Captron Electronic safeCAP SC30 User manual

safeCAP SC30
Operating Instructions
Original operating instructions
safeCAP SC30
Operating Instructions
Original operating instructions

Table of Contents
1 Foreword....................................................................................... 4
2 Safety.............................................................................................4
2.1 Notes and symbols used.......................................................... 4
2.2 General safety...........................................................................5
2.3 Personnel qualifications............................................................ 5
2.4 Intended use............................................................................. 6
2.5 Reasonably foreseeable misuse...............................................6
2.6 Determining the lifetime and validating the entire system.........7
2.7 Example calculation.................................................................. 7
3 General description..................................................................... 8
3.1 safeCAP SC30.......................................................................... 8
4 Storage.......................................................................................... 8
5 Assembly.......................................................................................8
5.1 Install safeCAP SC30............................................................... 9
5.2 Install protector SCP-6 (optional)............................................10
5.3 Install safety relay 3SK1 (optional)......................................... 10
5.4 Connect safeCAP SC30 to safety relay 3SK1........................ 10
5.5 Install safety relay MCR 225 (optional)...................................11
5.6 Connect safeCAP SC30 to safety relay MCR 225..................11
5.7 Install safety relay PNOZ s6 (optional)................................... 13
5.8 Connect safeCAP SC30 to safety relay PNOZ s6.................. 13
5.9 Connect safeCAP SC30 to an equivalent T-network.............. 14
5.10 Testing the safety function of the SC30.................................. 15
6 Operation.....................................................................................16
6.1 Operating safeCAP SC30.......................................................16
6.2 Operating safety relay SCR3-3SK1........................................ 16
7 Maintenance................................................................................16
7.1 Maintenance operations..........................................................16
2/25 1.1 safeCAP SC30
Original operating instructions

7.2 Testing the safety function of the SC30.................................. 17
7.3 Troubleshooting.......................................................................17
8 Disassembly................................................................................18
9 Disposal.......................................................................................18
10 Technical specifications............................................................ 18
10.1 Terminal assignment SC30..................................................... 18
10.2 Technical specifications SC30 one-channel............................19
10.3 Technical specifications SC30 two-channel............................ 19
10.4 Technical specifications, safety relay 3SK1............................ 20
10.5 Technical specifications, safety relay MCR-225......................21
10.6 Technical specifications, safety relay PNOZ s6...................... 22
11 Dimensional drawing SC30....................................................... 23
12 Manual updates.......................................................................... 24
13 Imprint......................................................................................... 25
safeCAP SC30
Original operating
instructions
1.1 3/25

1 Foreword
These operating instructions are intended for installers and operators and
should be kept for future reference. Read these operating instructions carefully
and make sure that you have fully understood the contents before installing or
working with the safeCAP SC30. The operator is responsible for validating the
entire safety system.
2 Safety
2.1 Notes and symbols used
Warning notes in relation to personal injury / material damage are formulated
according to the "SAFE” principle. This means they contain information on the
type and source of the hazard, potential consequences as well as how to avoid
and avert danger. The following hazard classifications apply in the safety notes:
DANGER
Danger designates a hazardous situation, which, if ignored, will lead to
death or serious injury. The symbol next to the warning indicates the type
and source of the danger.
WARNING
Warning designates a hazardous situation, which, if ignored, may lead to
death or serious injury. The symbol next to the warning indicates the type
and source of the danger.
CAUTION
Caution designates a hazardous situation, which, if ignored, may lead to
injury. The symbol next to the warning indicates the type and source of the
danger.
NOTICE
Notice designates a situation, which may cause material damages and
impair the product’s function if attention is not paid.
4/25 1.1 safeCAP SC30
Original operating instructions

TIP
Tip provides additional useful information about the handling of the product.
Symbol Meaning
4Avoiding and adverting danger in the warning note
►Instructions for action
All instructions to be followed within a procedure are always
listed in chronological order.
■List
2.2 General safety
All work on electrical systems or operating equipment may only be carried out
by a specially qualified electrician according to the applicable electrotechnical
regulations.
The safety of the system in which the SENSORswitch is integrated is the
responsibility of the operator.
WARNING
Dangerous machine movement
The functioning two-hand control only protects operators from dangerous
machine movements.
4Protect the machine danger zone against unauthorized access with
additional safety devices.
2.3 Personnel qualifications
A qualified electrician is a person with suitable technical training, expertise and
experience as well as knowledge of relevant standards, who can evaluate the
work assigned to them correspondingly and recognize potential risks.
The following general safety notes for working with electrical energy must be
observed:
safeCAP SC30
Original operating
instructions
1.1 5/25

