) are designed to enhance security in
both homes and service-sector businesses.
Any installation and use other than that specified in this manual is forbidden.
2.2 Warranty and limits to liability
Our product warranty refers to restoring compliance to the products through repairs or free replacement of any materials found to
be non compliant due to defect resulting from errors in the manufacturing process, including any expenses incurred due to the any
replacement actions (job orders, shipping, etc...).
Sellers of BPT S.p.A. products are directly liable to consumers of said products, and have the function of upholding this right of
warranty in favour of said consumers. Consumers must address the seller, and only the seller, when upholding this right, and clearly
communicate any product flaws or shortcomings within two months of noticing.
The warranty loses validity is any user fails to communicate any flaws within the above mentioned terms. Any claim is no grounds
for customers to cancel or reduce orders, nor for reimbursements of sorts on our part. Our warranty is void if any of the parts as
flawed are tampered with or repaired.
BPT S.p.A. cannot be held liable in case of damage caused by improper use of its products. Given that it’s the installers that design
and install the intrusion alarm system using BPT S.p.A original parts and third-party parts, our company cannot therefore vouch for
the reliability of the security alarm system. BPT S.p.A. denies any liability for claims made by users, installers or any third parties
as concerns use and installation of our products.
3 Important for SAFETY
If properly designed, the security alarm system provides high levels of safety to the areas it is meant to protect and to the
consumers that use it. To ensure this, certain rules must be followed:
•The installation must be carried out by qualified, expert staff and in full compliance with applicable laws.
•Check main power source connections and relative ground connections.
•Once the system is up and running, make sure users have changed the Factory User Code (123456).
•Maintenance on the system must only be carried out by qualified personnel; do not try to tamper with the system, you risk
compromising its proper working order, and risk electrocution due to the voltage.

ON
1
12 V
13,8 Vdc
+ -
NTC
230 Vac
4,7 kohm
4,7 kohm
+ - TC TAMPER ALARM
X
4,7 kohm
150 ohm
150 ohm
+ –
+
O5O6O7O8 –B A
1 2 3 4
OFF
ON
O1O2O3O4
NC
C
NA
JP1
NC
C
NA
JP2
NC
C
NA
JP3
NC
C
NA
JP4
1+
+
+
–
––
Z3 Z4 Z5 Z6 Z7 Z8
Z2 Z1 B A
2 3 4
OFF
ON
p. 5- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
4 System installation
4.1 System wiring
Antenna GSM
RS-232 PC
Connection
PXV64-PXV256
PXGSM
PXLAN-PXWEB
PX8I
Telephone
PSTN Telephone
line
Tamper
Siren with on-
board power
supply.
Siren
Single balancing
input
NC input
Sensor with
double balanced
input
Single balancing
input
Power supply 230 Vac
Battery
Bus branching
PX8OR
PX8IR
Siren
Relay
Back up power-
supply unit
PXKWD

p. 6- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
4.2 Wiring bus RS-485
If remote devices are properly installed, all bus communication LEDs featured on each device should be flashing. If some
are not flashing, this means installation or programming was wrong (check cabling, AIMING and programming in control
unit).
TRADITIONAL CABLING (enter - output)
BRANCHED-OUT CABLING
Branching out consists of a cable with three pairs two of which are twisted (each pair is made up of conductors A and B).
An analysis of this circuit shows that the structure of the RS-485 bus continues to be linear (enter-output).

