Cardinal SMARTCELL User manual

0330-0653-0M Rev D • DC Load Cell Kit
1
DC Digital
Load Cell Kit
Technical Manual

0330-0653-0M Rev D • DC Load Cell Kit
2

0330-0653-0M Rev D • DC Load Cell Kit
I
TABLE OF CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LOAD CELL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LATERAL AND LONGITUDINAL CHECKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLING LOAD CELL CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
HOMERUN CABLE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
Maximum Homerun Cable Length Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
225D Indicator Connection . . . . . . . . ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Re-Installing the 225D Indicator Rear Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
225DLC Controller Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
825D Indicator Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
Re-Installing the 825D Indicator Rear Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
825DLC Controller Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Load Cell Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GROUNDING INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
SETUP AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
Digital Scale Setup and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
To Begin 225D Setup and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Addressing Cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
End Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
225D Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
Smart Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Zero Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Trim Cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Span Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
To Begin 825D Setup and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
Login . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Setup Scale Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Setup DLC Card 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
DLC Card 1 Cell Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Smart Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
Zero Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Trim Cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Span Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
BALANCING WEIGHBRIDGE DEAD LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54

0330-0653-0M Rev D • DC Load Cell Kit
II
TABLE OF CONTENTS, CONT.
DIGITAL SCALE DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
225D DIGITAL SCALE DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
On Screen Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Diagnostic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
Hardware Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64
DETECTING 225D BOARD REPLACEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
225DLC DIGITAL CONTROLLER CARD REPLACEMENT . . . . . . . . . . . . . . . . . . . . 66
825D DIGITAL SCALE DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
On Screen Diagnostics ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
Diagnostic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72
Hardware Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
DETECTING 825D BOARD REPLACEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
825DLC DIGITAL CONTROLLER CARD REPLACEMENT . . . . . . . . . . . . . . . . . . . . 90
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
92
DISPLAYED ERROR MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
92
REPLACE LOAD CELL X ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
LOAD VOLTAGE DETECTED CELL X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
CURRENT DRAW MORE THAN 150% OF CAPACITY . . . . . . . . . . . . . . . . . . 94
LOAD CELL X NOT RESPONDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
95
COMMUNICATIONS ERROR BETWEEN INDICATOR AND SCALE . . . . . . .
95
LOAD CELL X HAS NO ADDRESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
COMMUNICATION ERROR BETWEEN LOADCELLS X AND Y . . . . . . . . . . . 97
SCALE WILL NOT RETURN TO ZERO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
SCALE IS UNSTABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
97
LOAD CELL OR SCALE COMMUNICATION PROBLEMS . . . . . . . . . . . . . . .
98
PARTS IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Serial Number_______________________
Date of Purchase ____________________
Purchased From_____________________
___________________________________
___________________________________
RETAIN THIS INFORMATION FOR FUTURE USE
PRECAUTIONS
Before using this product, read this manual
and pay special attention to all
"NOTIFICATION" symbols:
DANGER!
WARNING!
CAUTION!

0330-0653-0M Rev D • DC Load Cell Kit
III
Copyright
All rights reserved. Reproduction or use, without expressed written permission, of editorial or
pictorial content, in any manner, is prohibited. No patent liability is assumed with respect to the
use of the information contained herein.
Disclaimer
While every precaution has been taken in the preparation of this manual, the Seller assumes
no responsibility for errors or omissions. Neither is any liability assumed for damages
resulting from the use of the information contained herein. All instructions and diagrams have
been checked for accuracy and ease of application; however, success and safety in working
with tools depend largely upon individual accuracy, skill, and caution. For this reason, the
Seller is not able to guarantee the result of any procedure contained herein. Nor can they
assume responsibility for any damage to property or injury to persons occasioned from the
procedures. Persons engaging the procedures do so entirely at their own risk.
FCC Compliance Statement
This equipment generates uses, can radiate radio frequency, and if not installed and used in
accordance with the instruction manual, may cause interference to radio communications. It
has been designed within the limits for a Class A computing device pursuant to Subpart J of
Part 15 of FCC rules to provide reasonable protection against such interference when
operated in a commercial environment. The operation of this equipment in a residential area
may cause interference in which case the user will be responsible to take whatever measures
necessary to correct the interference.
You may find the booklet “How to Identify and Resolve Radio-TV Interference Problems”
prepared by the Federal Communications Commission helpful. It is available from the U.S.
Government Printing Office, Washington, D.C. 20402. Request stock No. 001-000-00315-4.

