Carrier CRNEMAFX001A00 User manual

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-734 Printed in U.S.A. Form 48/50-51SI Pg 1 4-99 Replaces: New
Book111444
Tab 1a1b5a5a6a6b
Installation Instructions
Part Numbers: CRNEMAFX001A00, CRNEMAFX002A00,
CRNEMAFX003A00
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should in-
stall, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions such as changing bulbs. All other operations should be
performed by trained service personnel. When working on air-
conditioning equipment, observe precautions in the literature,
tags and labels attached to the unit or accessory, and other safe-
ty precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves.
GENERAL
Carrier’s commercial rooftop ultra-violet germicidal lamps
are designed to kill odor causing mold and fungus that may de-
velop in the wet evaporator section of an HVAC unit. The high
output, low temperature germicidal lamps are installed in the
evaporator section of the HVAC unit, and are pointed directly
at the evaporator coil and condensate pan. The short wave
length ultra-violet band light inhibits and kills mold, fungus,
and microbial growth.
The Carrier germicidal lamps have been specifically de-
signed and optimized for 40 to 45 F, high-humidity operation in
a moving airstream inside an HVAC unit. The Carrier germi-
cidal lamps have output ratings at 45 F in a 400 fpm airflow of
120 microwatts/cm2at a 1 meter range.
PACKAGE USAGE
Before installing accessory or performing maintenance or
service on accessory, turn off main power switch to unit.
Electrical shock can cause injury or death. There may be
more than one disconnect switch.
Never expose eyes or skin to ultra-violet light from any
source. After installation, provide an interlock to turn off
germicidal lamps when access door is opened. Lamp must
be off before entering HVAC unit to perform maintenance
or service. Personal injury may result.
Use only specified high-output, low temperature bulbs with
this accessory. Use of a lower wattage or incorrect bulb can
result in damage to accessory or bulb. Correct bulbs have a
blue end cap.
Do not touch emitter glass without gloves. Damage to bulb
may result. Oil from fingerprints will permanently etch
glass of bulb and weaken structure. Clean bulb after
handling.
Bulb contains a small quantity of mercury. If a bulb breaks,
clean and dispose with care.
UNIT ELECTRICAL CHARACTERISTICS PART NUMBER
48/50HJ004-014,48/50TJ004-014
50HJQ004-012 208/230 V, 70-85 W, 50/60 Hz CRNEMAFX002A00
48/50EJ,EK,EW,EY024-068
48/50HJ015-025, 50HJQ014,016,
48/50TJ016-028
115 V, 70-85 W, 50/60 Hz CRNEMAFX001A00
208/230 V, 70-85 W, 50/60 Hz CRNEMAFX002A00
277 V, 70-85 W, 50/60 Hz CRNEMAFX003A00
Accessory Ultra-Violet Germicidal Lamps
Single Package Rooftop Units
50/60 Hz