p. 7- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
DOUBLE-BRANCH CABLING

p. 8- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
BUS AMPLIFIER CABLING

p. 9- Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
APPLICATIVE NOTES ON CABLING OF THE RS-485 BUS
Cabling of the bus connecting the control unit to the remote modules, inserters, and keypads must follow the rules dictated by the RS-485.
Only use a screened and twisted cable with section of at least:
• 2x0.5 mm² for power supply and 2x0.22 mm² twisted for data.
• 2x0.5 mm² for power supply and 2x2x0.22 mm² twisted for data
(used to perform branching).
The sock must always be continuous and connected to the control unit’s
negative (-) terminal.
The maximum length of the cable (max stretches of 800 m) and the conductor
sections depend on the number of modules and from the overall draw on the
different stretches of bus. When power draw increases the voltage drop
increases on the cables and so reduces the power supply current to the
devices on bus.
The voltage at all + and - terminals of the devices on bus (keypads, inserters,
modules, ...) must not fall below 12 V DC.
If less, add an auxiliary power source and disconnect the positive while
keeping the negative mutual.
In case of long stretches of bus always install 150 ohm resistors among
terminals A and B at both ends of the bus.
Always carry out cabling of the bus in “enter and output” mode. Do not
cable the bus when in star configuration.
If you need this configuration follow the directions in this chapter.
Greater than 12 Vdc
YES
NO
CHOOSING THE CABLE SECTION FOR THE RS-485 BUS
For the RS-485 bus we suggest using the following cable:
• Twisted and grade 4-screened cable (600/1000 V).
• A twisted pair for data with section 2x0.22 mm².
• One pair to power the 2x0.5 mm2 or greater section depending on distances and voltages (check table below).
Below is the table for calculating the section of power cables with distance variances and power draws.
Any drops in power voltage must not exceed 1.4 V (voltage measured on terminals of the power source and those of the
devices with remotest bus).
MAXIMUM CABLE LENGTH BUS RS-485
POWER DRAW
SECTION
0,1 A 0,25 A 0,5 A 1 A
0,5 mm2175 m 70 m 35 m 17 m
0,75 mm2262 m 105 m 52 m 26 m
1 mm2350 m 140 m 70 m 35 m
1,5 mm2525 m 210 m 105 m 52 m
If a cable does not have the proper section additional auxiliary power sources must be added.

p. 10 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
Example:
Let’s say we have:
• Proxinet 36
• PXKWD (max consumption 60 mA)
• PX8IR (max consumption 40 mA)
• Sensors connected to the remote input expansion (total consumption 150 mA)
• Connection distance 200 m.
With max consumption of 250 mA in this case we either use a 1.5 mm2 section cable, or a 0.5 mm2 cable plus an auxiliary power
source at the end of the line as shown below:
CABLE RS-485
Screened 2x1,5mm² + 2x0,22mm² twisted
CABLE RS-485
Screened 2x0,5mm² + 2x0,22mm² twisted
Control unit Device on bus
Back-up
power-
supply
Control unit Device on bus
Maximum communication performance is guaranteed by using the specified cable (PXC75). Maximum communication
speed between peripherals is 115,200 baud. If not using the cable specified or if there are problems at installation, the
control unit transfer speed can be decreased (38,400, 9,600, 4,800 and 2,400 baud). The speed of the peripherals will
automatically set.

p. 11 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
CONNECTING INPUTS
4.3 Wiring the inputs
I bilanciamenti si effettuano con resistenze da 4,7 kohm.
Yellow 4
Violet 7
Red x100
Gold 5%
4.7 kohm 5% resistor
The U1 output gives a positive when output is active (ON =12, 8Vdc) The U1 output is factory-programmed as TC (active output
with system shut down, non active during the output time and when at least one are is turned on).
(NO) NORMALLY OPEN (NC) NORMALLY CLOSED
(SB) SINGLE BALANCING (DB) DOUBLE BALANCING
(CI) IMPULSE OR INERTIAL COUNTER (DB) DOUBLE BALANCING SENSOR
(DB) DOUBLE BALANCING SENSOR WITH MICROWAVE BLOCK WHEN CONTORL UNIT IS OFF (TC)

