
IOM-P72
SECTION IV
IV. STARTUP
SECTION V
V. SHUTDOWN
SECTION III
III. PRINCIPLE OF OPERATION
1. Movement occurs as pressure variations regis-
ter on the piston (5). The registering pressure
is the outlet, P2, or downstream pressure. The
range spring (28) or loading pressure (for dome
loaded or ratio loaded designs) opposes piston
(5) movement. As outlet pressure drops, the
range spring (28) or loading pressure pushes the
piston (5) down, opening the port; as outlet pres-
sure increases, the piston (5) pushes up and the
port opening closes.
2. A complete piston (5) failure will cause the regula-
tor to fail open.
For Spring Loaded Design the maximum outlet
pressure is indicated on the body as the upper range
spring pressure level, and is the recommended “upper
operative limit” for the sensing piston (see Section IV.
Startup, Step 7).
For Dome & Ratio Loaded Design the max outlet
pressure is 1500 psig (103.4 barg).
Max loading pressure for Ratio Loaded Design is 105
psig (7.2 barg).
DO NOT HYDROSTATIC TEST THROUGH AN
INSTALLED UNIT; ISOLATE FROM TEST.
CAUTION
1. Start with the block valves closed. A bypass
valve may be used to maintain outlet pressure
in the downstream system without changing the
following steps.
2. Relax range spring (28) by turning the knob (38)
counter clockwise (CCW) until rotation comes to
a complete stop; or remove the loading pressure
for dome loaded or ratio loaded designs.
3. If it is a “hot” piping system, and equipped with
a bypass valve, slowly open the bypass valve
to preheat the system piping and to allow slow
expansion of the piping. Closely monitor outlet
(downstream) pressure via gauge to ensure not
over-pressurizing. NOTE: If no bypass valve is
installed, extra caution should be used in starting
up a cold system; i.e. do everything slowly.
4. Crack open the outlet (downstream) block valve.
5. Slowly open the inlet (upstream) block valve ob-
serving the outlet (downstream) pressure gauge.
Determine if the regulator is flowing. If not, slowly
rotate the regulator knob (38) clockwise (CW) or
increase the loading pressure until flow begins.
6. Continue to slowly open the inlet (upstream) block
valve until fully open.
7. Continue to slowly open the outlet (downstream)
block valve, especially when the downstream pip-
ing system isn't pressurized. If the outlet (down-
stream) pressure exceeds the desired pressure,
close the block valve and go to Step 2, then return
to Step 4.
8. When flow is established steady enough that the
outlet (downstream) block valve is fully open,
begin to slowly close the bypass valve if installed.
9. Develop system flow to a level near its expected
normal rate, reset the regulator set point by turn-
ing the knob (38) (CW) to increase outlet pressure
or (CCW) to reduce outlet pressure. Adjust the
loading pressure for dome or ratio loaded designs.
10. Reduce system flow to a minimum level and ob-
serve set point. Outlet pressure will rise from the
set point of Step 9. The maximum rise in outlet
pressure on decreasing flow should not exceed
the stated upper limit of the range spring (28) by
greater than 10%; i.e. 2-100 psig (.14-6.9 Barg)
range spring (28).
Do not walk away and leave a bypassed
regulator unattended.
CAUTION
1. On systems with a bypass valve, and where sys-
tem pressure is to be maintained as the regulator
is shut down, slowly open the bypass valve while
closing the inlet (upstream) block valve. Fully
close the inlet (upstream) block valve. (When on
bypass, the system pressure must be constantly
observed and manually regulated. Close the
outlet (downstream) block valve.
2. If the regulator and system are to both be shut
down, slowly close the inlet (upstream) block
valve. Close the outlet (downstream) valve only
if regulator removal is required.