2
INSTALLATION
Location — Germicidal lamps are installed in the evaporator
section where they will have contact with the air stream and
moist surfaces. Refer to the installation locations provided in
Fig. 1-4. The stainless steel power supply section of the acces-
sory is installed on the outside of the unit and is waterproof.
See Fig. 5 for accessory dimensions.
Make sure site can be supplied with the necessary power re-
quirements. Ensure that there is adequate clearance for service.
Installation (48/50HJ,TJ015-028 Units and
50HJQ014, 016 Units) — Perform the following proce-
dure to install the germicidal lamp:
1. Turn off all power to unit.
2. Install reflective material (field-supplied) in installa-
tion location if desired. Reflecting ultra-violet light
energy is recommended to enhance performance and
reduce shadows. Lining the installation area with alu-
minum or aluminum foil allows light energy to reflect
instead of being absorbed, increasing the effectiveness
of the germicidal lamp.
3. Ultra violet light may damage certain plastics and
exposed non-UVC (Ultra Violet Radiation, C-Band)
protected wires. (Drain pans will not be damaged.)
Wrap exposed plastic and wiring with aluminum tape
or use metal conduit.
4. Mount field-provided light-switch disconnect switch
on unit hood. See Fig. 1, 6, and 7. Disconnect switch
should have a waterproof housing.
5. A separate source power supply must be routed to the
accessory germicidal lamp’s unit mounted disconnect
switch per applicable codes. Unit wiring and control
box connections should not be used. Refer to the Pack-
age Usage table for electrical characteristics of power
supply. Power source must be a suitable fused,
grounded, protected source with the correct voltage.
Other voltages will permanently damage the germi-
cidal lamp.
Wire per Table 1.
Table 1 — Wiring Recommendations
6. Any hinged potential access panel or door to the instal-
lation area must be interlocked with the accessory
power source to turn the lamp off if the door is opened.
Access doors should be labelled with appropriate
warnings about exposure to ultra-violet light.
A pushbutton door interlock switch (Carrier Part No.
HR54ZA101) is required on all hinged access panels.
Use a field-fabricated and -installed bracket to mount
the door interlock switch to the unit corner post. See
Fig. 6 and 8. Use insulated sleeve terminals for con-
nection to interlock switch. The pushbutton door inter-
lock switch is not required on non-hinged access
panels. Door interlock switch should be located on the
side of the access door that opens. Locate the switch
near the top of the door so it will not be in a location
where it interferes with maintenance or service.
Run wiring into disconnect switch. Door interlock
switch should be wired into the power (Black) lead,
between the disconnect switch and the germicidal
lamp, to break power to the accessory when the door is
opened.
7. Access doors may be equipped with a glass or Lexan®
window to view lamps.
A glass or Lexan window will not pass ultra-violet
rays and is not a safety risk.
8. Using the accessory as a template, mark two 1-in.
insertion holes on the mounting surface. Mark 8 holes
for accessory mounting. See Fig. 1 and 5 for location.
The 1-in. holes are used for electrical connections and
the germicidal bulb. See Fig. 5.
WIRING COLOR
Power Black
Neutral White
Ground Green
BULB
1.50
UVC DISCONNECT
SWITCH
36.00 ECONOMIZER
HOOD
TYP
5.00
30.00
TYP
UNIT TOP
COVER
TYPICAL
INDOOR
FAN SECTION
(TOP VIEW)
STRAIN
RELIEF
BUSHING
REQ.
7/8"
HOLE
7/8" HOLE
(REQUIRED
FOR
CONDUIT
ONLY)
BULB
Fig. 1 — Germicidal Lamps Installation Location — 48/50HJ,TJ015-028 and 50HJQ014 and 016 Units
NOTES:
1. Dimensions are in inches.
2. Dimensions are from out-
side edges.
3. Wiring is shown with
ROMEX cable. If conduit is
used, two holes in bracket
are used.

3
BULB
5.00
TYP.
38.50
TYP.
34.00
34.00
16.50
LOCATION OF
FIRST BULB
(SEE NOTE #2)
NOTE:
1. Unless otherwise specified
all dimensions are to out-
side of part.
2. On size 038-048 units, use
4 bulbs spaced at 34.00''.
On size 054-068 units, use
5 bulbs spaced at 34.00''.
3. Dimensions are in inches.
Fig. 2 — Germicidal Lamps Installation Location — 48/50EJ,EK,EW,EY Units
(Size 024-034 Shown)
NOTE: Dimensions are in inches.
Fig. 3 — Germicidal Lamps Installation Location — 48/50HJ,TJ004-007 and 50HJQ004-007 Units

4
9. Drill 1-in. holes in unit where marked.
Fig. 4 — Germicidal Lamps Installation Location — 48/50HJ,TJ008-014 and 50HJQ008-012 Units
NOTE: Dimensions are in inches.
Fig. 5 — Accessory Dimensions
NOTE: Dimensions are in inches.