p. 12 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
5 Installing the control unit
5.1 Features
GENERAL CHARACTERISTICS Proxinet 36 Proxinet 76 Proxinet 192
Power supply voltage 230 Vac - 15% + 10% 50/60 Hz
Power source 1 A 1,5 A 2,5 A
Transformer 20 VA 38 VA 52 VA
Card power draw (excluding battery recharge) 70 mA 70 mA 71 mA
Battery 7,2 Ah 7,2 Ah or 15 Ah 15 Ah
Working temperature 0° - 40° C 0° - 40° 0° - 40°
Relative humidity 25% - 75% without condensation
Max safety rating 2 2 2
Environmental Class III
Dimensions (HxLxD) 380 x 260x 25 mm
IP IP30 IP30 IP30
Weight: (without battery) 2,70 Kg 4,50 Kg 5,95 Kg
Following are the technical features of the control units (optional component means one that can be purchased separately).
TECHNICAL SPECIFICATIONS Proxinet 36 Proxinet 76 Proxinet 192
Area 4 8 16
Scenarios 32 32 32
Total inputs 36 76 192
Wire inputs 20 36 128
Radio inputs 16 40 64
Inputs in control unit 12 12 16
Types of inputs in control unit NC, NA, SB, DB, CI NC, NA, SB, DB, CI NC, NA, SB, DB, CI
Types of inputs on BUS NC, NA, SB, DB, CI NC, NA, SB, DB, CI NC, NA, SB, DB, CI
On board relay outputs 1 2 3
Total programmable outputs 20 36 128
Programmable control unit outputs 4 4 8
Programmable bus outputs 16 32 120
Inputs expansion module in control unit 1 1 1
Inputs expansion modules on bus 1 3 14
Output expansion modules on bus 2 4 15
Radio concentration modules on bus 2 8 16
Inserters 4 8 16
Keypads 4 8 16
Transponder keys 20 (99 with PXV 256) 50 (999 with PXV 256) 50 (999 with PXV 256)
Installer’s codes 1 1 1
User code 20 (99 with PXV 256) 50 (999 with PXV 256) 50 (999 with PXV 256)
Radio commands 832 32
Timer Daily / Weekly Daily / Weekly Daily / Weekly
Events 200 (999 with PXV 256) 999 (9999 with PXV 256) 999 (9999 with PXV 256)
BUS 485 1 1 2
PSTN Combiner Yes Yes Yes
GSM Combiner Optional Optional Optional
Voice synthesis Optional Optional Optional
Telephone numbers 816 16
CONTACT-ID Yes Yes Yes
FW control unit reprogramming Yes Yes Yes
LAN Optional Optional Optional
Control by SMS Yes (with GSM) Yes (with GSM) Yes (with GSM)
Controlling by VOICE Yes (with PXV xxx) Yes (with PXV xxx) Yes (with PXV xxx)
Programming and Assistance Remote LAN Yes (with LAN) Yes (with LAN) Yes (with LAN)
Programming and Assistance Remote PSTN Yes Yes Yes
Programming and Assistance Remote GSM Yes (with GSM) Yes (with GSM) Yes (with GSM)
RTC + buffer battery No No Yes

p. 13 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
5.2 Components of the control unit
Proxinet 36 - Proxinet 76 - Proxinet 192
DESCRIPTION
1230 Vac grid connection terminals.
Careful! High Voltage.
2 Fastom / ground connector terminal.
3 Connector cable for grounding the cover.
4 47 kohm temperature gauge (optional) PXSTB
5Battery connection cables.
Respect the polarities (red = +, black = -).
6Central tamper.
7
Line fuse.
for Proxinet 36: no fuse, the transformer is fitted with a 130°- rated heat protector.
for Proxinet 76: no fuse, the transformer is fitted with a 130°- rated heat protector.
For Proxinet 192: glass fuse T 500 mA.
5.3 Card description
Proxinet 36 Proxinet 76 Proxinet 192
DESCRIPTION
1
Bus RS-485 for connecting keypads, remote modules and inserters.
[+,-] power supply to bus.
[A,B] data.
[F6] for Proxinet 36: NO fuse.
[F6] for Proxinet 76: self-restoring fuse 1,35 A.
[F6] for Proxinet 192: self-restoring fuse 1,35 A.

