
20
SURGE CORRECTION CONTROL
There are two stages for surge correction: envelope control
(surge prevention) and surge protection.
Envelope Control
A surge condition occurs when the lift becomes so high that the
gas flow across the impeller reverses. This condition can even-
tually cause compressor damage. The surge prevention algo-
rithm notifies the operator that chiller operating conditions are
marginal and to take action, such as lowering entering con-
denser water temperature, to help prevent compressor damage.
If a high sound condition occurs at low guide vane position, the
EC/HGBP (Envelope Control/Hot Gas Bypass) valve is used to
decrease the sound level. The envelope control algorithm is an
operator-configurable feature that can determine if lift condi-
tions are too high for the compressor and then take corrective
action. High efficiency mode or low noise mode can be select-
ed. Lift is defined as the difference between the saturated tem-
perature at the impeller eye and at the impeller discharge. The
maximum lift a particular impeller wheel can perform varies
with the gas flow across the impeller and the size of the wheel.
If Actual Lift is higher than reference lift, a capacity inhibit
signal will be sent. If Actual Lift is higher than reference lift
plus Envelope High Deadband, a capacity decrease signal will
be sent. If Actual Lift is lower than reference lift minus Enve-
lope Low Deadband, these 2 signals will be canceled. Capacity
Control will respond to these 2 signals and make correction on
IGV1 TARGET POSITION, VFD TARGET SPEED, and EC/
HGBP actuator. To improve system performance SURGE
PROFILE OFFSET will be incremented by 1 if no surge pre-
vention has been active in the past 5 minutes. The Reference
Lift will subtract the SURGE PROFILE OFFSET prior to com-
paring to Actual Lift.
Surge Protection
The Surge Protection algorithm will run after SURGE DELAY
TIME has elapsed when compressor has been commanded to
turn on. It compares the present PERCENT LOAD CURRENT
value with the previous value once every second. If the differ-
ence exceeds the maximum AMPS change value (SURGE
DELTA % AMPS + [PERCENT LINE CURRENT / 10]), an
incidence of surge has occurred, and the surge protection signal
will be sent.
When an incidence of surge determined in this manner has oc-
curred, the SURGE COUNTS will be incremented by one. On
receiving the surge protection signal, Capacity Control will
make corrections on IGV1 TARGET POSITION, VFD TAR-
GET SPEED, and EC/HGBP actuator. When correction is in
effect, Surge Protection Count will increase by 1 when a com-
mand for either IGV decrease, VFD speed increase, or EC/
HGBP actuator activation is required for correction. Guide
vane movement will be inhibited for 1 minute after surge pro-
tection ends.
Chiller will do 259 Alarm shutdown under the following
conditions.
• If Surge Protection Counts exceed 20 within a Surge Time
Period. Note that if VFD, then VFD target speed must
equal max before this alarm is activated.
• If IGV, VFD, and HGBP cannot be further adjusted for
surge protection when Surge Protection Counts exceed 4
within a Surge Time Period.
If IGV, VFD, and HGBP control cannot correct the problem,
the chiller will initiate a shutdown alarm when the surge count
is greater than 4.
ENVELOPE/HOT GAS BYPASS (HGBP) CONTROL
This function is used to artificially load the chiller and keep it
running under low load conditions or to prevent surge condi-
tions. Since this also reduces the performance of the machine,
EC/HGBP Control is a user-selectable option.
The EC/HGBP control valve is a modulating type controlled
by a 4 to 20 mA signal.
Envelope/hot gas bypass operation has three different modes
when installed (hgbp_opt > 0) and enabled (hgbp_sel > 0):
• Envelope control and surge protection — Each compressor
has unique lift characteristics that can be plotted to deter-
mine performance. The controller will determine operating
conditions that could result in compressor surge and acti-
vate the bypass valve to prevent surge until the chiller op-
erating parameters are in a safe area on the curve where the
valve may be closed again.
• Envelope (HGBP) low load operation — In this condition,
the valve will be opened to prevent a recycle shutdown
from occurring. The valve will remain open until this min-
imal loading condition has passed and there is no surge
condition present.
• Combination for envelope control and surge correction, as
well as low load operation — When this option is selected,
both EC for envelope control/surge protection and EC for
low load operation will be performed. Surge protection
will take higher priority if both conditions are satisfied.
DEMAND LIMIT
The PIC6 controls provide a feature for limiting AVERAGE
LOAD CURRENT or MOTOR KILOWATTS by limiting ca-
pacity via guide vane control/VFD control. The limit may be
applied in two ways. The first is called ACTIVE DEMAND
LIMIT, which is equal to a BASE DEMAND LIMIT value (set
in the SETPOINT screen, default value 100%). ACTIVE DE-
MAND LIMIT may also be forced to be different from BASE
DEMAND LIMIT by manually overriding (forcing) the value
via a CCN network device. If the DEMAND LIMIT SOURCE
exceeds the ACTIVE DEMAND LIMIT by 5% or less, capaci-
ty will be inhibited. If the DEMAND LIMIT SOURCE ex-
ceeds the ACTIVE DEMAND LIMIT by more than 5%, ca-
pacity will be decreased.
Alternatively, the limit may be applied by AUTO DEMAND
LIMIT INPUT, an optional 4 to 20 mA input. This demand
limit control option (4 to 20 mA DEMAND LIMIT TYPE) is
externally controlled by a 4 to 20 mA signal. The option is set
up on the Configuration Menu
GENERAL CONFIGURA-
TION screen. When enabled, 4 mA will set ACTIVE DE-
MAND LIMIT to 100% of the DEMAND LIMIT SOURCE
(regardless of the value of BASE DEMAND LIMIT), and 20
mA will set ACTIVE DEMAND LIMIT to the value config-
ured for DEMAND LIMIT AT 20 mA in the Configuration
Menu
SERVICE PARAMETERS screen.
OVERRIDE CONTROL
Capacity overrides can prevent some safety shutdowns caused
by exceeding the motor amperage limit, evaporator refrigerant
low temperature safety limit, motor high temperature safety
limit, and condenser high pressure limit. In these cases there
are two stages of capacity control:
1. When the value of interest crosses the first stage set point
into the override region, the capacity is prevented from
increasing further, and the status line on the PIC6 control-
ler indicates the reason for the override. Normal capacity
control operation is restored when the value crosses back
over the first stage set point, leaving the override region.
2. When the value of interest is in the override region and
further crosses the second stage set point, the capacity is
decreased until the value meets the override termination
condition. The PIC6 controls resume normal capacity con-
trol operation after the override termination condition has
been satisfied. (In the case of high discharge superheat,
there is an intermediate stage.)
Table 15 summarizes these override parameters.