BroadAccess CAG40D-MIN User manual

P/N 760-000718 Rev A
BroadAccess
CAG40D-MIN
Installation Guide


BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A
000718a_CAGD40-MIN.doc 08-Mar-06 4:33 PM Page i
Table of Contents
List of Figures __________________________________________________________________iii
List of Tables___________________________________________________________________ iv
1. Introduction _____________________________________________________________ 1
1.1. Scope__________________________________________________________ 1
1.2. Compatibility ___________________________________________________ 1
1.3. Related Documentation____________________________________________ 2
1.4. System Overview ________________________________________________ 2
1.5. Safety Precautions________________________________________________ 4
1.6. Inventory Check _________________________________________________ 4
2. Site Preparation __________________________________________________________ 5
2.1. Overview_______________________________________________________ 5
2.2. Mechanical Requirements__________________________________________ 5
2.2.1. Rack Preparation _______________________________________ 5
2.3. Cable Requirements ______________________________________________ 6
2.3.1. Power ________________________________________________ 6
2.3.2. Open Cables___________________________________________ 6
2.3.3. Fiber Optic Cables ______________________________________ 6
3. Installation______________________________________________________________ 7
3.1. Installation in 19” Rack ___________________________________________ 7
3.1.1. General_______________________________________________ 7
3.1.2. Parts Required _________________________________________ 9
3.1.3. Tools Required_________________________________________ 9
3.1.4. Installation Procedure ___________________________________ 9
3.2. Backplane Dipswitch Settings _____________________________________ 10
3.2.1. General Configurations _________________________________ 10
3.2.2. RU Number Settings ___________________________________ 11

Table of Contents
Page ii March 2006
P/N 760-000718 Rev A
3.2.3. System Number Settings_________________________________ 12
3.2.4. CU Group Number _____________________________________ 13
4. Cable Connections _______________________________________________________ 14
4.1. Overview ______________________________________________________ 14
4.2. Ground________________________________________________________ 14
4.2.1. Racks________________________________________________ 14
4.2.2. Cages________________________________________________ 15
4.3. DC Power _____________________________________________________ 16
4.3.1. Installation Procedure___________________________________ 16
4.3.2. External Power Supply Test ______________________________ 17
4.3.3. Backplane Voltage Test _________________________________ 17
4.4. External Cables _________________________________________________ 18
4.5. Communication Ports ____________________________________________ 19
4.6. Fan Connection _________________________________________________ 20
5. Final Installation Activities ________________________________________________ 21
5.1. Card Installation ________________________________________________ 21
5.2. Accessories ____________________________________________________ 22
5.3. System Power Up _______________________________________________ 22
6. Index__________________________________________________________________ 23

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page iii
List of Figures
Figure 1. CAG40D-MIN - Front View _____________________________________________ 3
Figure 2. Installation of CAG40D-MIN in 19” Rack __________________________________ 8
Figure 3. Location of Dipswitches on CAG40D-MIN Backplane________________________ 10
Figure 4. Grounding Rack and CAG40D-MIN Cages_________________________________ 15
Figure 5. Power Cable Connections to CAG40D-MIN Backplane _______________________ 16
Figure 6. CAG40D-MIN Backplane Voltage Test Points ______________________________ 18
Figure 7. Comm Port Locations on CAG40D-MIN___________________________________ 19
Figure 8. Fan Cable Connection on CAG40D-MIN __________________________________ 20
Figure 9. Card Positions in Typical CAG40D-MIN __________________________________ 21

Table of Contents
Page iv March 2006
P/N 760-000718 Rev A
List of Tables
Table 1. Power Cable Specifications_______________________________________________ 6
Table 2. KIT-19”-E Installation Kit _______________________________________________ 9
Table 3. CAG40D-MIN Backplane Dipswitches ____________________________________ 11
Table 4. RU Number Dipswitch Setting ___________________________________________ 12
Table 5. Dipswitch Settings Used to Set System Number in Multiple CU
Systems _____________________________________________________________ 13
Table 6. CU Group Number Dipswitch Settings (16-17) on CAG40D-MIN
Backplane ___________________________________________________________ 13
Table 7. CAG40D-MIN Backplane Test Points _____________________________________ 18

