Broan HRVH100S User manual

USER GUIDE
HEAT RECOVERY VENTILATOR
MODEL HRVH100S
AND
ENERGY RECOVERY VENTILATOR
MODEL ERVH100S
VB0235
These products earned the
ENERGY STAR®by meeting strict energy
efficiency guidelines set by Natural
Resources Canada and the US EPA. They
meet ENERGY STAR requirements only
when used in Canada.
22735 rev. 01
READ AND SAVE THESE INSTRUCTIONS
INSTALLER: LEAVE THIS MANUAL WITH HOMEOWNER
Broan-NuTone LLC; Hartford, Wisconsin www.broan.com 1-877-862-7626
REGISTER YOUR PRODUCT ONLINE AT: www.broan.com/register
For additional information - visit www.broan.com

Congratulations!
You have made an excellent choice! The operating principle of your Heat Recovery Ventilator
or your Energy Recovery Ventilator will give you personal comfort you have never known
before.
We have prepared this User Guide especially for you. Please read it carefully to ensure you
obtain full benefit from your unit. Over the coming months, you will increasingly appreciate the
feeling of living in a more comfortable house.
Please take note that this manual uses the following symbols to emphasize particular
information:
WARNING
Identifies an instruction which, if not followed, might cause serious
personal injuries including possibility of death.
!
CAUTION
Identifies an instruction which, if not followed, may severely damage the
unit and/or its components.
CAUTION
Make sure at all times that the outside intake and exhaust hoods are free
from any snow during the winter season. It is important to check your unit
during a big snow storm, so it doesn’t draw in any snow. If this is the case,
please operate the unit in recirculation mode, or turn it OFF for a few hours.
Do not use your unit during construction or renovation of your house or
when sanding drywall.This type of dust may damage your system.
Since the electronic control system of the unit is incorporated with a
microprocessor, it may not operate correctly because of external noise
or very short power failure. If this happens, unplug the unit and wait
approximately 10 seconds. Then, plug the unit in again. At least once a
year, the unit mechanical and electronic parts should be inspected by
qualified service personnel.
2
NOTE: Indicates supplementary information needed to fully complete an instruction.
We welcome any suggestions you may have concerning this guide and/or the unit, or ways to
better serve you. Please forward all correspondence at the address below:
Broan-NuTone LLC
Indoor Air Quality Mkt.
926 W. State St.,
Hartford, WI 53027
CAUTION
When leaving the house for a long period of time (more than two weeks), a
responsible person should regularly check if the unit operates adequately.
If the ductwork runs through an unconditioned space (e.g.: attic), the unit
must operate continuously except when performing maintenance and/or
repair. Also, the ambient temperature of the house should never drop
below 65°F.

TABLE OF CONTENTS
3
1. SERVICE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 BOOTING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 OPTIONAL MAIN AND AUXILIARY CONTROLS . . . . . . . . . . . . . . . . . . . 4
3. MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
3.1 QUARTERLY MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
3.2 ANNUAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DESCRIPTION HRVH100S ERVH100S QUANTITY
HEPA filter (1 per kit) and
prefilter (2 per kit) kit SV21293 SV21293 1
Prefilter (2 per kit) SV61561 SV61561 1
Core filter SV61563 SV61562 2
All parts listed in the following table are available where you have bought your unit.
NOTE: Please note that parts not listed are not available; those parts require assembly
knowledge that only manufacturer can garantee.
1. SERVICE PARTS
REPLACEMENT PARTS AND REPAIRS
In order to ensure your ventilation unit remains in good working condition, you must
use Broan-NuTone LLC genuine replacement parts only. Broan-NuTone LLC genuine
replacement parts are specially designed for each unit and are manufactured to comply
with all the applicable certification standards and maintain a high standard of safety. Any
third party replacement part used may cause serious damage and drastically reduce the
performance level of your unit, which will result in premature failing. Broan-NuTone LLC
recommends to contact a certified service depot for all replacement parts and repairs.

4
2. CONTROLS
This unit is equipped with an integrated control located
under the electrical compartment of the unit. Use the push
button (1) to control the unit; the LED (2) will then show
which mode the unit is in (see illustration at right and table
below).
2.1 BOOTING SEQUENCE
The unit booting sequence is similar to a personal computer boot sequence. Each time
the unit is plugged after being unplugged, or after a power failure, the unit will perform a
30-second booting sequence before starting to operate.
During the booting sequence, the integrated defrost control LED will light AMBER for
5 seconds, and then will shut off for 2 seconds. After that, the LED will light RED for
the rest of the booting sequence. During this RED light phase, the unit is checking and
resetting the motorized damper position.Once the motorized damper position completely
set, the RED light turns off and the booting sequence is done.
NOTE: No command will be taken until the unit is fully booted.
NOTE: The integrated control must be turned OFF to use an optional main control.
If a problem occurs during the unit operation, its integrated control LED (2) will blink.The color
of the blinking light depends on the type of error detected. Refer to Section 4 Troubleshooting
on last page for further details.
1
2
VD0310
LED COLOR RESULTS
AMBER UNIT IS ON LOW SPEED
GREEN UNIT IS ON HIGH SPEED
NOLIGHT UNIT IS OFF OR CONTROLLED BY AMAIN CONTROL
2.2 OPTIONAL MAIN AND AUXILIARY CONTROLS
For more convenience, this unit can also be controlled using an optional main wall
control. Many models can be used, but only one main wall control can be connected to
the unit.
NOTES: 1. The integrated control must be turned OFF to use an optional main control.
2. If an optional auxiliary control is used, if activated, the operation of this
auxiliary control will override the optional main control operation.
For more information about the available controls and their operation modes, refer to the
Main and auxiliary wall control User Guide (included with the ventilation unit and also
available at www.broan.com).

5
WARNING
Risk of electric shock. Before performing any maintenance, always turn off
and disconnect the unit from its power source. When cleaning the unit, it
is recommended to wear safety glasses and gloves.
!
3. MAINTENANCE
A. Heat or energy recovery core
B. Heat or energy recovery core filters (2)
C. Prefilter
D. HEPA filter
E. Core bracket
VL0060
AB
B
D
C
E
This unit needs quarterly and annual maintenances.
Refer to the illustration below to identify the inner removable parts of your unit:
3.1 QUARTERLY MAINTENANCE
Turn the unit OFF and unplug it.
Using a Phillips or a Robertson
screwdriver, loosen both door screws
(A).
NOTE: The screws will stay attached to
the door.
VD0302
A
Other manuals for HRVH100S
1
This manual suits for next models
1
Table of contents
Languages:
Other Broan Heating System manuals
Popular Heating System manuals by other brands

Truma
Truma Trumatic E 2400 E Operating instructions and installation instructions

Aqua-Hot
Aqua-Hot 200 Series installation manual

Vent-Axia
Vent-Axia HR100S Installation and maintenance instructions

aerauliqa
aerauliqa QR350ABP installation manual

WatchGas
WatchGas ATEX BEACON manual

Lampoassa
Lampoassa 203GT user manual