5
10. Use field-supplied no. 10 self-drilling screws to attach
accessory to unit.
NOTE: Holes can be drilled in unit if self-drilling
screws are not used. Drill 8 holes for eight no. 10
screws used to attach accessory to unit. Using eight no.
10 screws, attach accessory to unit.
Be sure accessory has a watertight seal against unit
wall. Use standard 1/2-in. strain relief connectors
when running wiring through any hole in unit.
Repeat for all accessory germicidal lamps.
11. Wire accessory germicidal lamp to disconnect switch.
See Table 1 for wiring recommendations. Use UVC
resistant wire, outdoor duty, 14-gage ROMEX cable or
1/2-in. conduit for all wiring. Wire power, neutral, and
ground leads to disconnect switch. Do not ground to
unit. See Fig. 9.
Route wiring away from indoor fan motor and coil sur-
faces. Strain relief bushings are required when routing
wire through panels. A 7/8-in. diameter hole is
required in top coil support bracket to route wiring to
disconnect switch. The 7/8-in. diameter hole may be
factory-drilled depending on when the unit was pro-
duced. Field-drilling of hole may be required.
When using ROMEX cable, accessories can be wired
in series. When using conduit, accessories cannot be
wired in series due to size of conduit, and an additional
7/8-in. diameter hole is required in top coil support
bracket for routing of conduit from both accessories.
See Fig. 6.
When connecting to terminals in accessory germicidal
lamp, strip end of wire 3/8-in. and push wire into ter-
minal. Ultra-violet lamps should be operated continu-
ously from power source. Lamps should not be
connected to indoor fan power source or any power
source where they would be cycled more than twice
per day.
NOTE: If door interlock switch is used, black power
lead will be connected to the door interlock switch wir-
ing (not to the disconnect switch).
12. Locate the germicidal bulb. DO NOT TOUCH
GLASS ON BULB. Grasp the bulb only by the base
(non-glass part). Clean the bulb using a lint free wipe
and isopropyl alcohol. Make sure O-ring on bulb is
toward the accessory and push into the 1-in. hole until
seated. Hold the bulb in place and lock into place by
installing the spring wire fastener to the lances on the
bulb.
13. Push on the power plug. Do not force. Rotate
90 degrees if necessary.
14. Affix the ultra-violet light warning label to the outside
of the unit, in plain sight, on all access doors. Replace
label when worn. See Fig. 10.
15. Test all circuits and return power to unit. Accessory
bulb should glow with a blue hue. If bulb cannot be
seen briefly back out bulb and view from safe distance.
Replace bulb when done. If bulb does not glow, check
wiring, safety interlock, or replace bulb.
Installation (48/50EJ,EK,EW,EY Units) —Perform the
following procedure to install the germicidal lamp:
1. Turn off all power to unit.
2. Install reflective material (field-supplied) in installa-
tion location if desired. Reflecting ultra-violet light
energy is recommended to enhance performance and
reduce shadows. Lining the installation area with alu-
minum or aluminum foil allows light energy to reflect
instead of being absorbed, increasing the effectiveness
of the germicidal lamp.
Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.
Fig. 6 — Disconnect Switch and Interlock Switch Installation —
48/50HJ,TJ015-028 Units and 50HJQ014 and 016 Units
NOTE: Dimensions are in inches.

6
UVC ACCESSORY OUTDOOR
AIR HOOD UVC DISCONNECT
SWITCH
10-12"
1.25
0
3.67
0
0
0.25
1.62
2.00
5.16
2.38
0
FLAT PATTERN
0
0.25
0.25
1.62
0
0.30
0.50
Fig. 7 — Disconnect Location —
48/50HJ,TJ015-028 Units and 50HJQ014 and 016 Units
Fig. 8 — Field-Fabricated Bracket for Door Interlock Switch —
48/50HJ,TJ015-028 Units and 50HJQ014 and 016 Units
NOTE:
1. Unless otherwise specified
all dimensions are to outside
of part.
2. Dimensions are in inches.

