(Figure 7 - Response from SMART Link-485)
The fields of the string in Figure 7 are as follows:
"S" - start of the sample/string/response.
"MDTC-M0618-01" - the serial number of the extensometer connected to the SMART Link-485.
"IDE" - indicates the location where the information about the MPBX was read from. The "E" indicates the
SMART ID is external to the Link-485, this is usually the case when using SMART Link-485.
If this had been "IDI", the "I" standing for "internal" would indicate that the information about the
MPBX was read from within the Link-485 (an extra SMART ID is added inside the Link-485). This
would be the case when the Link-485 is paired/bonded to a specific legacy instrument that does not
have a SMART ID memory chip built in. The Link-485 would have the serial number of the MPBX
penciled in on the label under the "Paired SMART Instrument SN".
"23.5" - temperature in Celsius
"645" - this is a legacy value for Voltage that MDT has kept for backwards compatibility issues. This value
divided by 56 gives you volts DC. In the example 645/56 =11.5Vdc.
"M" - precedes the first reading (position) and indicates Metric units.
Three values following “M” - first value is the initial value, the second value is the current reading (this
is the value that will be reported in MultiLogger) and the third value is the delta. There are as many of
these 3 value entries as there are sensors on the SMART Link-485 (in the example there are six).
"AAM" - echo of the port, channel and unit command issued: All ports, All channels, Metric units.
MultiLogger Configuration
Typically, the Direct Connect Channel configuration would be used for configuring the SMART Link-485.
However, since the number of Direct Connect Channels in a Campbell CR6 Datalogger are limited to 12 and
each position requires a channel; if the system must read more than 2 MPBXs with 6 positions each, there
would be insufficient channels. In this case, use a Multiplexer configuration, the following section details this
configuration.
Note - A gage type has been added to support reading the MDT SMART Link-485. Contact Canary Systems
if your
installation of software does not list the required gage types.
Direct Connect Channel Configuration
Add a Campbell CR6 MCU to the network, double-click to load the Logger form. Then, select the Direct
Connect option on the Program tab, as shown in Figure 8.
(Figure 8 - Program tab of the MultiLogger
program configuration outlining the Direct Connect option)