WARNING
Improper work on electrical systems!
Electric shock can result in death or life-threatening injuries.
4Before working on electrical systems, disconnect them from their
voltage supply and secure them against being switched on again.
4Wear appropriate personal protective equipment (PPE).
4Defects that are ascertained, such as damaged or loose cables, must
be remedied immediately.
2.4 Intended use
Combined with the safety relay, safeCAP SC30 ensures safety-related release
and interruption of a safety circuit. safeCAP SC30 is used to protect people
from work machines with dangerous closing movements. safeCAP SC30 is
tested with the following safety relays: MCR 225, 3SK1, 3RK3 and PNOZ s6.
Connection of MCR 225, 3SK1 and PNOZ s6 is described as an example in
the instructions. The operator is responsible for safety-related release and
interruption of the safety circuit.
2.5 Reasonably foreseeable misuse
Any use other than as specified Chapter 2.4, "Intended use" or extending
beyond this is deemed to be improper.
The switch is not suitable for:
■use as a two-hand control without the aforementioned relay or in case
of use of an equivalent t-network, the independent calculation of the
performance level in accordance with ISO 13849-1:2015.
■use as a two-hand control without validation of the entire system.
■use with cables between SC30 and safety relay with a length exceeding
30 m.
■use as a two-hand control in combination with another switch.
■use as an emergency stop command device.
■use in potentially explosive atmospheres.
■use outdoors.
6/25 1.1 safeCAP SC30
Original operating instructions

2.6 Determining the lifetime and validating the
entire system
The following steps are mandatory.
■Determine the real parameters of the system.
4Required performance level
4dop
4hop
4tcycle
■The operator must verify that the lifetime TM is not exceeded.
■Validate the entire system.
■Observe the safety considerations in the operating instructions of the safety
relay.
2.7 Example calculation
The following values are only examples and must be replaced with your own
values.
■Performance level e must be achieved.
■dop = 250 d
■hop = 24 h
■tcycle = 10 s
nop [cycles / year]
nop = (dop * hop *3600 s) / tcycle
nop = 250 d / y * 24 h / d * 3600 s / h / 10 s / cycle = 2,160,000 cycles / year
According to the operating instructions, the relay has a lifetime of approximately
20 million cycles before a dangerous failure can occur.
TM = 20,000,000 / nop
TM = 20,000,000 / 2,160,000 = 9.3 years
According to this calculation, the relay has to be replaced after 9.3 years.
For other relays, values such as B10D or T10D can be specified. These values are
not considered here and can be requested from CAPTRON.
safeCAP SC30
Original operating
instructions
1.1 7/25

3 General description
3.1 safeCAP SC30
safeCAP SC30 is equipped with two LEDs.
The green LED (1) lights up when it is ready for
operation. The yellow LED (2) lights up when
actuated.
4 Storage
Conditions
safeCAP SC30 -30°C (-22°F) to 80°C (176°F)
Safety relay SCR3-3SK1 -40°C (-40°F) to 80°C (176°F)
Protector SCP-6 Protected against UV light for max. two
years 20°C (68°F)
50% -70% relative air humidity
5 Assembly
WARNING
Improper work on electrical systems!
Electric shock can result in death or life-threatening injuries.
4Before working on electrical systems, disconnect them from their
voltage supply and secure them against being switched on again.
4Work on electrical installations should be carried out only by qualified
personnel in compliance with local and national electrical regulations
and specifications.
8/25 1.1 safeCAP SC30
Original operating instructions

