manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cedes
  6. •
  7. Security Sensor
  8. •
  9. Cedes cegard/Pro CabSafe 2D User manual

Cedes cegard/Pro CabSafe 2D User manual

CabSafeä Door Protection
Quick Start Guide
Thank you for purchasing the CEDES CabSafe elevator
door protection system. This “Quick Start” guide
provides basic information for the system concept. This
document does not replace the installation and operating
instructions for the components included in this kit and
available online at www.cedes.com.
Consult the installation and operation instructions
relevant to the individual devices included in this kit for
additional information regarding the system, additional
warnings, requirements and device-specific
specifications:
115 944 CabSafe System Operating Manual; and
116 106 cegard/Pro (CabSafe 2D) Operating Manual
Download these documents at: www.cedes.com.
For glass elevators, please see operating instructions
for additional requirements.
Important Notes:
• This door protection system must only be installed and
commissioned by qualified elevator installation
personnel.
• Before beginning installation of this door protection
system, you must be sure that the elevator has been
properly placed “Out of Service” to ensure that the
elevator and related components will not be allowed to
move during the installation. You must follow all
applicable safety protocols, rules and regulations that
apply.
• Upon completion of the installation and
commissioning of this door protection system,
qualified elevator installation personnel must ensure
that the installation complies with all applicable local,
regional and national regulatory requirements, and
that the operation of the elevator control system,
including this light curtain, perform in accordance with
the application and regulatory requirements.
System Overview:
This CabSafe system is designed for use as part of an
elevator door protection system in accordance with
ASME ANSI A17.1-2019 / CSA B44-19. The CabSafe
2D forms an invisible field of criss-cross beams that
detect the presence of persons or objects between the
doors. The CabSafe 3D detects persons or objects
approaching the elevator entrance. These devices are
connected to a CabSafe Controller. When an object is
detected, the output from the CabSafe controller
changes state to indicate that the doors should be
reopened since a person or object is present in the
respective detection field.
CabSafe 2D (cegard/Pro):
The CabSafe 2D transmitter and receiver are normally
mounted on the doors in a center-opening application or
on the door and the slam post in a side-opening
application. The maximum door speed should be less
than 0.5 m/s (1.64 ft/s). The lowest beam must be less
than 25 mm (1 inch) from the sill. The optical Axis must
be within ± 5˚ between the transmitter and receiver.
Attach a felt strip in the center of the associated
mounting or spacer profile to reduce any vibration that
might occur. Once the CabSafe 2D components are
mounted, connect the cables from the devices to the
CabSafe Controller. Then secure the cables in place,
allowing enough slack so that they can bend freely,
without becoming snagged on moving parts. Use cable
guide wires on door(s) to prevent excessive cable sway.
CabSafe 3D:
The CabSafe 3D is a time-of-flight (TOF) transom-
mounted device that projects a detection field in front of
the elevator cab entrance. For OEM applications where
the transom already has a cut-out for the sensor, the
mounting is straightforward using an optional backplate
included with the sensor and two (2) security screws
(spanner type).
The cable must exit right from the sensor as you
look into the cab (regardless of left-open, right-open
or center-open application).
The above figure shows a “Sensor Mounted in Center”
For center mounting applications, the sensor should be
centered in the opening as shown above. For side-
mounting applications, the sensor must:
• Be positioned no more than 240 mm (9.5 inches)
from the slam post (Distance “D”).
• Be less than 300 mm (12 inches) from the landing
side of the landing door (Distance “S”).
Route the cable from the CabSafe 3D to the CabSafe
controller. Connect the cable to the CabSafe 3D and
then secure the sensor in the transom. An optional
stainless-steel back of transom bracket is also available
for modernization applications.
CabSafe Controller:
CabSafe controllers are available with a wide ranging or
24 V DC ± 20% input power. The CabSafe sensor
components plug into the CabSafe Controllers the same
way for all variants. Namely,
• CabSafe 2D Transmitter = 3-pole Plug
• CabSafe 2D Receiver = 4-pole Plug
• CabSafe 3D Sensor = 6-pole Plug.
Power is connected to the corresponding pins on power
connector. See labels on device for details.
CabSafe 200 with
Relay Output
85-265 VAC /
19.2-37 VDC /
120-300 VDC
CabSafe 100 with
Relay Output
19.2-37 VDC
CabSafe 100 with
Solid-State Output
19.2-28.8 VDC
S
Optical
Axis
DIP Switch Configuration
All versions of the CabSafe controller are configured
using DIP switches. The switch settings are described
in the following paragraph. Switches should be
configured when power is off on the CabSafe Controller.
DIP SW 1 & 2 – CabSafe 3D Location
The CabSafe 3D location is the position of the sensor as
you look into the elevator cab from the landing side. For
side-opening applications, the CabSafe 3D must be
mounted on the same side as the slam post / strike jamb.
Function
DIP 1
DIP 2
No function
0
0
CabSafe 3D mounted on left
1
0
CabSafe 3D mounted on right
0
1
CabSafe 3D mounted in center
1
1
Distance “D” as shown below is 240 ± 10 mm (9.45 ± 0.4
inches).
The above figure shows a “Sensor Mounted on Right.”
The above figure shows a “Sensor Mounted on Left.”
DIP SW 3 & 4 – Door Closed Detection
Normally, the light curtain is able to detect when the
doors have reached a point when the CabSafe 3D can
be rendered inoperative. When the light curtain does not
move with the door(s), an external signal is used to
render the CabSafe 3D inoperative. The external signal
should transition less than 450 mm (18 inches) from full
close. For additional information, see operating manual.
Function
DIP 3
DIP 4
No function
0
0
Via Light Curtain
1
0
Via External Signal
0
1
DIP SW 5 – 8: Sensor Mounting Height
Select based on the mounting height of the CabSafe 3D.
Function
DIP 5
DIP 6
DIP 7
DIP 8
No function
0
0
0
0
6.67 – 7.5 ft
1
0
0
0
> 7.5 to 8.5 ft
0
1
0
0
> 8.5 to 9 ft
0
0
1
0
> 9 to 10 ft
0
0
0
1
DIP SW 9: 2D/3D Select
To fulfill ANSI A17.1-2019 / CSA B44-19, both the
CabSafe 2D and CabSafe 3D must be active. If DIP9 is
configured as 2D Only, the CabSafe 3D sensor must be
disconnected from the CabSafe Controller.
Function
DIP 9
2D and 3D Both Active
0
2D Only (3D must be disconnected)
1
DIP SW 10: Output Logic Selector
This configuration changes the polarity of the output.
Function
DIP 10
Standard
0
Inverted
1
116 122 (210504A) Quick Start Guide CabSafe
CabSafe 100 Solid-state Output Variant
CabSafe 100/200 Relay Output Variant
DIP SW 11: 3D Frequency Selector
This setting is used to prevent interference between
CabSafe systems when elevators face one another.
Function
DIP 11
Frequency Range Group A
0
Frequency Range Group B
1
DIP SW 12: Reserved for future use.
An online support and troubleshooting
tool is available to assist with
installation and troubleshooting.
Scan the QR code This link is also
available at www.cedes.com under
Product Listing – CabSafe.
CEDES Corporation of America
Telephone: +1 612.424.8400
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2) this device must accept any interference
received, including interference that may cause
undesired operation.
Specifications subject to change without notice.
ON = 1
OFF = 0

