Delayed Egress Lock Maintenance Manual
INSTRUCTIONS
Electrified Locks, Relays and Timers
These systems are meant to delay the egress in certain but not all cases. The delayed egress device should be automatically
unlocked in case of a re, earthquake etc. The door should be unlocked at once when the sprinkler or re detection system goes o
or during a power outage. In other words, it’s a matter of public safety if an emergency evacuation is required.
FOR SPECIAL LOCKING ARRANGEMENT: The delayed egress lock must be wired to a re alarm system per NFPA code or other
regulations to bypass the time delay in the event of a re. Contact your local code authority to verify compliance with re and
building codes.
RECOMMENDATIONS FOR INSPECTION AND MAINTENANCE:
1. It is the responsibility of the installer to ensure that the Dip Switch 8-1 setting complies with local Fire, Building and Life
Safety Codes. All installations must be approved by the local Authority Having Jurisdiction (AHJ).
2. This product and all related accessories or parts must be inspected and maintained on a quarterly basis.
3. Contacting surfaces of the electromagnetic lock and armature plate must be kept free of contaminating materials.
Surfaces must be cleaned periodically with a non-abrasive cleaner.
4. All mounting fasteners must be inspected on a quarterly basis. When properly installed, the ends of the armature
plate allow a slight movement, but the plate will feel secure when grasped at the bolt. There should be no movement
to the mounting bracket or housing of the electromagnetic lock. For added safety, thread locking compound should
be applied for the armature plate bolt and the four captive electromagnetic lock mounting screws to reduce chance of
screws loosening over extended time.
5. The door frame must be inspected and deemed structurally sound for the installation of the electromagnetic lock.
The structural integrity of the mounting surfaces must be strong enough to meet or exceed the holding force of the
product.
6. The lock must be protected from potential damage due to intruders or tampering. Wire the built-in tamper switch to an
annunciator device to be alerted when the cover is removed by someone tampering with the lock.
7. The components, hardware, installation instructions and mounting template included are intended for use on out
swinging doors.
8. Do not install this product on the exterior of buildings.
9. Check the door starts countdown when continuously pressed to exit. Adjust both the proxy sensor and proxy trigger to
ensure the countdown is triggered when the door is pressed to open.
a. To increase the height of the proxy sensor from the front cover surface, turn the proxy holder clockwise.
b. To decrease the height of the proxy sensor from the front cover surface, turn the proxy holder
counterclockwise increasing the gap between the sensor and the proxy trigger.
c. Using the M5 Allen key, screw in or out the proxy trigger that is spring loaded to increase or decrease the gap.
Note: The proxy sensor and the proxy trigger does not need to touch to operate correctly.
10. Separate mounting accessories not included with this product must be used in the following applications:
a. Narrow head jamb situations or center-hung doors.
b. Wherever there is insucient space on the door frame header to mount the lock
c. Hollow metal or wood frames where the doorstop is not thick enough to allow the product to be installed
d. Wherever an obstruction in the door prevents installation of the armature plate at a proper height
e. Doors that do not permit the armature plate to be mounted low enough to meet the magnet surface.
11. A mechanical latching device is recommended in conjunction with the Delayed Egress lock.
12. Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem,
please call Camden. If you must wait for the following workday to call for assistance, leave the door inoperable until
satisfactory repairs can be made. Never sacrice the safe operation of the automatic maglock for an incomplete
solution.
WARNING: Improper installation, maintenance, inspection or usage of the product or any related accessories or parts may
cause the electromagnetic lock, armature plate and associated hardware to disengage and fall, causing serious bodily injury and
property damage.
The re marshal will ne you for it during an inspection.
Call: 1.877.226.3369 / 905.366.3377
Visit: www.camdencontrols.com
Opening New Doors to
Innovation, Quality and Support!
Page 2 of 2
Delayed Egress Lock Maintenance Manual
INSTALLATION INSTRUCTIONS
File: Delayed_Egress_Maintenance_
Manual.indd
Revision: Sept 27th 2021
Part No.: 40-82B292
TROUBLESHOOTING
Problem Solution
Lock has no holding force Check the power supply. Voltage should be 12 to 24 VDC +/- 10%.
Check wiring of power supply and releasing devices.
Lock will hold a screwdriver or set of metal pliers,
but the door will not lock.
Check to ensure the armature plate is correctly aligned to the maglock. Follow the armature
plate mounting instructions on the template and the installation manual 40- 82B236
Lock is operating and locking but it hums against
the armature plate.
Check that the power supply is ltered DC. The humming is caused by AC on the DC supply.
A proper ltered and regulated DC power supply will resolve the issue.
There is a latency of the lock not releasing after
power is removed.
Refer to Figure A and check the placement of any suppression devices. Residual magnetism
is related to the presence of electricity (i.e., capacitance) in the lock circuit. Degaussing or
dimpling the lock are not advised since it will cause unintended consequences.
MAINTENANCE SCHEDULE
Company Name: _________________________________________________________
DCPowerSupply
(filtered&regulated)
Switch Maglock
+
‐
DCPowerSupply
(filtered&regulated)
Switch
Maglock
+
‐
Recommended
placementofswitchto
ensureinstantrelease.
PlacingtheRTEswitch
(pushplateorPIR)onthe
wronglegmaycausethe
bondtocollapsemore
slowlythanexpected.
Ensuretheswitch
interruptsthepositive
wireandnotthenegative
wire.
Maglock
+
‐
MOV
Maglock
+
‐
Neverconnecta
parallelreversediode
asshown.
Door Location Date Notes Initial