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 1
1. Introduction
1.1. Scope
This document describes the procedures required for installation of a basic
BroadAccess CAG40D-MIN in a 19” rack.
Note: The instructions in this manual are also relevant for the
CAGE40-MIN cage.
Note: If installing the CAG40D-MIN with the MPU-x, you should also refer
to the MPU-x Unit Installation Guide.
The document includes the following sections:
•Section 1 - Introduction: provides document and system overview.
•Section 2 - Site Preparation: explains how to prepare the site prior to
installation.
•Section 3 - Installation: explains how to install a CAG40D-MIN in a 19” rack
and basic rack configuration.
•Section 4 - Cable Connections: explains how to connect power, grounding and
communication cables to the system.
•Section 5 - Final Installation Activities: outlines the remaining activities
required to complete the installation of the system.
1.2. Compatibility
The CAG40D-MIN is compatible for use as a Remote Unit (RU) with
BroadAccess systems.

1. Introduction
Page 2 March 2006
P/N 760-000718 Rev A
1.3. Related Documentation
The following related BroadAccess documentation is available on the release date
of this guide.
•System Description
•Service Manual including:
CAG40D-M Installation Guide
Link, Service and Alarm Cables Connection Guide
Applications and Engineering Guide
BroadAccess Configuration Guide
BroadAccess Maintenance Guide
LCT Installation and Administration Guide
Card and Accessory Installation Instructions
1.4. System Overview
The CAG40D-MIN, which serves as an RU, comprises a card cage into which all
cards required for operation are inserted. A CAG40D-MIN cage supports up to
128 subscribers.
The CAG40D-MIN can be installed with the MPU-x. The MPU-x (Mini Power
Unit) contains a charger and backup batteries for powering the CAG40D-MIN.
The CAG40D-MIN is supplied with a front door. The door assists in cooling the
cards by blocking the cage’s front opening, so that the airflow is directed upwards,
toward the cards. The door also protects the equipment, and contains a transparent
plastic window that enables easy monitoring.
The CAG40D-MIN cage with cards is shown in Figure 1.

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 3
Figure 1. CAG40D-MIN - Front View
The CAG40D-MIN can be installed as follows:
•Outdoor Cabinet (factory installed)
•standard 19” rack
There are three methods of installing the CAG40D-MIN :
•joined units configuration - CAG40D-MIN and MPU-x are assembled to form
a combined unit.
•separate units configuration - CAG40D-MIN and MPU-x are installed in
different locations.
•without the MPU-x unit - a different power supply feeds the CAG40D-MIN.
Note: In configurations where the CAG40D-MIN is installed in a 19’’ rack
separate from the MPU-x (or configurations where a different power
supply feeds the CAG40D-MIN), an optional adapter panel
(ADP-CAG-M) is required.

1. Introduction
Page 4 March 2006
P/N 760-000718 Rev A
1.5. Safety Precautions
To avoid injury and prevent equipment damage, observe the following safety
precautions:
•Do not move or ship equipment unless it is properly packed in its original
wrapping and shipping containers.
•Observe ESD (Electrostatic Discharge) procedures when handling card.
•When connecting equipment to the DC voltage supplies, ensure correct
polarity.
•Equipment service and maintenance should be undertaken only by trained
personnel.
•Do not touch the backplane when system power is on.
•To prevent damage by lightning, ground the system units and add lightning
protectors to any lines that exit the building.
•Do not permit unqualified personnel to operate workstations used to manage
the system.
1.6. Inventory Check
Before installing the system, ensure that all the equipment to be installed has
arrived. At each site, remove the lists from their envelopes. Take the equipment
out of the boxes, and check that all the parts appearing in the lists have in fact
arrived.
If anything is missing in the order, do not continue with the installation without
conferring with an experienced installation technician. Make sure that the missing
equipment is received from the supplier. If you are uncertain whether or not to
continue with the installation before the missing equipment arrives, please contact
the Customer Support department.

