• Near bedrooms and living areas.
• On each level of your home.
• 1 to 3 meter away from all fuel burning applianc-
es.
• At eye level to allow optimum monitoring of the
indicator lights.
2. AREAS WHERE NOT TO INSTALL
CO ALARMS:
• In an enclosed space (for example in a cup-
board or behind a curtain).
• Where it can be obstructed (for example by fur-
niture).
• Directly above a sink.
• Next to a door or window.
• Next to an extractor fan.
• Next to an air vent or other similar ventilation
openings.
• In an area where the temperature may drop below
-10 °C or exceed 40 °C.
• Where dirt and dust may block the sensor.
• In a damp or humid location.
• In the immediate vicinity of a cooking appliance.
4. PLACEMENT:
The CO alarm is designed to be installed on the
wall or a ceiling.
5. INSTALLING YOUR CO ALARM:
CAUTION: This alarm should be installed by
a competent person.
The installation of this device should not be
used as a substitute for proper installation,
use and maintenance of fuel burning appli-
ances, including appropriate ventilation and
exhaust systems.
It does not replace a smoke alarm.
Installation with screw and plug:
Detach the alarm from the mounting base by twisting
counter clockwise.
Use the mounting base to mark up horizontally
the screw holes on the wall.
Attach the alarm by twisting clockwise.
Please note: The label in the product must not
be removed as it contains important information
regarding the product.
UK
Carbon monoxide alarm device
Commercial reference : 4002
Developed by CAVIUS
PLEASE READ THE USER GUIDE CAREFULLY
BEFORE USE AND RETAIN FOR FUTURE USE!
This Cavius carbon monoxide (CO) alarm is de-
signed and tested to detect CO in private homes,
camping trailers, mobile homes and caravans. It
will provide early warning of the presence of CO.
SAFETY INSTRUCTIONS:
The device comes with a 3V lithium battery. Bat-
teries are to be handled with care and battery pow-
ered devices should be kept out of reach of chil-
dren. Do not try to recharge or burn the batteries.
Information about carbon monoxide:
CO - Carbon monoxide - is known as the “silent
killer” because it is odourless, tasteless and co-
lourless. It can kill in few minutes. This apparatus
may not prevent the chronic effects of Carbon
Monoxide exposure.
All people are at risk for CO poisoning. Unborn ba-
bies, infants, the elderly, and people with chron-
ic heart disease, anemia, or respiratory problems
are generally more at risk than others.
The apparatus will not fully safeguard individuals
at special risks
Breathing CO can cause headache, dizziness,
vomiting, and nausea. If CO levels are high
enough, you may become unconscious or die.
1. TECHNICAL INFORMATION:
Diameter: 40mm Height: 38m.
Type of alarm: Type B apparatus with elec-
tro-chemical CO sensor.
Battery: Powered by a non-replaceable 3V
CR123 Lithium battery with 10-year life (included).
IMPORTANT: Do not try to replace the bat-
tery. Replace the product if the battery fails.
Product Life: 10 years after manufacturing date.
Complies to standards: EN50291-1:2018,
EN50270, EN50271, EN60335, RoHs, REACH.
Working condition: -10 to +400C, 30 to 95% non-con-
densing.
Storage/Transport: -20 to +500C, 10 to 95% non-
condensing.
Alarm Sound Level: The minimum sound level is 85
dB at 3 meters.
2. THE BEST AREAS TO INSTALL YOUR CO
ALARM:
• Ideally, an apparatus should be installed in every
room containing a fuel-burning appliance.
Peak ceiling
Minimum 30cm
from peak
Minimum 30cm
from wall
Wall
Ceiling
Sounder
Yellow LED
Fault indicator
Green LED
Power indicator
Test/ hush
button
Mounting
base
Red LED
Alarm indicator
Minimum 15cm from ceiling
Wall
Ceiling
Minimum 1,20m to 1,50m from the oor
Floor
Recommended CO alarm location
Mark up screw holes with a pen
Use the enclosed screws
and plugs for installation
1 to 3m from replace
Wall
Developed by CAVIUS Aps Julsøvej 16, DK-8600
Manufactured in P.R.C.
The CE mark affixed to this product confirms its
compliance with the European Directives which
apply to the product.
All Rights reserved: CAVIUS Aps assumes no re-
sponsibility for any errors, which may appear in
this manual. Furthermore, CAVIUS Aps reserves
the right to alter the hardware, software, and/or
specications detailed herein at any time with-
out notice, and CAVIUS Aps does not make any
commitment to update the information contained
herein. All the trademarks listed herein are owned
by their respective owners. Copyright © CAVIUS
Aps.
127290rev6
6. TEST FUNCTION:
After installation and at least once per quarter, test
your alarm to make sure it is operating correctly.
It is recommended to check visually every week
if the green LED ashes correctly (every minute)
When the top button is pressed the alarm sound-
er will sound, and when the button is released,
the alarm will make a self-test of the sensor and
battery for approximately 9 seconds. During this
delay the three LEDs will be ashed in sequence.
The result of the test will be indicated after the test
has been completed.
If the test passes, the green LED will emit for 3
sec. If the test fails, a fault indication will be given
(See section 11).
After the test function is performed, the alarm will
need to recover for one minute before the next
test can be done (to allow the sensor chamber to
re-settle after the test current is applied).
The alarm will also do a self-test every 24 hour
and test the sensor for faulty sensor, drift or short
circuit.
TIP: It is safe to cover the sound output hole with
your nger during the testing to minimize the
sound level emitted.
7. NORMAL MODE:
In normal mode, POWER indicator (Green LED)
will ash every 60 seconds
8. ALARM MODE:
When a dangerous concentration of CO is detect-
ed, the CO alarm will go into ‘Alarm Mode’. It will
be indicated by a series of repeated tones and the
red LED will ash every 0.5 second.
9. WHAT TO DO IF THE ALARM SOUNDS:
• Keep calm and open all doors and windows.
• If the alarm continues to be activated, then evac-
uate the premises.
• Get medical help for anyone suffering the effects
of carbon monoxide poisoning.
• Call the appropriate emergency central
10. HUSH FUNCTION:
Hush of the alarm is only possible under a level
of 200ppm. If you cannot hush the alarm, please
refer to section 9.
When the alarm is under CO alarm warning, it can
be silenced for about 10 minutes by pressing the
TEST/HUSH button.
When battery fault the indication can also be si-
lenced for up to 8 hours by a short press on the
TEST/HUSH button. This function can only be
carried out once during a fault.
11. FAULT WARNINGS:
Battery fault: Battery low condition is indicated
by a very short tone burst “beep” every 60 sec-
onds with yellow LED flashing. Your CO alarm
battery is low voltage.
Sensor fault: Sensor fault is indicated by two
very short tone burst “beeps” every 60 seconds
with yellow LED ashing. Your CO alarm will not
respond to CO.
End of life: End of sensor life is indicated by three
very short tone burst “beeps” every 60 seconds
with yellow LED ashing. Your CO alarm needs
to be replaced.
12. MAINTENANCE:
• Check if the alarm sounds and indicators
flash properly by pressing TEST/HUSH button
at least once per quarter.
• Your alarm should be vacuum cleaned once per
• quarter to remove dust and dirt. It can be wiped
with a damped cloth. Never use detergents or oth-
er solvents to clean the unit.
• Never attempt to disassemble the unit or clean
inside.
• Commonly occurring materials, vapours or
gases, e.g. in cleaning uids, polishes, paints,
cooking operations, etc., may affect the reliabili-
ty of the alarm in the short or long term.
• When household cleaning supplies or similar con-
taminants are used, the area should be venti-
lated.
• Please do not expose to rain or moisture and do
not knock or drop the detector. Open or tamper
with the alarm could cause malfunction.
Visual and sound patterns:
13. OTHER INFORMATION:
Do not paint the alarm.
Disposal: Please dispose the product properly
at the end of life. This is electronic waste which
should be handled properly.
WARNING: Batteries shall not be exposed to ex-
cessive heat such as shine, re, or the like. Note
the local country regulations regarding installa-
tion.
WARNING: To prevent injury, this apparatus must
be permanently xed to the ceiling/wall in accor-
dance with the installation instructions.
Normal mode
Alarm mode
Test pass
Battery fault
Sensor fault
End of life of
sensor
Short ash green
LED every 60sec
Sound sweep
with red LED
Green LED will emit for
3sec
1 beep every 60sec with
yellow LED
2 beeps every 60sec
with yellow LED
3 beeps every 60sec
with yellow LED --- --- --- ---
- - - -
- - - -
-- -- -- --
EN50291-1:2018
EN50291-2:2010
www.cavius.com

