BRAHMA EG12 Series User manual

2704_r03 1/5
EG12* ... SERIES
SOLENOID GAS VALVES WITH 1/2”
CONNECTION AND OPERATING
PRESSURE UP TO 500mbar
DESCRIPTION
This series of solenoid gas valves are of normally closed
type, suitable for civil and industrial applications, supplied
with alternate or direct current and inclusive of a wire-net filter
on the inlet to avoid the entrance of dirt of > 1 mm.
Gas valves marked with “S” or “L” after reference type have
direct current supplied coil, which permitted to make actions
as silent as possible.
There is the possibility to have a fast opening or a slow
opening valve (obtained by special hydraulic shock-
obsorber), with flow adjustment and fast opening initial flow
adjustment and inlet pressure plugs (all of them) or outlet
plugs (excluding those with flow adjustment).
Gas valves of this series, conforming to EN161, have a CE
type Certificate (CE Reg. N° 63AQ0626) in accordance to
European Directives 90/396 and 93/68.
−EC- type certification in accordance with the new
European Gas Appliances Regulation (EU) 2016/426
(GAR);
−conformity to EC Low-voltage directive 2014/35/EU
TECHNICAL FEATURES
Class: A
Group: 2
Supply voltage (1): 230 Vac / 50-60 Hz
110 Vac / 50-6 Hz
Operating temperature: -10°C / +60°C
Closing time: ≤1s (all versions)
Opening time: ≤1s (quick opening
versions only)
Mounting: vertical and horizontal
Body: die-cast aluminium
Core hitch: PG9
(1) Versions with different supply voltages are available.

2/5 2704_r03
DIRECTIONS FOR INSTALLATION AND MAINTENANCE
•This valve is a safety appliance and should not be
modified. The manufacturer's responsibility and guarantee
are invalidated in case the device is tampered with by the
user.
•The applicable national regulation and European
standards (Ex. EN 60335-1 and EN 60335-2-102) related
to the electrical safety must be respected;
•Assemble the valve to the installation so that the arrow
on the valve body has the same direction as the fuel flow.
•During the assembly of the valve to the installation
piping, avoid twisting on the sheath and always use an
hexagonal wrench to be fitted to the valve body.
•Make sure that no foreign matters have entered the
valve body.
•Make sure that the max. fuel input pressure never
exceeds the value appearing on the label.
•All operations (installation, maintenance, etc.) must be
carried out by a qualified technician.
•Before any connection operation, completely isolate the
system from power supply (multi-pole disconnection).
Place the system safely to avoid accidental switch-on and
make sure there is no voltage. If the system is not
switched off, there is a risk of electric shock.
•During and after any operation (installation,
maintenance, etc.), make sure that the type and code are
the ones provided, check the correct functioning and the
internal and external thickness of the valve.
•In the event of a fall or impact, the valves must not be
started, as safety functions may be compromised even if
no damage is visible to the outside.
•Faulty valves or damaged must be unplugged from power
supply and cannot be used.
•The valve has a designed lifetime* based on the
endurance tests in the standard EN 161. A summary of
the conditions has been published by the European
Control Manufacturers Association (Afecor)
(www.afecor.org). The designed lifetime is based on use
of the valve according to the manufacturer’s technical
notes. After reaching the designed lifetime in terms of the
number of burner startup cycles, or the respective time of
usage, the valve has to be replaced by authorized
personnel.
* The designed lifetime is not the warranty time specified
in the Terms of Delivery
DIRECTIONS FOR EG12*L... VALVES ADJUSTMENT
Flow adjustment for EG12*L...
To adjust the gas flow, you have to remove one of the two
screws used to fasten the lag group (the not enamelled one,
marked with 4 in Fig.1) and rotate clockwise the whole group
to reduce the flow or in the opposite direction to increase it.
Opening time adjustment
After removing the top protection, by rotating it
counterclockwise, you have to act on the adjustment screw,
marked with 1 in Fig.1; by rotating clockwise, the opening
time becomes longer, by rotating in the opposite direction, the
opening time becomes shorter.
Quick release initial flow adjustment
After removing the top protection by rotating it
counterclockwise, if you rotate clockwise the nut marked with
2 in Fig.1, the initial release will be reduced; if you rotate the
same nut counterclockwise, the initial release will be
increased.
DIRECTIONS FOR EG12*SR... AND EG12*AR... VALVES
ADJUSTMENT
Flow adjustment for EG12*R
After removing the bottom protection by rotating it
counterclockwise, rotate clockwise the nut marked with 1 in
Fig.2 to reduce the flow, rotate in the opposite direction to
increase the same.
2 1
3
4
Fig. 1
1
Fig. 2

