caprari CapDRIVE Technical manual

CapDRIVE
CODE N°
:
996772/G
EDITION: 05/14
USE AND INSTALLATION HANDBOOK

2
Index
1. CapDRIVE Introduction ………………………………………………………..……………………………………………………….…………3
2. Safety Instructions ..…………………………………………………………….……………………………………………………….………… 3
3. Technical Characteristics …………………………………………………………………………………………….………………..……….. 4
3.1 Weight and dimensions …..…………………………………………………………………………………………………………………….. 4
4. Electric wiring …………………………………………………………………………………………………………………….…………………. 5
4.1 Protections ………………………………………………………………………………………………………...……………………………….… 9
4.2 Electromagnetic compliance ……………………………………………………………………………………………………………..…… 9
4.3 Installation with long motor cables …………………………………………………………………………………………….……….... 9
5. CapDRIVE installation …………………………………………………………………………………………………………..………………. 10
5.1 CapDRIVE installation for Constant Pressure control……………………………………………….……………………….……. 12
5.1.1 Pressure tank ……….…………………..…………………………………………………………...………….…………………………....12
5.1.2 Pressure sensor ……………………………………………………………………………………………………………………….…..… 12
6. CapDRIVE Use and Programming ………….……….………………………………………………………………………………….…… 13
6.1 CapDRIVE display …………………………………………………………………………………….…………….…….…………………………13
6.2 Initial configuration ……………………………………………………………….………………………………………………………….…… 13
6.3 Initial view ………………………………………………………………………………………………………………………………………..…….15
6.4 Menù view .………………………………………………………………………………………..…………………………………………....…… 16
6.5 Installer parameters ……………………………………………………………………………………………………………………………… 16
6.6 Advanced parameters …………………………………………………………………………………………………………………………… 21
7. Protections and alarms …………………………………………………………………………………………………………………..….…. 23
8. Auxiliary pumps during constant pressure control…………………………………………………………….………………..… 25
8.1 DOL pumps ……………………………...…………………………………………………………………………………………………………… 26
8.2 COMBO function ………………………………………………………………………………………………………………………….….……. 27
9. Trouble-shooting chart ……………………………………….…………………………………………………………………………………. 29
Techinical assistence …………………………………………..…………………………..………………………………….……………………………. 30

3
1. CapDRIVE Introduction
CapDRIVE is a variable frequency drive designed to control and protect pumping systems by varying the outputfrequency
to the pump.
CapDRIVE can be applied to both new and existing pumping systems, and provides:
energy and cost savings
simplified installation and an overall lower pumping system cost
longer life of the pumping system and relevant components
improved reliability
CapDRIVE, when connected to any pump, manages the system operation to maintain a certain constantphysical quantity
(pressure, differentialpressure, flow, temperature, etc.) regardless of theconditions of use. Thepump is operated onlywhen
needed thus avoiding unnecessary energy consumption.
CapDRIVE at the same time is able to:
protect the motor from overload and dry running
implementsoft start and soft stop toincrease the systemlife andreduce currentpeaks
provide an indication of current consumption, voltage, and power
maintain a record of run time and display any errors and/or failures reported by the system
control up to two additional pumps at a constant speed (Direct On Line)
connect to other CapDRIVE units for combined operation
Through the use of inductive filters (optional) CapDRIVE eliminates dangerous surges that are inducedin longcables,
making CapDRIVE suitable for control of submersible pumps.
2. Safety Instructions
CAPRARI strongly suggests carefully reading this operation manual before using and installing its products
Any operation (installation, maintenance and repair) must be carried out by trained, skilled, and qualified personnel.
Failure to observe and follow the instructions in this manual may result in dangerousand potentially lethal electric shock.
Pay attention to all standard safety and accident prevention regulations.
The device must be connected to main power supply via a switch to ensure the
complete disconnection from the network before any operation on the CapDRIVE itself
(including visual inspection) and/or on the connected load.
Disconnect CapDRIVE from the main power supply before commencing any work.
Do not remove, for any reason, the cover and the cable plate without having first
disconnected the device from the main power supply and having waited at least 5
minutes.
CapDRIVE and pumping system must be grounded properly before operation.
For the entire period CapDRIVE is powered, high voltage is present on the output
terminals of the inverter whether or not the pump is running.
Tightening all 4 screws on the cover with washers is recommended before powering
the device. Otherwise, there may be a failure to connect the cover to ground, creating
the risk of electric shock or even death.
Avoid any shock or significant impact during transport.
Check the CapDRIVE immediately upon delivery and check for damage and/or missing parts. If either occurs, immediately
notify the supplier.
Damages due to transport, incorrect installation, or improper use of the device will null and void the warranty.
Tampering or disassembly of any component will automatically void the warranty.
CAPRARI cannot be held responsible for any damages to people and/or property due to improper use of itsproducts.