0330-0653-0M Rev D • DC Load Cell Kit
IV

0330-0653-0M Rev D • DC Load Cell Kit
1
INTRODUCTION
Cardinal Scale’s DC Load Cell kit provides you with the components necessary for the
construction of a digital scale for a tank/hopper installation or an above-ground or pit truck
scale. The DC Load Cell Kit utilizes Cardinal Scale’s SmartCell DC digital load cells and
225DLC or 825-DLC Digital Load Cell Controller to provide in-depth diagnostics, easy
maintenance, and a simplified calibration. Braided cabling is available for enhanced rodent
protection throughout the scale.
This manual should be studied thoroughly before attempting to install the digital scale and
must be used in conjunction with certified drawings of the particular scale being installed.
In case of conflict, the certified drawings will govern.
Safety should always be the prime consideration during all phases of the installation. Failure to
comply with the instructions in this manual will void all warranty implied or stated.

0330-0653-0M Rev D • DC Load Cell Kit
2
LOAD CELL INSTALLATION
NOTE: Cardinal Scale Mfg. Co. recommends that the customer install protective conduit/cover
for the load cell cables whenever the condition is present that can result in damage or abrasion
to the load cell cables.
CAUTION! Be sure all restraint systems are loosened before jacking up the scale.
1. At each section, jack up the weighbridge and remove the load cell spacers.
2. Verify that the recess in the lower Locating Plate is clean and free of dirt and debris.
3. Place the load cells in the lower Locating Plate, following these guidelines:
•Ensure the flat surface (A) of the load cell is aligned with the notch (B) in the load cell
bearing cup.
•Make sure you place the load cell bearing cup with the notch in the lower locating plate.
•Additionally, the load cell must be correctly oriented on the scale. The notch in the load
cell bearing cup must be placed in the lower locating plate in the direction of longitudinal
scale movement (with the flow of traffic).
WARNING! Failure to install the load cell correctly in the load cell bearing cup,
and the notched load cell bearing cup properly oriented in the lower locating
plate will result in damage to the load cell and void the warranty!
NOTE: The load cell bearing cups are provided with O-ring seals to ensure the cleanliness of
the bearing surfaces, and that the bearing buttons are properly centered on the bearing
surface. Should the cups become separated from the cells, first lubricate the O-ring, and then
using a small wire to break the air seal on the O-ring, press the load cell bearing button back
into the load cell bearing cup, and then remove the wire.
B
A
A
Flow of Traffic
Correctly
installed load
cell bearing cup.
Incorrectly installed load
cell bearing cup.
Flat surface (A) of
load cell correctly
installed in notch
(B) of load cell
bearing cup.
Flat surface (A) of load
cell incorrectly installed
in notch (B) of load cell
bearing cup.

0330-0653-0M Rev D • DC Load Cell Kit
3
LOAD CELL INSTALLATION, CONT.
4. Lower the weighbridge in place and verify that the load cell bearing cup is seated on the top
plate and that the load cell is plumb (within 2 degrees in all directions).
5. When all load cells are in place, verify that the scale weighbridge is properly located
laterally and longitudinally. Verify that all load cells are vertical (plumb, within 2 degrees in
all directions). If any are not plumb, jack up the scale at that cell, and reposition the cell.
Care should be exercised to ensure that when the process is complete, all load cells are
vertical (plumb).
6. After repositioning the load cells, again verify that they are vertical (plumb, within 2 degrees
in all directions) and that the weighbridge is seated on each load cell.
7. Next, verify that each load cell is taking its share of the dead load of the scale. If necessary,
install one or more shims between the upper loading bearing cup and weighbridge.
Refer to the Balancing Weighbridge Dead Load section of this manual for instructions on
checking load cell output.
LATERAL AND LONGITUDINAL CHECKING
The check stand brackets should be set on smooth and level concrete and securely fixed to
the concrete to prevent damage to the load cells and/or the scale from excessive movement of
the scale weighbridge.
IMPORTANT! Cardinal Scale Mfg. Co. recommends that lateral and longitudinal
checking limits be adjusted to ± 1/8-inch (3.2 mm) clearance.
IMPORTANT!Load cell
must be vertical (plumb)
within 2 degrees in all
directions!