2704_r03 3/5
OVERALL DIMENSIONS
EG12*L*GMO
EG12*SR*GMO
EG12*A*A3C
EG12*S*GMO
EG12*AR*CFD
VALVE BODY CENTRE
DISTANCE INLET/OUTLET
EG12*SR*GFD

4/5 2704_r03
DIAGRAM
PRESSURE DROP
mbar
FLOW
RATE
m
3
/h
A : Standard flow rate m
3
/h of NATURAL GAS relative density 0.554
B : Standard flow rate m
3
/h of LPG relative density 1.54
C : Standard flow rate m
3
/h of TOWN GAS relative density 0.411
D : Standard flow rate m
3
/h of AIR relative density 1
SUMMARY TABLE
Type Operating
pressure
(mbar)
Orifice
diameter
(mm) Connections Weight
(g) Coil Consumption
(VA)
230Vac
Consumption
(VA)
110Vac
Flow
(m³/h gas with
∆P2.5mbar)
EG12*A
EG12*A
EG12*A
0 ÷ 500
0 ÷ 500
0 ÷ 500
15
15
15
G1/2"
G1/2"
G1/2"
734
764
766
BE6*A3C
BE6*AFP
BE6*AFD
20
20
20
18
18
18
7,5
7,5
7,5
EG12*AR
EG12*AR
EG12*AR
0 ÷ 500
0 ÷ 500
0 ÷ 500
15
15
15
G1/2"
G1/2"
G1/2"
752
782
784
BE6*A3C
BE6*AFP
BE6*AFD
20
20
20
18
18
18
7,5
7,5
7,5
EG12*S
EG12*S
EG12*S
EG12*S
0 ÷ 500
0 ÷ 500
0 ÷ 500
0 ÷ 500
15
15
15
15
G1/2"
G1/2"
G1/2"
G1/2""
780
810
812
832
BE6*C3C
BE6*CFP
BE6*CFD
BE6*G..
20
20
20
20
18
18
18
18
7,5
7,5
7,5
7,5
EG12*SR
EG12*SR
EG12*SR
EG12*SR
0 ÷ 500
0 ÷ 500
0 ÷ 500
0 ÷ 500
15
15
15
15
G1/2"
G1/2"
G1/2"
G1/2"
800
830
832
851
BE6*C3C
BE6*CFP
BE6*CFD
BE6*G..
20
20
20
20
18
18
18
18
7,5
7,5
7,5
7,5
EG12*L 0 ÷ 250 15 G1/2" 935 BE6*G.. 20 18 7,5

NOTES FOR PRODUCT DISPOSAL
The device contains electronic components and cannot therefore be disposed of as normal household waste. For the disposal
procedure, please refer to the local rules in force for special waste.
BRAHMA S.p.A.
Via del Pontiere, 31
37045 Legnago (VR) - ITALY
Tel. +39 0442 635211 - Fax +39 0442 25683 16/03/18 Subject to amendments without notice
http://www.brahma.it
E-mail : brahma@brahma.it
2704_r03 5/5
ATTENTION --> Company Brahma S.p.A. declines any responsibility for any damage resulting from Customer tampering with the device.
TYPE REFERENCE
EG12 * S R P * G FD 8 P D 230/50-60
Supply voltage
Type Description
110/50-60 110Vac/50-60Hz
230/50-60 110Vac/50-60Hz
Opening Type (fast/slow)
Type Description
A Fast opening valve.
S Fast, silent opening valve.
L Slow, silent opening valve
(this version is inclusive of
flow adjuster).
Flow adjustment
Valve fitted with equipment for
flow adjustment.
Pressure
plug
Valve inclusive of pressure
plug G1/4” size.
Gas pressure switch type
Type Description
P Fixed setting
PR adjustable setting
Gas pressure switch position
Type Description
D Right
S Left
Connection type
Type Description
2C Connection with two core
cable-IP65.
3C Connection with three core
cable-IP65.
FP Connection with flat fast-on.
FD Connection with fast-on for plug
DIN43650-IP65.(GFD IP40)
MO Connection with terminal
board-IP40.
Type
Test pressure point position
Type Description
7 Inlet left
8 Inlet right
5 Outlet (“S” and “L” versions only)
Winding type
Type
Descrizione
A Supply in alternate current.
C Supply in direct current.
G
Supply in alternate current, but valve
operates in direct current thanks to an
embodied rectification bridge.
(“MO” and “FD” connection versions only)
Table of contents
Other BRAHMA Control Unit manuals
Popular Control Unit manuals by other brands

Rockwell Automation
Rockwell Automation Allen-Bradley MSR42 user manual

HMS
HMS IXXAT Safe T100 Safety Manual–Original Instructions

BENKISER
BENKISER 828er quick start guide

Applied Motion Products
Applied Motion Products Si2035 Hardware manual

Graco
Graco CGM Instructions and parts

Burkert
Burkert 6724 Series operating instructions