4
210
3. Technical Characteristics
model Vin +/- 15% max Vout
Max line
current
Max
motor
current
Typical P2 motor
[V] AC [V] [A] [A] [KW] [HP]
CapDRIVE 011
1 x 230 1 x Vin 15 9 1,1 1.5
3 x Vin 15 7 1,1 1.5
CapDRIVE 030
1 x 230 1 x Vin 20 10 1,5 2
3 x Vin 20 11 3 4
CapDRIVE 022
3 x 380 - 460 3 x Vin 10 62.2 3
CapDRIVE 040 3 x 380 - 460 3 x Vin 13,5 945,5
CapDRIVE 055
3 x 380 - 460 3 x Vin 16 14 5,5 7,5
CapDRIVE 075
3 x 380 - 460 3 x Vin 21 18 7,5 10
CapDRIVE 110
3 x 380 - 460 3 x Vin 31 25 11 15
CapDRIVE 150
3 x 380 - 460 3 x Vin 35 30 15 20
Power frequency:48 - 62 Hz
Max. ambient temperature at nominal current: 40°C (104 °F)
Max. altitude at nominal current: 1000 m
Grade of protection:IP55 (NEMA 4) *
4 Settable digital output signals (N.O or N.C)
4 Analog Input
4 Settable digital input signals (N.O or N.C)
PWM configurable: 2.5, 4, 6, 8, 10 kHz
RS485 serial communication
* auxiliary cooling fan of the CapDRIVE, used in wall mounted applications, has a protection rating of IP54.
CapDRIVE is able to power the motor with a higher current for a short period of time according to the linear relation:
101% of the nominal current for 10min., 110% nominal current for 1 min.
3.1 Weight and dimensions
* Weight without auxiliary cooling fans and
without packing.
model Weight *
[Kg]
CapDRIVE
011 4
CapDRIVE
030 4,3
Cap
DRIVE
022
4,4
Cap
DRIVE
040
4,4
CapDRIVE
055
7,3
CapDRIVE
075
7,5
CapDRIVE
110
7,7
Cap
DRIVE
150 7,9
Cap
DRIVE
011,030,022,040
Cap
DRIVE
055,075,110,150

5
4. Electric wiring
Power boardCapDRIVE 011, 030
Power supply:
LINE: L1, L2, earth
It is recommended to use cable
lugs
Output:
3 ph motor: earth,U ,V ,W
1 ph motor: earth, U
(running), V (common)
It is recommended to use cable
lugs.
230 V AC auxiliary fans (wall
mounting kit)
FAN: F1, F2
Cable stripping recommended for line
input and output to the motor.
Control board
power board

6
Power boardCapDRIVE 022, 040
Power supply:
LINE: GND , L1, L2, L3,
It is recommended to use cable
lugs.
Motor output:
MOTOR: U, V, W, GND
It is recommended to use cable
lugs.
12 V dc auxiliary fan (wall mounting
kit) :
0VE, + VE
WARNING: respect the polarity.
Cable stripping recommended for line
input and output to the motor.
Control board
power board
50

7
Power boardCapDRIVE 055, 075, 110, 150
Power supply:
LINE: L1, L2, L3, GND
It is recommended to use cable
lugs.
Motor output:
MOTOR: U, V, W, GND
It is recommended to use cable
lugs.
12 V dc auxiliary fan (wall mounting
kit) :
VENT: +, -
WARNING: respect the polarity.
Cable stripping recommended for line input and output to the motor.
Control board
power board