p. 14 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
2
Control unit input terminals, can be of the NA, NC, SB, DB, CI types.
[+,-] power supply.
[1,2,3,4] inputs 49..56. Negative reference.
[F3] for Proxinet 36: NO fuse.
[F3] for Proxinet 76: self-restoring fuse 1,35 A.
[F3] For Proxinet 192: self-restoring fuse 1,35 A.
3
Control unit output terminals.
[AUX +, -] power supply available via self-restoring-fuse protected output F5.
[U1] positive programmable output protected by 100 ohm resitor (ON=13.8 Vdc, OFF=NA).
[U2] for the Proxinet 192 it is a C-NA relay output, for the others it’s an open collector output which is
negative programmable and protected by a 100 ohm resitor (ON=0 Vdc, OFF=NA).
[U3, U4] open collector outputs which are negative programmable and protected by 100 ohm resistor (ON=0 Vdc, OFF=NA).
[NO, C, NC] clean-contacts general alarm relay (ony one for the Proxinet 36).
[F5] for Proxinet 36: NO fuse.
[F5] for Proxinet 76: self-restoring fuse 1,35 A.
[F5] for Proxinet 192: self-restoring fuse 1,35 A.
A short circuit with open collector output activated for an extended time may lead to breaking of the protecting
resitor.
4 / 5
[T, +] terminals for connecting the control unit tamper.
[JP3] bridge to activate / deactivate the tamper (position C deactivates the control unit tamper, and position O
activates it).
6
[PE] grounding terminal.
[L, L] input terminal for PSTN external telephone line.
[T, T] output terminals for PSTN telephone line outgoing to telephone or control unit.
7
[CN2] connector for GSM module.
[F4] for Proxinet 36: NO fuse.
[F4] for Proxinet 76: self-restoring fuse 1,35 A.
[F4] For Proxinet 192: self-restoring fuse 1,35 A.
8Dip switch 1 serves to switch the control unit from operational to maintenance mode (ON=Maintenance,
OFF= Operational).
Dip Switch 2 serves to restore the factory codes.
Dip Switch 3 is unused.
DipSwitch 4 serves to reprogram the control unit firmware.
9[P1] button to relaunch control unit (not required for restoring parameters; does not alter configuration).
10 [CN3] connector for the PXV64/PXV256 voice guide and language card.
11
[CN1] RS-232 socket for connecting to OC (via RS-23w straight male/female cable) or to Ethernet interface.
[F4] for Proxinet 36: NO fuse.
[F4] for Proxinet 76: self-restoring fuse 1,35 A.
[F4] For Proxinet 192: self-restoring fuse 1,35 A.
12 [JP2] bridge to power Ethernet interface linked up to the CN1 connector (activates the 12 Vdc on connector CN1
(RS-232) in pin 9). A position = enable 12 Vdc; B position = disables 12 Vdc.
13
[F1] for Proxinet 36: glass T fuse 3,15 A.
[F1] for Proxinet 76: glass T fuse 3,15 A.
[F1] For Proxinet 192: glass T fuse 3,5 A.
14 [Vac] terminals to connect to transformer.
15
[CN7] battery connector.
[F2] for Proxinet 36: self-restoring fuse 1,6 A.
[F2] for Proxinet 76: self-restoring fuse 2,5 A.
[F2] For Proxinet 192: self-restoring fuse 3 A.
16 / 17
If installed, the PXSTB is temperature probe that optimises battery recharges.
[PXSTB] connector for PXSTB probe.
[JP1] bridge to activate (PXSTB and bridge not present) or disable (no PXSTB nor bridge present) the PXSTB
probe.
18
[CN5] connector for input expansion in control unit.
[F3] for Proxinet 36: NO.
[F3] for Proxinet 76: self-restoring fuse 1,35 A.
[F3] For Proxinet 192: self-restoring fuse 1,35 A.
19 [+, U5, U6, U7, U8, -] CN6 connector for open collector outputs which are negative programmable and
protected by 100 ohm resitor ((ON=0 Vdc, OFF=NA).