WARNING
Improper safeCAP SC30 assembly!
An improperly assembled or non-functional two-hand control device can
result in death or life-threatening injuries.
4Select mounting surfaces for the safeCAP SC30 based on the
dimensions and spacing specified in DIN EN ISO 1385:2019.
4Protect safeCAP SC30 against unintended actuation, for example
SCP-6.
4Before working on the machine, check safeCAP SC30 for proper
function.
The safety distance between the machine and the two-hand control is
calculated based on the following formula.
S = K (t1 + t2) + C
■(S) Safety distance
■(K) Expected approach velocity of the human body or body parts. In
accordance with EN ISO 13855:2010
4Walking speed 1600 mm/s
4Grasping speed 2000 mm/s
■(t1) Time the safety equipment needs to respond.
■(t2) Time the machine needs after receiving the safety equipment signal
until the machine stops.
■(C) Additional horizontal distance from the danger zone in mm in
accordance with EN ISO 13855:2010
5.1 Install safeCAP SC30
► Disconnect the system from its voltage supply
and secure it against being switched on again.
► Clean the area below the switch.
► Unscrew the lock nuts (1) on the switch.
► Insert the switch into the prepared Ø 22.5 m
hole and screw the lock nuts back on.
► Align safeCAP SC30 and tighten the lock
nuts.
Wiring outside of enclosed installation spaces
must be protected against mechanical
safeCAP SC30
Original operating
instructions
1.1 9/25

damage (including vibration or bending, for
example).
5.2 Install protector SCP-6 (optional)
► Clean the area above the switch. The bonding
surface must be free of dust, grease, oil,
silicone and separating agents.
► Remove the film on the adhesive strip from
the back of the protector and position it above
safeCAP SC30.
► Press down firmly on the entire surface of the
protector.
5.3 Install safety relay 3SK1 (optional)
TIP
More detailed information can be found in the supplier documentation.
5.4 Connect safeCAP SC30 to safety relay 3SK1
The lines between safeCAP SC30 and the safety
relay must be laid separately of other signal paths
or live lines.
► Disconnect the system from its voltage supply.
► Set the DIP switch (2). The position of the DIP
switch is indicated in the circuit diagram.
► Connect safeCAP SC30 to the safety relay
using a 4-pin M 12 cable according to the
circuit diagram. The optional cables LKW 40-5
(5 m) / LKW 40-10 (10 m) or LKG 40-5 (5 m) /
LKG-40-10 (10 m) can be used.
10/25 1.1 safeCAP SC30
Original operating instructions

3
4
2
1
+VDC
0V
PhotoMOS-Relay NO
LED1
LED2
1 | Autostart / Monitored Start
2 | Cross fault detection OFF /ON
3 | 2 single ch. / 1 double ch. sensor
4 | Start up Test yes / no
SET / RESET
A2
A1
INK IN1 T1
PAR
IN2
T2
INF
INS
Q1
Qn
24V
24V
OV
OV
1
2
3
4
4
3
1
2
S1
S2
+24V
NO
NO
NO
NO
T2
INF
ohne Kontaktvervielfältigung
without contact multiplication
Q1
0V 0V
0V
SC30
SC30
R
5.5 Install safety relay MCR 225 (optional)
TIP
More detailed information can be found in the supplier documentation.
5.6 Connect safeCAP SC30 to safety relay MCR
225
► Disconnect the system from its voltage supply.
► Connect safeCAP SC30 to the safety relay using a 6-pin M 12 cable
according to the circuit diagram. The optional cables LKW 60-5 (5 m) /
LKW 60-10 (10 m) or LKG 60-5 (5 m) / LKG-60-10 (10 m) can be used.
safeCAP SC30
Original operating
instructions
1.1 11/25

+VDC
0V
PhotoMOS-Relay NC
PhotoMOS-Relay NO
4
7
1
2
3
5
LED1
LED2
NO
24 V
NO
NC
NC
+
S1
1
S22
S11 S12
S1
2 S21S2
2 S21
A B
-
0 V
24 V
+-
0 V
1 4 5 7 2 3
1 4
5
7 2 3
MCR-225
+24V
0V
Rückführ-
kreis
A
B
Safecap
Safecap
Feedback circuit
SC30
SC30
12/25 1.1 safeCAP SC30
Original operating instructions