7
3. Ultra violet light may damage certain plastics and
exposed non-UVC protected wires. (Drain pans will
not be damaged.) Wrap exposed plastic and wiring
with aluminum tape or use metal conduit.
4. Mount field-provided light-switch disconnect switch
on unit. See Fig. 11 for location. Disconnect switch
should have a waterproof housing.
5. A separate source power supply must be routed to the
accessory germicidal lamp’s unit mounted disconnect
switch per applicable codes. Unit wiring and control
box connections should not be used. Refer to the Pack-
age Usage table for electrical characteristics of power
supply. Power source must be a suitable fused,
grounded, protected source with the correct voltage.
Other voltages will permanently damage the germi-
cidal lamp.
Wire per Table 1.
6. Any hinged potential access panel or door to the instal-
lation area must be interlocked with the accessory
power source to turn the lamp off if the door is opened.
Access doors should be labelled with appropriate
warnings about exposure to ultra-violet light.
A pushbutton door interlock switch (Carrier Part No.
HR54ZA101) is required on all hinged access panels.
Use a field-fabricated and -installed bracket to mount
the door interlock switch. See Fig. 8. Use insulated
sleeve terminals for connection to interlock switch.
The pushbutton door interlock switch is not required
on non-hinged access panels. Door interlock switch
should be located on the side of the access door that
opens. Locate the switch near the top of the door so it
will not be in a location where it interferes with main-
tenance or service.
Run wiring into disconnect switch. Door interlock
switch should be wired into the power (Black) lead,
between the disconnect switch and the junction box
(installed in Step 10), to break power to the accessory
when the door is opened.
7. Access doors may be equipped with a glass or Lexan®
window to view lamps. A glass or Lexan window will
not pass ultra-violet rays and is not a safety risk.
8. Using the accessory as a template, mark two 1-in.
insertion holes on the mounting surface. Mark 8 holes
for accessory mounting. See Fig. 2 for location. The
1-in. holes are used for electrical connections and the
germicidal bulb. See Fig. 5.
9. Drill 1-in. holes where marked.
10. Use field-supplied no. 10 self-drilling screws to attach
accessory to unit.
NOTE: Holes can be drilled in unit if self-drilling
screws are not used. Drill 8 holes for eight no. 10
screws used to attach accessory to unit. Using eight no.
10 screws, attach accessory to unit.
Be sure accessory has a watertight seal against unit
wall. Use standard 1/2-in. strain relief connectors
when running wiring through any hole in unit.
Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.
UVC EXPOSURE HAZARD
RISQUE D'EXPOSITION AUX UVC
Turn off power to UVC lights before servicing or repairing.
Never expose unprotected eyes or skin to the UVC light.
This unit contains high energy ultraviolet C-band (UVC) germicidal
lamps which can cause serious temporary eye and skin irritation.
Couper l'alimentation des lampes UVC avant l'entretien ou les
reparations.
Cet appareil contient des lampes germicides haute energie a ultra-violets
de bande C (UVC), qui peuvent causer l'irritation momentanee grave des
yeux et de la peau.
Ne jamais exposer les yeux ou la peau non proteges a la lumiere UVC.
CU000135
WARNING
!
AVERTISSEMENT
!
`
`
`
`
`
`
`
`
Fig. 10 — Warning Label
TO DISCONNECT
SWITCH OR
JUNCTION
BOX
BLK
WHT
GRN
GRN
GRN
Fig. 9 — Accessory Wiring