p. 15 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
5.4 Wall mounting
Proxinet 36 - Proxinet 76 - Proxinet 192
Install the control unit far from access points and so it is hard to find.
Secure onto a suitable wall that can permanently hold up the control unit.
Set it up to have holes and channels for the initial installation cables to pass through.
Use the specific four holes for securing to the wall.
5.5 Cabling
Proxinet 36 Proxinet 76 Proxinet 192
– Cut off the magnetothermic switch linked to the control unit before the network 230 Vac and for the entire time the
control unit is open.
– Handling the 230 Vac main power supply cables is hazardous; risk of electrecution.
–Connect the ground via a Faston to the appposite connector (Proxinet 36, Proxinet 76), or to the PE terminal (Proxinet
192). Connecting the ground must be done in compliance with current regulations.
– Connect the Line cable and the Neutral of thr 230 Vac to the transformer terminals.
– Block the 230 Vac power supply cable in the container so that it cannot move even if the terminals are disconneted.
– Before closing the control unit check that all of the metal parts are connected to the ground (control unit and cover).
– Re-attach the magnetothermic switch associated with the control unit only once internal cabling of the control unit.
230 Vac
Set up a suitable bipolar cut-off device (magnetothermic switch), with distances greater than 3 mm between contacts, wit
sectioned power source.

p. 16 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
BATTERY
The battery works as secondary power source to the security alarm unit. To optimise recharging and duration over time, we suggest
installing the PXSTB, a temperature probe which allows to regulate the battery recharge depending on the temperature itself.
Installation of the PXSTB probe without opening jumper JP1 lowers battery charge voltage by 1 Volt thus impeding recharge.
Respect battery polarities while connecting.
PXSTB installed PXSTB not installed
The JP1 jumper needs to be open (unbridged).
Make contact between the PXSTB and battery.
The JP1 jumper needs to be closed (bridged).
TAMPER
CONTROL UNIT TAMPER IS ACTIVATED CONTROL UNIT TAMPER IS DEACTIVATED
ANTI-OPENING TAMPER ANTI-OPENING AND TEARING TAMPER
Tamper is activated (JP3 on O). Tamper is deactivated (JP3 on C).
Not using the unit tamper annuls the safety level of the system.

p. 17 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
1) Using a steel drill bit, perforate the right side of the control-
unit container so you can then secure the tamper horizontally
using the short screw.
2) Secure the tamper to the right side of the control unit using
the second short screw.
1) Using a proper drill bit, perforate the wall at the same height
as the tamper hole.
2) insert the apposite long screw into the hole on the right side
of the control unit, tighten the washer and secure with the
locking nut. The tamper must be able to rotate.
3) Ajust the height of the plug screw so that when closing the
cover the small tamper-lever can also close.
BUS RS-485
For cabling to the RS-485 bus see chapter 4.2.
INPUTS
To cable the inputs see chapter 4.3.
U1 PROGRAMMABLE OUTPUT (positive)
A short circuit to the GND with active output for an extended time may lead to breakage of the protective resistor.
U1 is freely-programmable output that supplies a positive when
activated:
• U1 ON = 13,8 Vdc
• U1 OFF = not connected
It is factory-programmed as a TC to abate microwaves when
system is switched off (U1 = OFF if at least one area is on during
out times; U1 = ON is the system is completely switched off.
The output is protected by a 100 ohm resitor.
It may also be used to command sirens or other roles.
U2, U3, U4 (Open Collector) PROGRAMMABLE OUTPUTS
In the Proxinet 192 control unit the U2 output is a
relay with C-NA terminals.
U2, U3, U4 are freely-programmable Open connector outputs
that provide a negative when activated:
• U2, U3, U4 ON = 0 V DC
• U2, U3, U4 OFF = not connected
The outputs are protected by 100 ohm resistors.
A 12 V DC short circuit with active output for an extended time may lead to breakage fo the protective resistor.
Siren requiring power supply