5.7 Install safety relay PNOZ s6 (optional)
TIP
More detailed information can be found in the supplier documentation.
5.8 Connect safeCAP SC30 to safety relay PNOZ
s6
► Disconnect the system from its voltage supply.
► Connect safeCAP SC30 to the safety relay using a 6-pin M 12 cable
according to the circuit diagram. The optional cables LKW 60-5 (5 m) /
LKW 60-10 (10 m) or LKG 60-5 (5 m) / LKG-60-10 (10 m) can be used.
+VDC
0V
PhotoMOS-Relay NC
PhotoMOS-Relay NO
4
7
1
2
3
5
LED1
LED2
NO
24 V
NO
NC
NC
Y
+
S1
1
S12
S11 S22
S2
2 S21S1
2 S21
A B
-
0 V
24 V
+-
0 V
safeCAP SC30
Original operating
instructions
1.1 13/25

PNOZ s6
+24V
0V
Rückführ-
kreis
A
B
Safecap
Safecap
Feedback circuit
SC30
SC30
S12 S12S34 S22
S11
S22S12 S21
2313
41
2414 42
33
34
5.9 Connect safeCAP SC30 to an equivalent T-
network
The equivalent T-network realizes parts of the start/restart safety function in
accordance with ISO 13849-1:2015 Table 8.
If an equivalent T-network is used for the relay, the following conditions must be
met.
■The entire FIT value for the equivalent T-network must be determined via
an FMEDA or an equivalent method.
■The equivalent T-network must be certified in accordance with
EN 60947-5-1:2017.
■Must not exceed a FIT value of 40.
■Performance level e category 4 in accordance with ISO 13849-1:2015 must
be met.
■MTTFd must exceed 45.
14/25 1.1 safeCAP SC30
Original operating instructions

■The equivalent T-network must have a diagnosis with a diagnostic coverage
of at least 99%.
■The following formula must be met:
MTTFd (Equivalent t-network) = MTTFd (safeCAP) * 30 / ( MTTFd (safeCAP)
- 30).
Exception: MTTFd (safeCAP) = 100;
This data is indicated to achieve performance level e. All other requirements
for two-hand controls must be met in accordance with the standard
ISO 13851:2019.
+24V
0V
Rückführ-
kreis
A
B
Safecap
Safecap
Feedback circuit
SC30
SC30
The safety function depicted corresponds to the start/restart function in
accordance with Chapter 5.4.3 of ISO 13849-1 [1] (see also ISO 13849-1 Table
8).
5.10 Testing the safety function of the SC30
To ensure the safety function of the SC30, test the safety function as follows.
■During initial start-up
■Once the testing interval has expired
■After maintenance and repairs
Record the results.
safeCAP SC30
Original operating
instructions
1.1 15/25

► Disconnect safeCAP SC30 from the machine.
► Connect a meter to the contacts of the safety relay that release the
machine function.
► Actuate the SC30s one after another.
aThe LEDs must light up in green and yellow.
aThe safety relay must not release N/O or N/C contacts.
Switching on must be verified at the output contacts of the safety relay
using the meter and must not exceed the safety times (0.5 s in this case).
► Disconnect the safeCAP SC30 from the power supply.
► Actuate and continue actuating the SC30.
► Restore the power supply.
aThe LEDs must light up in green and yellow.
aThe safety relay must not release N/O or N/C contacts.
6 Operation
6.1 Operating safeCAP SC30
► Touch both safeCAP SC30 switches simultaneously (within 0.5 s).
► The machine process is triggered.
6.2 Operating safety relay SCR3-3SK1
TIP
More detailed information can be found in the supplier documentation.
7 Maintenance
7.1 Maintenance operations
Carry out the following maintenance operations at the specified intervals.
16/25 1.1 safeCAP SC30
Original operating instructions

Maintenance operation as
needed
annually Testing interval
Clean the switch surface X
Test the safety function X
Check cables for intactness
and firm fit
X
Check screw connections
for tightness
X
7.2 Testing the safety function of the SC30
How to test the safety of SC30 see "Testing the safety function of the SC30",
page 15.
7.3 Troubleshooting
Green LED (1) isn’t lighting up.
► Check the plug on the back for tightness and
damage.
► Check cable for damage.
► Check the power supply.
Yellow LED (2) doesn’t light up when
actuated.
► Switch actuated too slowly.
► Switch actuated too fast.
► Switch actuated with excessively thick gloves.
► Switch surface excessively dirty.
Green LED (1) and yellow LED (2) are lit up.
Process on the machine not triggered.
■Have the switch checked for proper connection.
safeCAP SC30
Original operating
instructions
1.1 17/25