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 5
2. Site Preparation
2.1. Overview
This section describes the required actions that must be performed, before
installing in a rack, as follows:
•mechanical requirements
•cable requirements
2.2. Mechanical Requirements
2.2.1. Rack Preparation
2.2.1.1. Rack Preparation for 19in 44U Racks supplied with the CAGE40-M
The rack is prepared and installed according to the 19in 44U Rack Installation
Instructions supplied with the Service Manual.
2.2.1.2. Rack Preparation for other Racks
When a CAG40D-MIN is to be installed on other racks, the rack should take into
account the following CAG40D-MIN dimensions:
•Width 482 mm/19 inches
•Height 6U (246 mm/9.7 inches)
•Depth 302 mm/11.9 inches total (280 mm/11 inches from rack front)
•Weight Approx. 10 kg/22 lb (for typical CAG40D-MIN including cards)
In addition, a fan unit is installed below each CAG40D-MIN. Ensure that space is
set aside for each fan unit. The fan unit’s dimensions are:
•Width 482 mm/19 inches
•Height 1U (41 mm/1.6 inches)
•Depth 247 mm/9.8 inches
Note: It is recommended to leave enough space behind the rack to allow
easy access for maintenance personnel.

2. Site Preparation
Page 6 March 2006
P/N 760-000718 Rev A
2.3. Cable Requirements
2.3.1. Power
The power source is connected to the system via the female power tap connectors.
1. Each CAG40D-MIN, including fans, requires a power source (-48 Vdc or
-60 Vdc) for a maximum load of 16 A via a power junction box that includes
circuit breakers. For each CAG40D-MIN, a 16 A circuit breaker is required.
Note: If the CAG40D-MIN is installed with the MPU-x, refer to the MPU-x
Unit Installation Guide for cable connections.
2. Prepare cables in accordance with the specifications detailed in Table 1.
3. Ensure that all wires end with suitable cable terminals.
Table 1. Power Cable Specifications
Function Cable Color Cable
-48/-60 Vdc Black 10 AWG (6 mm2)
Positive Red 10 AWG (6 mm2)
Ground Yellow/Green 10 AWG (6 mm2)
2.3.2. Open Cables
When ordering open cables (HDSL, F/O, subscriber, alarm etc.), ensure that the
length you specify fits the distance between the rack and the MDF.
2.3.3. Fiber Optic Cables
The maximum attenuation permitted on each fiber optic cable (Tx and Rx) that
will serve as link between CU and RU, or uplink, depends on the optical card to
be used on the link. For further details, refer to the installation instructions for the
specific card.

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 7
3. Installation
3.1. Installation in 19” Rack
3.1.1. General
This section describes the installation of a CAG40D-MIN in a standard 19” rack.
Several cages can be installed above each other in a standard 19” rack, providing
that an interval of 1U is maintained between each cage for a fan unit, which is
installed below each CAG40D-MIN (see Figure 2).
Caution: In a rack containing more than one system, intervals of at least 1U
must be allowed for above and below each CAG40D-MIN, to provide
airflow between cages. In cases where other equipment is installed in
the same rack, every precaution must be taken not to obstruct the
airflow around each CAG40D-MIN. For this reason, please consult
Customer Support before installing other equipment in the same rack
as CAG40D-MIN.

3. Installation
Page 8 March 2006
P/N 760-000718 Rev A
6U
RACK
FAN UNIT
1U
CAGE 2
ON
OFF
PSDC
Vin
FAIL
ON
OFF
PSDC
Vin
FAIL
ONTU-
E15 ONTU-
E15 CPTCPT
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
LI16-
CU-E
Figure 2. Installation of CAG40D-MIN in 19” Rack

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 9
3.1.2. Parts Required
Table 2 lists the parts required for installation of a single CAG40D-MIN:
Table 2. KIT-19”-E Installation Kit
Item Part Description CAT No. Quantity
1 Front panel fixings HH23/55468 26
2 Nut, hex, S.S. M6 HN06/N0000 26
3 Nut, floating M6 HN06/NF006 26
4 Screw, pan-phil. M6x16 HS06/N6P15 26
5 Washer, plastic, M6x14 HW06/P0006 26
6 ADP-CAG-M adapter panel for 19” rack
(optional) 722Y73-901 1
3.1.3. Tools Required
•Phillips screwdriver
•Crimping tool
•Digital voltmeter (DVM)
•Hexagonal head ¼ ” screwdriver
3.1.4. Installation Procedure
Note: Numbers in brackets refer to the item column of Table 2.
1. Attach ADP-CAG-M adapter panel (item 6) to CAG40D-MIN left wall side
using screws and washers (items 4, 5), as shown in Figure 1.
2. Prepare the screws for installation by inserting them in the plastic washers as
follows:
For racks with square holes: use screws (item 4) and washers (item 5)
For racks with round holes: use screws (item 4) and washers (item 1)
3. Install floating nuts (item 3 for racks with square holes; item 2 for racks with
round holes) behind the rack front rail for each of the four holes (two on each
side).
4. Place the CAG40D-MIN at the required height.
5. For each of the four holes in the front of the CAG40D-MIN (two on each side),
insert the assembled screw and washer from the front of the CAG40D-MIN,
and secure with the floating nuts.