8
Control board
Analog inputs (10 or 15 Vdc
):
AN1: 4-20 mA: sensor 1
AN2: 4-20 mA: sensor 2
AN3: 4-20 mA / 0 - 10 Vdc (settable
by jumper C.C.): external set
AN4: 4-20 mA / 0 - 10 Vdc (settable
by C.C.): trimmer for frequency
regulation / external set 2
Digital outputs:
motor run signal:
oNO1, COM1: closed contact with
motor running.
oNC1,COM1: closed contact with
motor stopped.
alarm signal
oNO2,COM2: opened contact
without alarm.
oNC2,COM2: closed contact without
alarm.
DOL1 pump relay:
oNO3,COM3: closed contact with
DOL1 running.
oNC3,COM3: opened contact with
DOL1 running.
DOL2 pump relay:
oNO4,COM4: closed contact with
DOL2 running.
oNC4,COM4: opened contact with
DOL2 running.
Relays are no voltage contacts. Max. voltage to
the contacts is 250 V with max current of 5 A.
RS485:
S+
S-
G
It is recommended to
respect the polarity
linking more CapDRIVE in
series.
Digital inputs:
IN1 : motor start & stop
IN2: value set 1 & 2 switching
IN3: sensor 1 & 2 switching
IN4 : motor start & stop + alarms
reset
0V
We recommend using only no
voltage contacts.
Opening or closing the digital
contacts (depending on software
configuration set (see inst.
parameters) you

9
4.1 Protections
The protections required upstream each CapDRIVEsdepends on the type of installation, and local regulations. We
recommend to use overload protection with the characteristic curve of type C and type B circuit breaker, sensitive to both AC
and DC current.
4.2 Electromagnetic compliance
To ensure electromagnetic compatibility (EMC) of the system, it is necessary to apply the following measures:
Always connect the device to ground
Use shielded signal cables by placing the screen at one end.
Use motor cable as short as possible (<1 m / <3 ft). For longer lengths, it is recommended to use shielded cables
connecting the screen at both ends.
Separate signal, motor,and power supply cables.
Note: To enable the restoration of the display screen when there are electromagnetic interference, CapDRIVE
periodically provides some fast "refresh" of the display.
4.3 Installation with long motor cables
With long motor cables it’s recommended to decrease the
commutation frequency from 10 kHz (default) to 2.5 kHz
(advanced parameters). This reduces the probability of
voltage spikes in the motor windings whichmay damage the
insulation.
To prevent dangerous overheating of dv/ dt andsinusoidal
filters it is recommended to set the correct PWM value in
relation to the cable length.
For motor cable lengths up to 50 metersit’s recommended
to place between CapDRIVE andmotor a dv / dt
reactance, available on request.
For motor cable lengths greater than 50meters it’s
recommended to place between CapDRIVE and motor a
sinusoidal filter, available on request.

10
5. CapDRIVE installation
CapDRIVE can be installed directly on the fan cover of the motor or mounted on the wall.
Motor mounting kit
In this application CapDRIVE is cooled by the motor fan. Motor kit (available upon request) allows a solid coupling of the two
units and it is composed of:
CapDRIVE 011,
030,
022,
040
n.°4 rods
n.°4 M5 nuts
Qty 4 x spring washer
n.° 4 hooks
n.° 1 cooling ring
CapDRIVE 0
55
, 0
75
,
110, 150
n.° 4 M5 screws.
n.° 4 clamps
n.° 4 clips to add if necessary
N.°1 centre pin
Use the cooling ring for best cooling of CapDRIVE during
operation. Warning: when using the cooling ring, the cooling
air of the motor is slightly warmer than without the
CapDRIVE; if the resulting motor temperature exceeds the
indicated maximum allowable value, remove the cooling
ring, leaving the CapDRIVE to be cooled by itself.