8
Repeat for all accessory germicidal lamps. There may
be 3, 4, or 5 lamps required.
Install a standard 4 x 4 junction box in the unit near the
disconnect switch. Wire the disconnect switch to the
junction box. Connect power (black), neutral (white),
and ground (green) wiring.
NOTE: If door interlock switch is used, power (black)
lead will be connected to the door interlock switch.
11. Wire all accessory germicidal lamps to junction box.
See Fig. 9 and 12. See Table 1 for wiring recommenda-
tions. Use UVC resistant wire, outdoor duty, 14-gage
ROMEX cable or 1/2-in. conduit for all wiring. Wire
power, neutral, and ground leads to disconnect switch.
Do not ground to unit. When connecting to terminals
in accessory germicidal lamp, strip end of wire 3/8-in.
and push wire into terminal. Ultra-violet lamps should
be operated continuously from power source. Lamps
should not be connected to indoor fan power source or
any power source where they would be cycled more
than twice per day.
12. Locate the germicidal bulb. DO NOT TOUCH
GLASS ON BULB. Grasp the bulb only by the base
(non-glass part). Clean the bulb using a lint free wipe
and isopropyl alcohol. Make sure O-ring on bulb is
toward the accessory and push into the 1-in. hole until
seated. Hold the bulb in place and lock into place by
installing the spring wire fastener to the lances on the
bulb.
13. Push on the power plug. Do not force. Rotate
90 degrees if necessary.
14. Affix the ultra-violet light warning label to the outside
of the unit, in plain sight, on all access doors. Replace
label when worn. See Fig. 10.
15. Test all circuits and return power to unit. Accessory
bulb should glow with a blue hue. If bulb cannot be
seen briefly back out bulb and view from safe distance.
replace bulb when done. If bulb does not glow, check
wiring, safety interlock, or replace bulb.
Installation (48/50HJ,TJ004-014 Units and
50HJQ004-012 Units) —Perform the following proce-
dure to install the germicidal lamp:
1. Turn off all power to unit.
2. Install reflective material (field-supplied) in installa-
tion location if desired. Reflecting ultra-violet light
energy is recommended to enhance performance and
reduce shadows. Lining the installation area with alu-
minum or aluminum foil allows light energy to reflect
instead of being absorbed, increasing the effectiveness
of the germicidal lamp.
3. Ultra violet light may damage certain plastics and
exposed non-UVC protected wires. (Drain pans will
not be damaged.) Wrap exposed plastic and wiring
with aluminum tape or use metal conduit.
4. Mount field-provided light-switch disconnect switch
on unit. Disconnect switch should have a waterproof
housing.
Size 004-007 Units:
A field-supplied bracket is required to mount the light-
switch disconnect on size 004-007 units. Perform the
following procedure to install the disconnect switch:
a. Remove two screws from unit top cover flange,
located above accessory installation location. Save
screws.
b. Fabricate disconnect mounting switch bracket. See
Fig. 13 for bracket dimensions and details.
c. Drill hole in side panel of unit for disconnect wir-
ing. See Fig. 14 for hole dimensions.
Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.
5.25
16.00
UVC
DISCONNECT
BOX
024-034 UNIT SHOWN
NOTES:
1. Unless otherwise specified all
dimensions are to outside of
part.
2. Dimensions are in inches.
Fig. 11 — Disconnect Switch Location — 48/50EJ,EK,EW,EY Units