8 Disassembly
WARNING
Improper work on electrical systems!
Electric shock can result in death or life-threatening injuries.
4Before working on electrical systems, disconnect them from their
voltage supply and secure them against being switched on again.
4Work on electrical installations should be carried out only by qualified
personnel in compliance with local and national electrical regulations
and specifications.
■Disconnect the system from its voltage supply
and secure it against being switched on again.
■Disconnect the electrical connection between
safeCAP SC3 and the safety relay.
■Loosen the nuts (1) and pull out safeCAP SC3.
9 Disposal
Different types of electrical and electronic components must be recycled
according to their type. All applicable statutory, state and local laws and
regulations must be complied with.
10 Technical specifications
10.1 Terminal assignment SC30
One-channel Two-channel
3
4
2
1
+VDC
0V
PhotoMOS-Relay NO
LED1
LED2
+VDC
0V
PhotoMOS-Relay NC
PhotoMOS-Relay NO
4
7
1
2
3
5
LED1
LED2
18/25 1.1 safeCAP SC30
Original operating instructions

10.2 Technical specifications SC30 one-channel
Operating voltage 24 V (19.2 to 28.8 V)
Contact rating 100 mA (70 mA at 75°C)
Output PhotoMOS relay NO
Output pulse Constant signal when actuated
LED 1 Green LED
LED 2 Yellow LED
Reverse polarity protection Yes
Short circuit protection Yes
Power consumption Max. 20 mA at 24 V
Operating temperature -25°C (-13°F) to +75°C (167°F)
Degree of protection IP Front IP68 plug IP67
Type of actuation Capacitive
Actuation force No actuation force required
Rated insulation voltage 32 V
Switch-off delay TaMax. 50 ms
Power-up delay Max. 30 ms
MTTFd100 years
10.3 Technical specifications SC30 two-channel
Operating voltage 24 V (19.2 to 28.8 V)
Contact rating 100 mA (70 mA at 75°C)
Output PhotoMOS relay NC, NO
Output pulse Constant signal when actuated
LED 1 Green LED
LED 2 Yellow LED
Reverse polarity protection Yes
Short circuit protection No
Power consumption Max. 20 mA at 24 V
Operating temperature -25°C (-13°F) to +75°C (167°F)
safeCAP SC30
Original operating
instructions
1.1 19/25

Degree of protection IP Front IP68 plug IP67
Type of actuation Capacitive
Actuation force No actuation force required
Rated insulation voltage 32 V
Switch-off delay TaMax. 50 ms
Power-up delay Max. 30 ms
MTTFd100 years
10.4 Technical specifications, safety relay 3SK1
General data
Wire cross-section 0.5 - 2.5 mm2
Operating temperature - 25 to + 60°C
Storage temperature - 40 to + 80°C
Switching capacity, relay outputs
Normally open contacts
Normally closed contacts
5 A / 24 V DC (DC 13)
1 A / 24 V DC (DC 13)
Resistance to short circuit
Max. safety fuse
Circuit breaker
6 A gL
C 1 A
Safety figures Value Unit
Category 4
PL e
MTTFd100 [years]
DCavg 99.0 [%]
PFHd1.3 e-9 [1/h]
average usage dop 220 [days/year]
average usage hop 12 [hours/day]
tcycle 20 [s/cycle]
Lifetime 20 [years]
20/25 1.1 safeCAP SC30
Original operating instructions
Table of contents
Popular Controllers manuals by other brands

ADTRAN
ADTRAN NetVanta 5305 quick start guide

bebro electronic
bebro electronic DC RS alpha manual

Promation Engineering
Promation Engineering P1-12VN4 AC Installation & operation manual

Pixsys
Pixsys DRR245-21-ABC-T manual

Wiznet
Wiznet W7500 Reference manual

Texas Instruments
Texas Instruments LM10524EVM user guide

Carel
Carel ir33 smart Application guide

SOMFY
SOMFY animeo LON 4 DC/E installation guide

Danfoss
Danfoss PVE 7 Series technical information

Chicago Pneumatic
Chicago Pneumatic ES 4000 STANDARD Instruction

industrie technik
industrie technik SEZ2M24 instructions

Honeywell
Honeywell UDC3200 series Operator's manual