3. Installation
Page 10 March 2006
P/N 760-000718 Rev A
6. Install a fan unit (FAN3A-RU or FAN3AL-RU) as follows:
indoor installation: one unit beneath each BroadAccess CAG40D-MIN
cage
outdoor installation: one unit beneath each BroadAccess CAG40D-MIN
cage if LI32 series cards are used.
Note: For fan unit installation, see the specific fan installation instructions
supplied with the Service Manual.
Note: Do not insert hands when operating fan - unit underside is open.
Failure to observe this caution may result in injury to personnel.
3.2. Backplane Dipswitch Settings
3.2.1. General Configurations
Three sets of dipswitches are located on the left side of the backplane at the rear
of the cage, as shown in Figure 3 and described in Table 3 and Table 6.
Note: Before power-up of the system, verify that all dipswitches are set
according to the exact configuration of your system.
Figure 3. Location of Dipswitches on CAG40D-MIN Backplane

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 11
Table 3. CAG40D-MIN Backplane Dipswitches
Switch Switch Name Function
1 Cage # Sets RU cage number:
Left - #2 (241 - 480 subscribers)
Right - #1 (1 - 240 subscribers)
2 CU Cage # Sets RU cage to work with CU cage 1 or 2, when star, ring
or mixed topology is used, where:
Left - CU cage 2
Right - CU cage 1
For example, in a 480 subscriber system (two cages at CU
side), RU 2 Cage 1 should be set to work with CU cage 2 by
setting the dipswitch at RU 2 to Left.
3 Unit #0
4 Unit #1 J3 - J7 set the RU number in the system (for details see
5 Unit #2 Table 4).
6 Unit #3
7 Unit #4
8 CU/RU Right – RU
9 to 10 System Number Set the system number for multi-CU systems (for details see
Table 5).
11 16/(12) Sets metering frequency:
Left - 16 kHz
Right - 12 kHz
12 48/60 Sets input DC supply level:
Left - -60 Vdc
Right - -48 Vdc
13 to 15 Optic
Configuration Dipswitches 13 to 15 set the optic configuration for the
system. For details, see “Optic Configurations” in the
Applications and Engineering Guide supplied with the
Service Manual.
16 to 17 CU Group # Set the CU group number (for details see Table 6).
18 to 21 Spare Not in use
22 to 24 NIU Not in use
3.2.2. RU Number Settings
To enable identification by the system, each RU must be assigned a number by
configuring dipswitches 3 to 7 on the RU backplane.
Table 4 details the dipswitch settings for each of the possible RU number options.
For example, to set an RU as Unit #1, set dipswitches 3, 4, 5, 6 and 7 to the right.
Note: The number of RUs that can be connected to each CU varies
according to topology and transmission type. Currently up to 16 RUs
(CAG40D-M, CAGE40-M, CAG40D-MIN or CAGE40-MIN) can be
connected to each CU.
Note: The RUs should always be numbered between 1 to 16.