11
Wall mounting kit
In this application CapDRIVE is cooled independently by its auxiliary cooling fanintegrated in the radiator.
Wall-mounted kit is composed of:
CapDRIVE 011, 030,
022,
040
n.° 1 auxiliary fan 230V AC (CapDRIVE 011,030) or
12 VDC (CapDRIVE 022, 040)
n.° 4 screws to fix cooling fan
n.° 1 protection grill
n.° 1 metal bracket in AISI 304
n.° 4 screws to fix CapDRIVE to wall bracket
CapDRIVE 0
55
, 0
75
,
110
n.° 2 12 V DC fans.
n.° 1 fanscover.
n.° 2 fanscover fixing screws
n.° 2 wall fixing brackets
n.° 4 M5 screwsfor CapDRIVE fixing to the brackets
n.°1 holesreference sheet
Make sure the manufacturer that the electric motor is suited for operation in the inverter.
Make sure to properly attach the grid of the auxiliary cooling fan.
Make sure to remove the auxiliary cooling fan if CapDRIVEis coupled to a motor. Failure to do so
creates a high risk ofoverheating the motor and CapDRIVE unit.

12
5.1 CapDRIVE Installation for constant pressure control
CapDRIVE controls the pump speed tomaintain constantpressure at a set point independent of the water demandin the
system.
A basic schematic is shown below:
5.1.1 Pressure tank
Installation of a pressure tank in the hydraulic system is recommended to compensate leakage of water in the system (or
during minimum water demand) and to avoid continuousstart/stop cycling of the pump (check the appendix for more
information). Selecting the proper volume and pre-charge pressure of the tank is very important; smaller tank volumeswill
not compensate adequately for minimum water usage or leakage, while larger volumes make it more difficult for CapDRIVE
to control the pressure evenly.
Recommended tank volume is equalto the 10% of the maximum water flow of thesystem (expressed in volume unit/min)
Example: if the max water flow is 50 liters/min, the pressure tank should have a capacity of 5 liters
If the max water flow is 20 gpm, the pressure tank should have a capacity of 2 gallons
Pre-charge pressure of the pressure tank should be at least 80% than the set-pressure of thesystem.
Example: if the set-pressure of the system is 4 bar, the pre-charge pressure of the tank should be 3.2 bar
If the set-pressure of the system is 60 psi, the pre-charge pressure of the tank should be 48 psi
5.1.2 Pressure sensor
CapDRIVE requires a pressure sensor with a linear output signal within the range 4 – 20mA. The pressure transducer can
be powered by any range of DC Voltage which includes the value 15 V dc.
CapDRIVE accepts the signal of a second pressure sensor in order to:
realize constant differential pressure (AN1 – AN2).
substitute first pressure sensor when it fails
switch pressure sensor by closing digital input IN2
SENSOR 1 AN1: 4-20 mA (-) signal
+15V: 15 Vdc (+) power supply
SENSOR 2 AN2: 4-20 mA (-) signal
+15V: 15 Vdc (+) power supply
Cap
DRIVE
1
2
3
5
4
1: pump
2: checkvalve
3: pressure tank
4: valve
5: valve
6: pressure sensor
6

13
6. CapDRIVE Use and Programming
CapDRIVE software is extremely simple to use, but allowsa wide variety of parameters to be set for ideal system
calibration. Setting Parameters are organized in 2 levels:
1: Installer level
A password is required for this level; these parameters are adjustable by trained professionals
Default password: 001
From the menu a different password can be set up.
2. Advanced level
A second and different password is required; improper setting of these advanced parameters could compromise the
integrity and the life of CapDRIVE and pump;
Default password 002
It is possible to set up a different password.
Installer and Advanced levelscan be entered only with the correct password; otherwise, it is impossible to set up
and/or modify anyparameters (they can beonly displayed).
6.1 CapDRIVE display
Screen is a back-lit LCD displaying 2 rows of 16 digits each. Alarms are indicated by an audible signal.
6.2 Initial configuration
When CapDRIVE isswitched on forthe first time, theinitial setting menuis displayed for the initialsettingofparameters to
configure pump characteristics, pressure sensor range, and system characteristics.
If the initial setting procedure is not completed properly, it is impossible to run the pump. Initial setting procedure can be
repeated if necessary.
The initial setting procedure can be repeated (by using the 2rd level password) to reconfigure CapDRIVE or if CapDRIVE is
installed in a different system.
A brief description of parameters and their allowable ranges are listed below:
STOP motor
Menu exit
Alarms reset
START motor
ENTER
Scroll up
Scroll down