0330-0653-0M Rev D • DC Load Cell Kit
4
INSTALLING LOAD CELL CABLES
All digital scales using Cardinal Scale’s SmartCell DC digital load cells are connected with a
daisy-chained CAN (Controller Area Network) cable. The load cell connection loop can begin
at any load cell and may continue clockwise as shown or counter-clockwise if preferred. Note
that in the tank/hopper example below there is not a connection between cells 1 and 2 and in
the truck scale example, there is not a connection between cells 4 and 6.
NOTE: Be sure to install the End Node Terminator on the load cell at the end of the connection
loop as shown in both examples.
Example: Typical Tank/Hopper Configuration
NOTE: If the loop were run in the other direction, the sequence would then be 2-4-3-1 with
load cell 1 having the End Node Terminator installed on it.
Example: Typical Truck Scale Configuration
NOTE: If the loop were run in the other direction, the sequence would then be 6-8-7-5-3-1-2-4
with load cell 4 having the End Node Terminator installed on it.
Homerun Cable
7
1
2
3
6
5
8
End Node
Terminator
4
225D or 825D
End Node
Terminator
1
3
225D or 825D
4
Homerun
Cable
2

0330-0653-0M Rev D • DC Load Cell Kit
5
1. Run the load cell cable through the conduit installed in the weighbridges between load
cells.
2. Install the load cell cable connectors on the load cell fittings, and hand-tighten the
connectors.
Insert load cell cable into the
weighbridge conduit.
Install load cell cable connectors on
load cell fittings, and hand-tighten.
3. Install the End Node Terminator on the last load cell of the connection loop.
Install End Node Terminator on the last
load cell of the connection loop.

0330-0653-0M Rev D • DC Load Cell Kit
6
HOMERUN CABLE INSTALLATION
The Homerun Cable is installed between the 225D or 825D indicator and the first load cell in
the loop (Start Node). Consult the chart below to determine the maximum Homerun Cable
length. Note that the number of load cells in the scale determines the maximum length.
Maximum Homerun Cable Length
(Determined by Number of Load Cells in Scale)

0330-0653-0M Rev D • DC Load Cell Kit
7
The Homerun Cable is made from five conductors, shielded PVC cable, and is terminated in
the 225D at the P5 terminal block and in the 825D at the P1 terminal block. The load cell end
is terminated with a 5-pin spring cage connector, from the Home Run Cable Connector Pack.
Refer to the table below for cable and connector information.
Cable and Connector Information
ITEM and DESCRIPTION
CARDINAL PART NO.
HOMERUN CABLE, 5 CONDUCTOR, SHIELDED PVC
(CONTAINS 2 x 18AWG, 2 x 22AWG, AND 1 x 22AWG)
6980-1092
CONNECTOR PACK, HOME RUN CABLE
(
INCLUDES 5-PIN SPRING CAGE CONNECTOR, 6610-1258
)
3502-0681-0A
RECOMMENDED HOMERUN CABLE
BELDEN 5303FE, 18 AWG, 5 CONDUCTOR
SUPPLIED BY DEALER

0330-0653-0M Rev D • DC Load Cell Kit
8
225D Indicator Connection
The homerun cable should be routed through the metallic gland connector installed in the
225D rear panel (lower right).
1. Remove the fourteen acorn nuts securing the rear panel assembly to the main housing.
2. Lift the rear panel from the main housing, taking care not to stretch the cable and wires
between the panel and main housing. Lay the rear panel on the workbench next to the
indicator.
IMPORTANT:You may need to loosen the gland connectors for the I/O cables to
allow enough slack in the cable and wires to avoid stretching them.
3. Loosen and remove the metal gland connector nut, and then remove the plastic insert.
ATTENTION!
OBSERVE PRECAUTIONS FOR HANDLING
ELECTROSTATIC SENSITIVE DEVICES
Digital Scale
AC Power
100-240 VAC
0.4 Amp Max.
I/O
(Serial,
Isolated
Inputs or
Outputs)
Optional
2XX-USBA
Connectors
Fiber
Optic
Cable
I/O
(Serial,
Isolated
Inputs or
Outputs)
51 mm
6 mm