3. Installation
Page 12 March 2006
P/N 760-000718 Rev A
Table 4. RU Number Dipswitch Setting
RU DipswitcH
Number 3 4 5 6 7
1 Right Right Right Right Right
2 Left Right Right Right Right
3 Right Left Right Right Right
4 Left Left Right Right Right
5 Right Right Left Right Right
6 Left Right Left Right Right
7 Right Left Left Right Right
8 Left Left Left Right Right
9 Right Right Right Left Right
10 Left Right Right Left Right
11 Right Left Right Left Right
12 Left Left Right Left Right
13 Right Right Left Left Right
14 Left Right Left Left Right
15 Right Left Left Left Right
16 Left Left Left Left Right
17 Right Right Right Right Left
18 Left Right Right Right Left
19 Right Left Right Right Left
20 Left Left Right Right Left
21 Right Right Left Right Left
22 Left Right Left Right Left
23 Right Left Left Right Left
24 Left Left Left Right Left
25 Right Right Right Left Left
26 Left Right Right Left Left
27 Right Left Right Left Left
28 Left Left Right Left Left
29 Right Right Left Left Left
30 Left Right Left Left Left
31 Right Left Left Left Left
32 Left Left Left Left Left
3.2.3. System Number Settings
When using multiple CU systems (more than one CU over SDH rings), each CU
and RU must be assigned a number by configuring dipswitches 9 and 10 on the
backplane.
Table 5 details the dipswitch settings for each of the possible system number
options. For example, to set a CU/RU as System #1, set dipswitches 9 and 10 to
the right.
Note: One CU in the multi CU system must be numbered as “1”.

BroadAccess CAG40D-MIN Installation Guide
P/N 760-000718 Rev A March 2006
Page 13
Table 5. Dipswitch Settings Used to Set System Number in Multiple CU
Systems
Dipswitch
System Number 9 10
1 Right Right
2 Left Right
3 Right Left
4 Left Left
3.2.4. CU Group Number
The CU Group Number, set through Dipswitches 16 and 17 on the CAG40D-MIN
backplane, is used for BroadAccess systems in which the CU is connected to the
local exchange through 2W connections in Automatic Connection Mode (if using
V5.x to connect the CU to the local exchange, use the management software
provided with your system to perform line provisioning accordingly).
Note: The CU Group Number is not applicable for Manual Connection
Mode.
Table 6 details the dipswitch settings for each of the possible CU Group Number
options.
Table 6. CU Group Number Dipswitch Settings (16-17) on CAG40D-MIN
Backplane
CU Cage No.
Dipswitch #2. CU Group No.
DipSwitch 16 CU Group No.
DipSwitch 17 CU Slot No. CU Subscriber
No.
1 (right) Right Right 1-4 1-64
1 (right) Left Right 5-8 65-128
1 (right) Right Left 9-12 129-192
1 (right) Left Left 13-15 193-240
2 (left) Right Right 1-4 241-304
2 (left) Left Right 5-8 305-268
2 (left) Right Left 9-12 369-432
2 (left) Left Left 13-15 433-480

4. Cable Connections
Page 14 March 2006
P/N 760-000718 Rev A
4. Cable Connections
4.1. Overview
This section describes the connection procedures for all cables required for
operating a 128 subscriber (single cage) system.
4.2. Ground
Note: Use accepted methods for grounding (grounding screw, clamp, etc.)
when connecting ground cables.
Note: Unless otherwise specified by local standards, we recommend the use
of 10 - 16 mm2cable for grounding purposes. Grounding cables
between cage and rack may be 6 mm2.
Note: For all grounded items, ground resistance measured between the
main ground bar (MGB) connected to the ground array and the earth
mass must be according to local regulations and not more than 5
Ω
.
Note: Safety/protective ground is through the rack and cage connections to
the ground.
Note: Logic ground to the equipment is through the grounded (+) Vdc.
4.2.1. Racks
Each rack must be grounded to the grounding system of the building in which it is
located.
1. Connect one end of the grounding cable to the building’s grounding system
(see Figure 4).
2. Connect the other end of the grounding cable to the rack ground bolt (for a
19in 44U Rack, see the installation instructions provided with the rack for
more information).
Table of contents
Popular Industrial Equipment manuals by other brands

POWERHANDLING
POWERHANDLING PowerPallet 2000 user manual

ABB
ABB HT609266 Operation manual

EINHELL
EINHELL LE-OFT 800 operating instructions

Wöhner
Wöhner CrossBoard 11 500 quick start guide

A.B.S.
A.B.S. Flexilo SPRING Assembly-, Operating-, and Filling Instructions

Beko
Beko BEKOSPLIT 14S Instructions for installation and operation