14
Parameter
Default
Description
Language
XXXXXX XXXX
End user com
munication language
Unit
XXXX bar
Unit
Motor type
singlephase/threephase threephase
Type of motor connected (Cap
DRIVE
011,030)
Rated motor Amp.
I = XX.X [A] XX
Rated current of the motor per it’s nameplate indication increased by
10%. The voltage drop caused by the inverter leads to higher input
current than nominal. Make sure motor is capable of accepting
increased current.
Rated motor freq
f = XXX [Hz] 50
Rated frequency of the motor per its nameplate.
Control mode: Constant value [bar]
F.s. press.sensor
p = XX.X [bar] 16
Sensor full scale.
Sensor test
Press ENT
If the transducer is not connected or connected improperly, the signal
SENSOR OFF is activated when pressing ENTER.
Max alarm value
p = XX.X [bar] 10
Maximum pressure all
owed in the system. If the pressure goes over
this value, an alarm occurs and the pump is stopped. Pump is
automatically restarted if the pressure goes below the maximum
value for a period of at least 5 seconds.
Motor test
START/STOP
Press START/STOP t
o run a test at rated frequency
Warning: make sure to run the system without damaging pump and
system
Rotation sense
---> / <--- --->
If, during the test, the motor runs in reverse,it is possible to change
the wiring sequence via software without physically changing wires at
the terminals.
Set value
p = XX.X [bar] 3
The value to be keptconstant
.
Autorestart
ON/OFF OFF
If ON is selected, after a lack of voltage,
CapDRIVE
returns to its
normal status; if CapDRIVE was powering the pump before the
voltage drop, it resumes powering the pump automatically.
Warning, review the advice in chapter 1
INITIAL SETUP
COMPLETED
Once the Setting procedure is completed you will get this indication
on the display; setting parameters are recorded by CapDRIVE; these
parameters can be set up individually in the INSTALLER Parameters
menu or ADVANCED Parameters menu.

15
6.3 Initial view
When first powering the CapDRIVE,the display shows : release of display software (LCD = X.XX) and the release of inverter
software (INV = X.XX) as shown below:
The following End User messages are displayed by pushing the scroll buttons:
Inv: ON/OFF Mot: ON/OFF
p=XX.X [bar]
p is the pressure value read by the pressure transducer.
By pressing ENTER the pressure set value is displayed <XXX.X>
Inv: ON/OFF Mot: ON/OFF
f = XXX.X [Hz]
f valueis the supplyfrequency tothe motor;On fixfrequency controlmode, by
pressing ENTER you can change the f value manually (word “set” is displayed) , press
ENTER again to exit parameter setting (word “set” disappeared).
Inv: ON/OFF Mot: ON/OFF
V_in=XXX [V] / I=XX.X [A]
V is the voltage supplied to the motor. This value is displayed only if motor is OFF; if
motor is ON, A value equal to the absorbed motor current is displayed
Inv: ON/OFF Mot: ON/OFF
cosphi = X.XX
cosphi indexmeans the angle phi between the voltage and current absorbed by the
motor
Inv: ON/OFF Mot: ON/OFF
P = XXXXX [W]
P is the power in Watts supplied to the pump
.
NORMAL status means no alarms.
If an alarm occurs, a messageblinks on the displayand an audible signal isactivated.
Pressing ENTER accesses: CapDRIVE lifetime, PUMP lifetime, consumption statistic,
alarm list.
To return to previous views, press ENTER.
Menù
ENT to access
To return to previous views, press ENTER.
First row gives the CapDRIVE status:
Inv: ON XXX.X Hz CapDRIVE is powered and is powering the motor showing its frequency.
Inv: ON Mot: OFF CapDRIVE is powered but motor is not running (i.e. motor/pump was stopped due to minimum
frequency being reached)
Inv: OFF Mot: OFF CapDRIVE is not powered
If COMBO function is activated, the CapDRIVE address is placed close to indication “Inv”.
XXXXXXXXXXXXXXX
XXXXXXX h : XX m
Motor Life
xxxxx h : xx m
%f 25 50 75 100
%h XX XX XX XX
LCD = X.XX
INV = X.XX
Inv: ON/OFF Mot: ON/OFF
STATUS:NORMAL
Inverter Life
xxxxx h : xx m