+ – U1 U2 U3 U4 NO C NC T –
AUX POS
M6 M7
APF22
O.C RELAY TAMPER
TT
+ –
TAMPER
+ – U1 U2 U3 U4 C NC T –
AUX POS
M6 M7
O.C RELAY TAMPER
12Vcc MCA PCS MANS–
SA10L
A
B
C
D
E
ACTUAL LANGUAGE:
ITALIANO
SELECT LANGUAGE:
ITALIANO
LOADING LANGUAGE
WAIT FOR RESTART
p. 18 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
If you wish to command a relay via an Open Collector output or
relay output you will need to add the 1N4007 diode parallel to
the relay coil.
GENERAL ALARM RELAY OUTPUTS RELAY 1 - RELAY 2
These relay outputs are for general alarm and are not programmable. They follow the general state of alarm and stay active for the
time programmed.
PSTN TELEPHONE LINE
LANGUAGE UPDATE BOARD PXLNG for control unit
The PSTN telephone line needs to be connected to terminals
[L, L] and in output, to terminals [T, T] for switch-boxes or
telephones.
So-called simulated phone lines like ADSL ones can
disturb CONTACT-ID digital communications with Security Firms.
For modifying the control unit language and firmware update. A language board is available for each type of control unit.
Update is available from version 1.0.16 of control unit.
At least a PXKWD keyboard must be connected (by default at address 1) for the language selection.
Change language by:
Ainserting the board;
Bresetting the control unit by pressing the button;
Cthe keypad shows the current language: press the button ;
Dselect the language to install using the keys / ;
A standby message is displayed during installation;
CThe current language is displayed after the update is over;
Bremove the board and re-start the control unit by pressing the button.
Siren requiring power supply Siren with on-board power supply

12345678910 11 12 13 14 15 16
p. 19 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
A
B
E
C
D
6.1 Features
GENERAL CHARACTERISTICS PXKWD
Power supply voltage 12 Vdc - 15 Vdc
Max power draw 60 mA
Working temperature 0° - 40° C
Relative humidity 25% - 75% senza condensa
Dimensions (HxLxD) 180x120 x 28 (a muro)
IP IP40
6.2 Card description
PXKWD
PXKWD DESCRIPTION
1
Bus RS-485 for connecting keypads, remote modules and inserters.
[+,-] power supply to bus.
[A,B] data.
2 [SW1] Anti opening / tearing tamper.
3 [JP1] Jumper to activate / deactivate the tamper (Jumper on = Tamper deactivated).
4 BUZZER Keypad buzzer
5 DL18 BUS communication.
6 PXKWD Keypad

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
08:24 16 /0 5 /10
#####UUUP---
p. 20 - Installation Manual code 24805670/06-05-2013 319F80C- ver 1.0 - The data and information in this manual may be changed at any time with no obligation on Brahms’s part to notify anyone of this.
ENGLISH
6.3 User interface
KEYPAD DISPLAY
The display is consists of two lines of 16 graphic characters. When idle the keypad goes into “Energy Saving” mode and reduces the
light intensity after a preset time.
Below the display there are 16 numbers that facilitate interpretation of the second line of display.
= area on.
= area in switching on phase (output time) without open inputs.
= area in switching on phase (output time) but not ready for adding presence of open inputs.
= area partially on (there is at least one temporarily excluded input associated to the area).
= area off.
= area not managed by the keypad.
Example:
Referring to the above shown display:
• Areas under management: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
• Areas not under management: 13, 14, 15, 16
• Areas switched-on: 1, 2, 3, 4, 5
• Areas being switched-on: 6, 7, 8, 9
• Areas switched-off: 10, 11, 12
#
U
X
P
-
LIGHT WARNINGS
LED STATUS LEGEND OF LIGHT SIGNALS
●
When off it means there are open inputs. Alarm is raised when a scenario is brought up. Check
open inputs when starting up scenarios.
●
Steadily on means there are NO open inputs. The system can be switched on without any problems.
●
When off it means that the areas are switched off (system switched off).
●
When on it means that all of the areas are switched on (system switched on entirely).
●
When flashing it means that at least one area is switched on (system switched on partially).
●
When off it means that the areas are NOT in alarm mode.
●
When on it means that at least one area is in alarm mode (system in alarm mode).
●
When flashing is means that the system has detected a silenced alarm. See event history for
alarm list. To remove notice see chapter on managing the system.
●
When off it means that there are faults in the system.
●
Steadily on it means the 230 Vac main power supply is absent.
●
When flashing it means that the control unit battery is not working.
(
●
always on,
●
flashing on,
●
off).
Table of contents