Basic documentation for OS-1401 module
1. DESCRIPTION AND PARAMETERS
The OS-1401 expansion module contains 12 semiconductor outputs with a semiconductor
switching element and plus common terminal. The module is equipped with removable screw-
type connector with 5.08 mm pitch. The outputs DO0÷DO3 can switch max. 24 V DC, 2 A per
output (the sum of all 4 output currents must not overtake 4.4 A). The outputs DO4÷DO11 can
switch max. 24 V DC, 0.5 A per output. The outputs are galvanically isolated from the internal
circuits (including power supply and communication) and group of outputs are separated one
from another. The status of each output indicated by LED at the front module panel.
1.1 BASIC PARAMETERS
Product standard ČSN EN 61131-2:2005 (idt IEC 61131-2:2003)
Protection class of electrical object
ČSN EN 61140:2003 (idt IEC 61140:2001) II
Connection removable screw-type connections, max. 2.5 mm
2
con-
ductor per terminal
Type of equipment built in
Power supply (SELV) typ. 24 VDC
Internal protection No
Typical power input 1 W
Max. power input 2 W
Power supply galvanic isolation from internal
circuits No
Coverage
- ČSN EN 60529:1993 (idt IEC 529:1989) IP10B
Height 100 g
Dimensions 90 × 53 × 65 mm
1.2 OPERATIONAL CONDITIONS
Class of ambient influence - ČSN 33 2000-
3:1995 (mod IEC 364-3:1993) normal
Operating temperature range 0 °C to +55 °C
Permissible temperatures during transport –25 °C to +70 °C
Relative humidity 10 % to 95 % without condensation
Atmospheric pressure min. 70 kPa (< 3000 m over the sea level)
Degree of pollution –
ČSN EN 60664-1:2004 (mod IEC 60664-1:1992)
1
Overvoltage category of installation -
ČSN EN 60664-1:2004 (mod IEC 60664-1:1992)
II
Working position vertical
Type of operation continuous
Electromagnetic compatibility
Emissions -
ČSN EN 55022:1999 (mod CISPR22:1997) class A*
Immunity min. according to requirements ČSN EN 61131-2:2005
Sinusoidal vibration resistance ** 10 Hz to 57 Hz, amplitude 0.075 mm,
57 Hz to 150 Hz, acceleration 1G
* In indoor conditions (i.e. such conditions, where using of radio and TV sets can be supposed in a dis-
tance of 10 m from the mentioned equipment), the product can cause radio disturbances. It might be
required in such cases that the user takes necessary measures to avoid this.
** Fc test according to ČSN EN 60068-2-6 (idt IEC 68-2-6:1995), 10 cycles in each axe.