16
6.4 Menu view
Pressing ENTER when you are in [MENU’ / ENT to access] in initial display, will display the following MENUs:
MENU’
Install. param
Installer password required to enter l
evel 1 (default 001)
MENU’
Advanced. param.
Advanced password required to enter level 2 (default 002)
MENU’
Retrive init.set
Installer password required to enter level 1 (default 001)
It is possible to return to original set parameters.
MENU’
Change init.set.
Advanced password required
to enter level 2 (default 002)
To exit the Menu level and return to initial display, press STOP button.
6.5 Installer parameters
Many of the Installer parameters are set during the Initial Configuration (chapter 6.2 Initial Configuration).
However, through the Installer Parameters menu, itis possible to change the set parameters or set others in order to perfect
the calibration of CapDRIVE to the pumping system.
parameter
default
desciption
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
Control mode
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
Constantvalue
Mode of control:
Constant value: CapDRIVE changes the speed of pump tokeep theset value
constant, independent of water demand.
Fix speed:CapDRIVE feeds the pump a set frequency, so the speed of
motor is kept constant.
Const. value 2 set: the two values are selected by opening or closing the
digital input IN2.
Fix speed 2 val: to be selected by opening or closing the digital input IN2.
External speed:control motor frequency by using analogical input AN4.

17
parameter
default
desciption
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
Unit
XXX
bar
Unit
F.scale sensor
p = XX.X [bar] 16
Sensor full scale
Min value sensor
p = XX.X [bar] 0
Sensor minimum value.
Max alarm value
p = XX.X [bar] 10
Maximum value allowed in the system. If the readen
value goes over this value, an alarm occurs and the pump
is stopped. Pump is automatically restarted if the readen
value goes below the maximum value for a period of at
least 5seconds.
Min alarm value
p = XX.X [bar] 0
Minimum value allowed in the system. If the readen value
goes lower than this value, an alarm occurs and the pump
is stopped. Pumpis automatically restartedif the readen
value goes higher than theminimum value for a period of
at least 5 seconds.
Ext.set enabling
ON/OFF OFF
Enabling of set value changing by analog input AN3.
Set value
p = XX.X [bar] 3
The set value to be kept constant
.
Compensation
p = XX.X [bar] 0
Value compensation at the maximum frequency for each
pump. Acting on the green button you can reverse the
sign.
Set value 2
p = XX.X [bar] 3
The set value to be kept constant.
Compensation 2
p = XX.X [bar] 0
Value compensation at the maximum frequency for each
pump. Acting on the green button you can reverse the
sign.
Set value update
t= XX.X [s] 5
Time to update set value for compensation.

18
parameter
default
desciption
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
To ensure proper operation of pressure control is recommended to place the sensor near the pump.
To compensate the pressure loss in the pipes (proportional to flow) it is possible to vary the pressure set in a linear
relation with respect to frequency.
It can perform the following test to verify the correct value of compensation:
1. install a pressure gauge away from the pressure sensor
2. open completely the valve
3. check the pressure gauge
--> Set the value of compensation. equal to the difference of the values from the two gauges.
When using a group of pumps, the pressure compensation to be applied to each pump is equal to the total pressure
compensation (when all the pumps are running at full speed) divided by the number of pumps in the group.
Operating freq.
f = XXX [Hz] 50
Set the frequency value (or the speed) to feed the pump.
Operating freq. 2
f = XXX [Hz] 50
Set the frequency value (or the speed) to feed the pump.
Freq. min. control
fmin = XXX [Hz] 50
Minimum frequency below which the pump tries
to stop.
Stop delay
t = XX [s] 5
Delay for which the pump tries to stop below freq.min.
control.
Control Ramp
t = XX [s] 20
Ramp time from freq.min.controlto min.motor freq. If,
during this time, the readen value goes below the (set
value - delta control), CapDRIVE powers the motor again;
otherwise, CapDRIVE will stop the pump.

