18
The pumps tted to these units have motors which meet efciency class IE2 for motors < 7.5kW and IE3 for motors > 7.5kW.
The additional electrical data required(1) is as follows:
For the low-pressure single pump motors of 30RBM/RBP 160-520 units (option 116T)
(2) (3)
180 200 220 300 330 400 430 470 520
1Nominal eciency at full load and nominal voltage % 85,7 85,7 85,7 85,7 85,7 87,5 87,5 87,5 89,9 89,9 89,9 89
1Nominal eciency at 75% of full load and nominal voltage % 86,9 86,9 86,9 86,9 86,9 88,2 88,2 88,2 90,4 90,4 90,4 90
1Nominal eciency at 50% of full load and nominal voltage % 86,4 86,4 86,4 86,4 86,4 87,5 87,5 87,5 89,6 89,6 89,6 89,7
2Eciency level -IE3
3Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4Company name or trademark, commercial registration number and
head oce of manufacturer
-Same as above
5Product model number -Same as above
6Number of motor poles - 222222222222
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 2,2 2,2 2,2 2,2 2,2 3 3 3 4 4 4 5,5
7-2 Maximum input power (400 V)(4) kW 2,80 2,80 2,80 2,80 2,80 3,81 3,81 3,81 4,96 4,96 4,96 6,80
8Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 X 400
9-2 Maximum current drawn (400 V)(5) A 4,92 4,92 4,92 4,92 4,92 6,81 6,81 6,81 8,27 8,27 8,27 11,30
10 Nominal speed rps - rpm 48 - 2900
11 Product disassembly, recycling or disposal at end of life -Disassembly using standard tools. Disposal and recycling using an appropriate company.
12 Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000(6)
II - Ambient air temperature °C < 40
IV - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specic
conditions in the Carrier selection programs.
V - Potentially explosive atmospheres - Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
For the low-pressure dual pump motors of 30RBM/RBP 160-520 units (option 116T)
(2) (3)
180 200 220 300 330 400 430 470 520
1Nominal eciency at full load and nominal voltage % 84,9 84,9 85,7 85,7 87,5 87,5 87,5 87,5 89,9 89,9 89,9 89
1Nominal eciency at 75% of full load and nominal voltage % 86,4 86,4 86,9 86,9 88,2 88,2 88,2 88,2 90,4 90,4 90,4 90
1Nominal eciency at 50% of full load and nominal voltage % 85,9 85,9 86,4 86,4 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,7
2Eciency level -IE3
3 Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4Company name or trademark, commercial registration number and
head oce of manufacturer
-Same as above
5Product model number -Same as above
6Number of motor poles - 222222222222
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 1,5 1,5 2,2 2,2 3 3 3 3 4 4 4 5,5
7-2 Maximum input power (400 V)(4) kW 1,94 1,94 2,80 2,80 3,81 3,81 3,81 3,81 4,96 4,96 4,96 6,80
8 Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 X 400
9-2 Maximum current drawn (400 V)(5) A 3,41 3,41 4,92 4,92 6,81 6,81 6,81 6,81 8,27 8,27 8,27 11,30
10 Nominal speed rps - rpm 48 - 2900
11 Product disassembly, recycling or disposal at end of life -Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12 Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specic
conditions in the Carrier selection programs.
V - Potentially explosive atmospheres - Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.