Other Cavius Security System manuals

Cavius CO ALRM User manual

Cavius

Cavius CO ALRM User manual

Cavius CV4002 User manual

Cavius

Cavius CV4002 User manual

Cavius CV3106 User manual

Cavius

Cavius CV3106 User manual

Cavius FLOOD User manual

Cavius

Cavius FLOOD User manual

Cavius 5103 User manual

Cavius

Cavius 5103 User manual

Cavius HEAT User manual

Cavius

Cavius HEAT User manual

Cavius FLOOD User manual

Cavius

Cavius FLOOD User manual

Cavius 3004-001 User manual

Cavius

Cavius 3004-001 User manual

Popular Security System manuals by other brands

BW Technologies Micro Clip XT Operator's manual

BW Technologies

BW Technologies Micro Clip XT Operator's manual

Risco LIGHT SYS 2 Quick user guide

Risco

Risco LIGHT SYS 2 Quick user guide

DAM MADCAT TOPCAT manual

DAM

DAM MADCAT TOPCAT manual

Meridian Euro user manual

Meridian

Meridian Euro user manual

First Alert 3035DF Operations & installation guide

First Alert

First Alert 3035DF Operations & installation guide

Advanced Axis AX-CTL-1L Installation & operation manual

Advanced

Advanced Axis AX-CTL-1L Installation & operation manual

Arexx TL-ALU9 user manual

Arexx

Arexx TL-ALU9 user manual

Lorex SG6350 instruction manual

Lorex

Lorex SG6350 instruction manual

System Sensor SpectrAlert Series Installation and maintenance instructions

System Sensor

System Sensor SpectrAlert Series Installation and maintenance instructions

KE2 EvapOEM troubleshooting guide

KE2

KE2 EvapOEM troubleshooting guide

HomeAware HA360US Installation and setup guide

HomeAware

HomeAware HA360US Installation and setup guide

DSC PK5500 installation instructions

DSC

DSC PK5500 installation instructions

Siemens FDM221 Technical manual

Siemens

Siemens FDM221 Technical manual

Techko S082K Operation manual

Techko

Techko S082K Operation manual

Axis T8343 installation guide

Axis

Axis T8343 installation guide

Honeywell Lynx Plus Series user guide

Honeywell

Honeywell Lynx Plus Series user guide

Krypto Security HK2 Installation and operation manual

Krypto Security

Krypto Security HK2 Installation and operation manual

AEI Security & Communications DE40BWB installation guide

AEI Security & Communications

AEI Security & Communications DE40BWB installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.