9
d. Attach field-supplied disconnect switch and field-
supplied 4-in. length of ROMEX cable to the
mounting bracket.
e. Slip flange of mounting bracket under top cover
flange, between top cover and side of unit. Line up
holes in mounting bracket with screw holes in unit.
f. With screws removed in Step a, attach mounting
bracket to unit.
g. Connect ROMEX cable to unit. Seal penetration
with RTV sealant to prevent rain water from being
drawn into the unit.
Size 008-014 Units:
A mounting bracket is not required. Disconnect switch
mounts directly onto the unit. See Fig. 15 and 16 for
location of disconnect switch on size 008-014 units.
Drill 0.875-in. hole in side of unit for wiring to discon-
nect switch. See Fig. 16 for wiring hole location.
Match up wiring hole in disconnect switch with wiring
hole drilled into side of unit. Mount disconnect switch
to unit with 4 self-tapping screws (field-provided).
Seal disconnect switch housing with RTV sealant to
prevent rain water from being drawn into the unit.
5. A separate source power supply must be routed to the
accessory germicidal lamp’s unit mounted disconnect
switch per applicable codes. Unit wiring and control
box connections should not be used. Refer to the Pack-
age Usage table for electrical characteristics of power
supply. Power source must be a suitable fused,
grounded, protected source with the correct voltage.
Other voltages will permanently damage the germi-
cidal lamp.
Wire per Table 1.
6. Any hinged potential access panel or door to the instal-
lation area must be interlocked with the accessory
power source to turn the lamp off if the door is opened.
Access doors should be labelled with appropriate
warnings about exposure to ultra-violet light.
A pushbutton door interlock switch (Carrier Part No.
HR54ZA101) is required on all hinged access panels.
Use a field-fabricated and -installed bracket to mount
the door interlock switch. See Fig. 17 and 18. Drill
0.406-in. hole in unit z-flange 1.75-in. from end of
door for pushbutton of interlock switch. Push button
will go through unit z-flange and will be contacted by
door. See Fig. 15.
Use insulated sleeve terminals for connection to inter-
lock switch. The pushbutton door interlock switch is
not required on non-hinged access panels. Door inter-
lock switch should be located on the side of the access
door that opens. Locate the switch near the top of the
door so it will not be in a location where it interferes
with maintenance or service.
Run wiring into disconnect switch. Door interlock
switch should be wired into the power (Black) lead,
between the disconnect switch and the germicidal
lamp, to break power to the accessory when the door is
opened.
7. Using the accessory as a template, mark two 1-in.
insertion holes on the mounting surface. Mark 8 holes
for accessory mounting. See Fig. 3 and 4 for location.
The 1-in. holes are used for electrical connections and
the germicidal bulb. See Fig. 5.
8. Drill 1-in. holes in unit where marked.
9. Use field-supplied No. 10 self-drilling screws to attach
accessory to unit.
NOTE: Holes can be drilled in unit if self-drilling
screws are not used. Drill 8 holes for eight no. 10
screws used to attach accessory to unit. Using eight no.
10 screws provided, attach accessory to unit.
Be sure accessory has a watertight seal against unit
wall. Use standard 1/2-in. strain relief connectors
when running wiring through any hole in unit.
10. Wire accessory germicidal lamp to disconnect switch.
See Table 1 for wiring recommendations. Use UVC
resistant wire, outdoor duty, 14-gage ROMEX cable or
1/2-in. conduit for all wiring. Wire power, neutral, and
ground leads to disconnect switch. Do not ground to
unit. Ultra-violet lamps should be operated continu-
ously from power source. Lamps should not be con-
nected to indoor fan power source or any power source
where they would be cycled more than twice per day.
Be careful not to drill into coil, refrigerant lines, or other
objects inside the HVAC unit. Damage to unit can result.
Fig. 12 — Junction Box Installation — 48/50EJ,EK,EW,EY Units (48EJ024 Shown)