0330-0653-0M Rev D • DC Load Cell Kit
9
4. Route the homerun cable through the nut and plastic insert and into the enclosure.
5. With the homerun cable routed into the enclosure, remove approximately 51 mm of the
cables’ outer jacket, exposing the internal wires.
6. Next, remove approximately 6 mm of insulation from each of the five wires.
7. Referring to the table below (or on the circuit board) for terminal connections, connect each
wire to the P5 terminal block on the 225DLC controller card.
225DLC Controller Card P5 Terminal Connections
Board
Label
Homerun Cable
Wire Color
Wire Color if using a
Load Cell Cable
SHLD
GRAY
BROWN
V+BUS
RED
WHITE
V-BUS
BLACK
BLUE
CAN H
WHITE
BLACK
CAN L
BLUE or LIGHT BLUE
GRAY
8. Using a small flat blade screwdriver press down on the release bar for the terminal, insert
the wire into the opening, and then remove the screwdriver. The release bar will return to
its original position, locking the wire in place.
9. Repeat steps 7 and 8 until all five wires of the homerun cable are installed in the P5
terminal block on the 225DLC controller card.
10.After all terminations have been made, remove the excess cable from the indicator
enclosure.
11.Insert the plastic insert into the metal gland connector, and finger-tighten the metal gland
connector nut and each of the black gland connectors.
Press Down Here
Insert Wire Here

0330-0653-0M Rev D • DC Load Cell Kit
10
Re-Installing the 225D Indicator Rear Panel
1. After all terminations have been made, remove the excess cable from the indicator
enclosure, and finger-tighten each of the cable gland connectors.
2. Ensure any unused gland connectors are plugged and replace the rear panel.
3. Secure the rear panel with the fourteen acorn nuts removed earlier, following a diagonal
pattern when tightening the acorn nuts.
4. Using a wrench, tighten the plastic gland connectors to 1.7 Nm.
5. Using a wrench, tighten the metal gland connector to 3.7 Nm.
225DLC Controller Card
USB-B
This port is used to perform firmware updates to the 225DLC controller card.
P5
Homerun
Cable
Attach
G
round
wire here
Ethernet
Po
rt for
iSite
USB-B
Port
Micro SD
Card Slot
LED1
LED
2
LED3
LED4
J1
End Node
J2, J3
ICAN
Jumpers
P4 – Legacy
Serial iSite
P4
Future Use

0330-0653-0M Rev D • DC Load Cell Kit
11
LED 1-4
The LEDs are used for diagnostic purposes. For a complete explanation of their function, refer
to the DIGITAL SCALE DIAGNOSTICS, Hardware Diagnostics section of this manual.
Ethernet Port
This port is used to connect the 225D to your network to send information to the cloud for iSite.
Micro SD Card Slot
The Micro SD card slot is not used at this time.
J1, End Node Jumper
Jumper J1 is the CAN bus END NODE jumper.
NOTE: The J1 jumper must be installed for the 225D communications to the scale to operate.
J2, J3 ICAN Jumpers
When ON (installed), these jumpers allow the 225D indicator to supply (source) 15 VDC to the
digital load cells in the scale. To operate from an external power source, such as the model
MB-AC media box or an external 12 to 24 VDC power supply provided by the customer, the
jumpers must be OFF (on one pin only or removed).
IMPORTANT! To operate from an external power source, the jumpers must be OFF
(on one pin only or removed), and 12 to 24 VDC must be applied to the V+BUS
terminal with a ground return to the V-BUS terminal of the P5 terminal block.
P5, Homerun Cable
The P5 terminal block is used to connect the homerun cable between the 225D indicator and
the first load cell in the loop (Start Node in the scale). Refer to the table below for terminal
connections.
Homerun Cable Connection to P5 Terminal Block
Board
Label
Homerun Cable
Wire Color
Wire Color if using a
Load Cell Cable
SHLD
GRAY
BROWN
V+BUS
RED
WHITE
V-BUS
BLACK
BLUE
CAN H
WHITE
BLACK
CAN L
BLUE or LIGHT BLUE
GRAY
P4, Legacy Serial iSite
This portion of the P4 terminal block is used to connect to Legacy Serial iSite wiring when
replacing or updating the indicator in an older system with a 225D.
P4, Future Use
This portion of the P4 terminal block is not used at this time. It is reserved for a future serial
connection.