19
parameter
default
desciption
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
Delta Control
p = XX.X [bar] 0.1
This value represents the value drop below the set value
required to restart the pump during control ramp.
Delta start
p = XX.X [bar] 0.5
This value represents the value drop below the set value
required to start the pump from stop condition.
Delta stop
p = XX.X [bar] 0.5
It's the value increase respect to set value which must be
passed so that there is a forced shutdown of the pump.
Kp and Ki parameters allow the dynamic control of system
by CapDRIVE; set values (Ki=50, Kp=005) are usually
enough to get a valid dynamic control
Pump DOL 1
ON/OFF OFF
Function to activate (ON) the first auxiliary pump DOL 1
(Direct On Line pump).
Pump DOL 2
ON/OFF OFF
Function to activate (ON) the second auxiliary pump DOL
2 (Direct On Line pump).
Alternance
ON/OFF OFF
Function to allow alternating starting priority between the
DOL pumps in order to allow equal use of them.
Ki
XXX
Kp
XXX

20
parameter
default
desciption
Constant value
Fix speed
Const.value 2 set
Fix speed 2 val.
External speed
Start delay AUX
t = XX [s] 1
delay time with which the pumps DOL start after the
variable speed pump has reached the maximum
frequency and the readen value has fallen below set value
– delta control.
COMBO
ON/OFF OFF
Function to enable multiple Cap
DRIVE
’s to work in
parallel as described in the technical appendix (see the
relevant chapter). Up to 8 CapDRIVE unitscan be
connected in parallel.
CapDRIVE’s communication through RS 485 gates is
granted by a private protocol.
PI control
Direct/Reverse
Direct
Direct: increasing misured value, Cap
DRIVE
decreases
motor frequency.
Reverse: increasing misured value, CapDRIVE increase
motor frequency.
Rotation sense
---> / <--- --->
If, during the test, the motor runs in reverse,it is possible
to change the wiring sequence via software without
physically changing wires at the terminals.
Dry run cosphi
cosphi = X.XX 0.65
If the pump goes into dry-running, the cosphi reachesits
lowest level. To set this value, contact the pump
manufacturer or test by closing the suction and checking
the value on the CapDRIVE display;a value can be set by
assuming a dry cosphi equivalent to 60% of the rated
cosphi specified by the manufacturer.
Restarts delay
t = XX [min] 10
Restart delay after a dry running alarm. At each tentative
(max 5) restart delay will be doubled.
Digital input 1
N.O. / N.C. N.O.
By selecting N.A. (normally open)
CapDRIVE
runs the
motor if the digital input 1 is open; motor will be stopped
if the digital input 1is closed.
By selecting N.C. (normally closed) CapDRIVE runs the
motor if the digital input 1 is closed;motor will be
stopped if the digital input 1 is opened.
Digital input 2
N.O. / N.C. N.O.
By selecting N.A. (normally open)
CapDRIVE
runs the
motor if the digital input 2 is open; motor will be stopped
if the digital input 2is closed.
By selecting N.C. (normally closed) CapDRIVE runs the
motor if the digital input 2 is closed;motor will be
stopped if the digital input 2 is opened.
Digital input 3
N.O. / N.C. N.O.
By selecting N.A. (normally open)
CapDRIVE
runs the
motor if the digital input 3 is open; motor will be stopped
if the digital input 3is closed.
By selecting N.C. (normally closed) CapDRIVE runs the
motor if the digital input 3 isclosed; motor will be
stopped if the digital input 3is opened.
Digital input 4
N.O. / N.C. N.O.
By selecting N.A. (normally open)
CapDRIVE
runs the
motor if the digital input 4 is open; motor will be stopped
if the digital input 4is closed.
By selecting N.C. (normally closed) CapDRIVE runs the
motor if the digital input 4 isclosed; motor will be
stopped if the digital input 4is opened.
Table of contents
Popular Controllers manuals by other brands

Motrona
Motrona MM 640 operating instructions

Healthy wave
Healthy wave Multi-Wave PEMF Mat Controller operating instructions

Galil
Galil DMC-2X00 user manual

PIETRO FIORENTINI
PIETRO FIORENTINI REVAL 182 Use and maintenance instructions

IPCOMM
IPCOMM SEC3M General Operating, Maintenance, and Installation Manual

BRIDGEWERKS
BRIDGEWERKS Mag Mate user manual