10
NOTE: If door interlock switch is used, black power
lead will be connected to the door interlock switch wir-
ing (not to the disconnect switch).
11. Locate the germicidal bulb. DO NOT TOUCH
GLASS ON BULB. Grasp the bulb only by the base
(non-glass part). Clean the bulb using a lint free wipe
and isopropyl alcohol. Make sure O-ring on bulb is
toward the accessory and push into the 1-in. hole until
seated. Hold the bulb in place and lock into place by
installing the spring wire fastener to the lances on the
bulb.
12. Push on the power plug. Do not force. Rotate
90 degrees if necessary.
13. Affix the ultra-violet light warning label to the outside
of the unit, in plain sight, on all access doors. Replace
label when worn. See Fig. 10.
14. Test all circuits and return power to unit. Accessory
bulb should glow with a blue hue. If bulb cannot be
seen briefly back out bulb and view from safe distance.
replace bulb when done. If bulb does not glow, check
wiring, safety interlock, or replace bulb.
MAINTENANCE
Disconnect all power before performing any maintenance
or service.
Bulbs need periodic replacement to maintain design specifi-
cations. Replace bulbs after 6000 hours of operation or 1 year,
whichever comes first. For best performance, replace bulbs at
the beginning of each cooling season.
Bulb output can also be checked with a UVC radiometer.
Replace bulb when output falls to 70% of initial reading
The following bulbs can safely be used with this accessory:
• CRSGLTUB001A00 (16-in. tube)
• CRSGLTUB002A00 (20-in. tube)
• CRSGLTUB003A00 (24-in. tube)
• CRSGLTUB004A00 (30-in. tube)
• CRSGLTUB005A00 (36-in. tube)
Other bulbs may plug into the accessory, but they should not
be used. Non-approved bulbs will overheat bulb and power
source. Normal operation temperature for the bulb is 80 F. Nor-
mal operation temperature for the power source is 125 F.
OPERATION
While lit, bulb color should be light blue. If bulb color
changes to red or flickers, replace the bulb. Bulbs that are not
light blue will not emit ultra-violet radiation and will not kill
harmful bacteria or fungi.
Fiberglass filter media are recommended for operation of
HVAC when filters are exposed to ultra-violet lamps. Polyester
or cotton filters are subject to ultra-violet degradation and are
not recommended.
Use only specified high-output, low temperature bulbs with
this accessory. Use of a lower wattage or incorrect bulb can
result in damage to accessory or bulb. Correct bulbs have a
blue end cap.
7.0
6.1
3.5 .25.59
2.875
.25
.31
2 PLACES
2.32
.32 ROUND SHARP
CORNERS
2 PLACES
2.37 .875
1.46
ROUND SHARP
CORNERS
2 PLACES
1
.25
4 PLACES
4
18 GA GALVANIZED
STEEL OR
EQUIVALENT
Fig. 13 — Disconnect Switch Field-Fabricated Mounting Bracket
(48/50HJ,TJ004-007 and 50HJQ004-007 Units Only)
NOTE: Dimensions are in inches.

11
.22"
.17"
3.25
0.5"
0.5"
.53" 1.125"
FRONT VIEW
0.875"
1.09
1.45"
SIDE VIEW
GERMICIDAL LAMP TO POWER
SUPPLY
Z-FLANGE DOOR INTERLOCK
SWITCH RAIN PROOF
LIGHT SWITCH
DISCONNECT
1.75"
Fig. 14 — Disconnect Wiring Hole Location
(48/50HJ,TJ004-007 and 50HJQ004-007 Units Only)
Fig. 15 — Typical Germicidal Lamp Installation —
48/50HJ,TJ008-014 and
50HJQ008-012 Units Shown
Fig. 16 — Disconnect Switch Wiring Hole Location
(48/50HJ,TJ008-014 and 50HJQ008-012 Units Only)
NOTE: Dimensions are in inches.
NOTES:
1. Use 18 gage galvanized steel.
2. Dimensions are in inches.
Fig. 17 — Field-Fabricated Door
Interlock Switch Bracket Details
(48/50HJ,TJ004-014 and 50HJQ004-012 Units Only)
Fig. 18 — Interlock Switch Installation
(48/50HJ,TJ004-014 and 50HJQ004-012 Units)
NOTE: Dimensions are in inches.
NOTE: Dimensions are in inches.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-734 Printed in U.S.A. Form 48/50-51SI Pg 12 4-99 Replaces: New
Book111444
Tab 1a1b5a5a6a6b
Copyright 1999 Carrier Corporation
This manual suits for next models
2
Table of contents
Popular Outdoor Light manuals by other brands

Claessens' Kids
Claessens' Kids Kid’Sleep Aquarium quick start guide

iGuzzini
iGuzzini LIGHT UP BB38 instruction sheet

LEMAX
LEMAX Tinseltown Plaza instructions

IKEA
IKEA FLUGBO 805.083.49 manual

GLUCKSTEIN ELEMENTS
GLUCKSTEIN ELEMENTS 39454-HBCLED Use and care guide

Saxby Lighting
Saxby Lighting Ware Outdoor Wall Instruction leaflet