Other manuals for CX-DE1200

1

This manual suits for next models

14

Other CAMDEN Lock manuals

CAMDEN CX-EPD 2850L User manual

CAMDEN

CAMDEN CX-EPD 2850L User manual

CAMDEN CX-92S TDS Series User manual

CAMDEN

CAMDEN CX-92S TDS Series User manual

Popular Lock manuals by other brands

Secu SELO-B operating instructions

Secu

Secu SELO-B operating instructions

Zap ACC300 quick start guide

Zap

Zap ACC300 quick start guide

Allegion FALCON X571 Special instructions

Allegion

Allegion FALCON X571 Special instructions

Falcon T351 Installation instructions manual

Falcon

Falcon T351 Installation instructions manual

SSS Siedle COM 611-02 Product information

SSS Siedle

SSS Siedle COM 611-02 Product information

Alarm Lock Trilogy PDL Series quick start guide

Alarm Lock

Alarm Lock Trilogy PDL Series quick start guide

Alarm Lock Trilogy Networx Double-Sided PDL6300 installation instructions

Alarm Lock

Alarm Lock Trilogy Networx Double-Sided PDL6300 installation instructions

Davcor Smartlock Digital 4300 MASTER SETUP AND OPERATIONAL INSTRUCTIONS

Davcor

Davcor Smartlock Digital 4300 MASTER SETUP AND OPERATIONAL INSTRUCTIONS

Invixium VERTU quick start guide

Invixium

Invixium VERTU quick start guide

ABS ABS-Lock T-Quick manual

ABS

ABS ABS-Lock T-Quick manual

Martindale Electric LOK6 Series instruction manual

Martindale Electric

Martindale Electric LOK6 Series instruction manual

ADAMS RITE RITE Touch user guide

ADAMS RITE

ADAMS RITE RITE Touch user guide

DORMA-Glas STUDIO RONDO quick start guide

DORMA-Glas

DORMA-Glas STUDIO RONDO quick start guide

Lockwood Nexion Classic user manual

Lockwood

Lockwood Nexion Classic user manual

Arregui SLIM LOCK CE CE1500P manual

Arregui

Arregui SLIM LOCK CE CE1500P manual

Assa Abloy Sargent KP Series Installation & programming instructions

Assa Abloy

Assa Abloy Sargent KP Series Installation & programming instructions

Burg B-Smart-Lock MASTER Installing instructions

Burg

Burg B-Smart-Lock MASTER Installing instructions

Videosec Cl-19 user manual

Videosec

Videosec Cl-19 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.