0330-0653-0M Rev D • DC Load Cell Kit
12
825D Indicator Connection
The homerun cable should be routed through the metallic gland connector installed in the
825D rear panel (lower right).
1. Remove the fourteen acorn nuts securing the rear panel assembly to the main housing.
2. Lift the rear panel from the main housing, taking care not to stretch the cable and wires
between the panel and main housing. Lay the rear panel on the workbench next to the
indicator.
IMPORTANT:You may need to loosen the gland connectors for the I/O cables to
allow enough slack in the cable and wires to avoid stretching them.
3. Loosen and remove the metal gland connector nut, and then remove the plastic insert.
ATTENTION!
OBSERVE PRECAUTIONS FOR HANDLING
ELECTROSTATIC SENSITIVE DEVICES
I/O (Serial, Isolated
Inputs/Outputs) or
Additional Scales
Digital Scale
AC Power
90-264 VAC
0.4 Amp
10/100 LAN
and USB
Access Cover
Ground
Lug
51 mm
6 mm

0330-0653-0M Rev D • DC Load Cell Kit
13
4. Route the homerun cable through the nut and plastic insert and into the enclosure.
5. With the homerun cable routed into the enclosure, remove approximately 51 mm of the
cables’ outer jacket, exposing the internal wires.
6. Next, remove approximately 6 mm of insulation from each of the five wires.
7. Remove the screw securing the 825-DLC Controller to the 825D main PC board and then
lift the 825-DLC straight up to remove it from the enclosure
8. Referring to the table below (or on the circuit board) for terminal connections, connect each
wire to terminal block P1 on the 825-DLC Controller.
825DLC Controller Card P1 Terminal Connections
Board
Label
Homerun Cable
Wire Color
Wire Color if using a
Load Cell Cable
SHLD
GRAY
BROWN
V+BUS
RED
WHITE
V-BUS
BLACK
BLUE
CAN H
WHITE
BLACK
CAN L
BLUE or LIGHT BLUE
GRAY
9. Using a small flat blade screwdriver press down on the release bar for the terminal, insert
the wire into the opening, and then remove the screwdriver. The release bar will return to
its original position, locking the wire in place.
10.Repeat steps 8 and 9 until all five wires of the homerun cable are installed in the P1
terminal block on the 825DLC controller card.
11.After all terminations have been made, reinstall the 825-DLC into the enclosure, taking care
not to strike the board against the side of the 825D enclosure.
12.Secure the 825-DLC to the main PC board with the screw removed earlier.
13.Remove the excess cable from the indicator enclosure.
14.Insert the plastic insert into the metal gland connector, and finger-tighten the metal gland
connector nut and each of the black gland connectors.
Re-Installing the 825D Rear Panel
1. After all terminations have been made, and the 825-DLC is secured to the main PC board,
ensure that all excess cable has been removed from the indicator enclosure, and finger-
tighten each of the cable gland connectors.
2. Ensure any unused gland connectors are plugged and replace the rear panel.
3. Secure the rear panel with the fourteen acorn nuts removed earlier, following a diagonal
pattern when tightening the acorn nuts.
4. Using a wrench, tighten the plastic gland connectors to 1.7 Nm.
5. Using a wrench, tighten the metal gland connector to 3.7 Nm.

0330-0653-0M Rev D • DC Load Cell Kit
14
825-DLC Controller Card
J2, End Node Jumper
Jumper J2 is the CAN bus END NODE jumper and should be ON (installed).
NOTE: The 825D is one end of the CAN bus connections and must be installed for the 825D
communications to the scale to operate.
J1, J3 ICAN Jumpers
When ON (installed), these jumpers allow the 825D indicator to supply (source) 12 VDC to the
digital load cells in the scale. To operate from an external power source, such as the model
MB-AC media box or an external 12 to 24 VDC power supply provided by the customer, the
jumpers must be OFF (on one pin only or removed).
IMPORTANT! To operate from an external power source, the jumpers must be OFF
(on one pin only or removed), and 12 to 24 VDC must be applied to the V+BUS
terminal with a ground return to the V-BUS terminal of the P1 terminal block.
J4, PWR END
This jumper will be installed if power originates at the 825D and powers the digital load cells in
the scale over the CAN bus cable (HomeRun Cable).
Mounting
Bracket
J2
End Node
P7, RS232
Serial Port
D1, D2, D3, D4
Ethernet
Port for iSite
Micro
USB
J3, J1 ICAN
Jumpers
P1
Homer
un
Cable
J4
PWR End
Edge Card
Connector
Table of contents
Other Cardinal Industrial Equipment manuals