Other manuals for cegard/Pro CabSafe 2D

1

This manual suits for next models

1

Other Cedes Security Sensor manuals

Cedes GridScan/Mini-SB2 User manual

Cedes

Cedes GridScan/Mini-SB2 User manual

Cedes TOF/Start User manual

Cedes

Cedes TOF/Start User manual

Cedes cegard/Lift LI Owner's manual

Cedes

Cedes cegard/Lift LI Owner's manual

Cedes GridScan/Mini-SR User manual

Cedes

Cedes GridScan/Mini-SR User manual

Popular Security Sensor manuals by other brands

Autonics CR Series product manual

Autonics

Autonics CR Series product manual

ADEMCO 655 installation instructions

ADEMCO

ADEMCO 655 installation instructions

Rohm BH1730FVC-TR Technical notes

Rohm

Rohm BH1730FVC-TR Technical notes

United Technologies Interlogix RF440I4 Installation sheet

United Technologies

United Technologies Interlogix RF440I4 Installation sheet

HST HM201-SC Installation and maintenance instructions

HST

HST HM201-SC Installation and maintenance instructions

Innovative Technology CCE 15 Short manual

Innovative Technology

Innovative Technology CCE 15 Short manual

Pilz PNOZ mmc2p operating manual

Pilz

Pilz PNOZ mmc2p operating manual

Motorola HMWS1060 Specifications

Motorola

Motorola HMWS1060 Specifications

jablotron JA-120PC manual

jablotron

jablotron JA-120PC manual

Rielta IPDL-Ex installation guide

Rielta

Rielta IPDL-Ex installation guide

RKI Instruments 35-3001A-01 Operator's manual

RKI Instruments

RKI Instruments 35-3001A-01 Operator's manual

Nivel System RD800 DIGITAL instruction manual

Nivel System

Nivel System RD800 DIGITAL instruction manual

Ludlum Measurements 44-7 manual

Ludlum Measurements

Ludlum Measurements 44-7 manual

Smartwares SH5-TSO-A quick start guide

Smartwares

Smartwares SH5-TSO-A quick start guide

RKI Instruments 35-3010RK-06-02 manual

RKI Instruments

RKI Instruments 35-3010RK-06-02 manual

Gordon Ellis Prima quick start guide

Gordon Ellis

Gordon Ellis Prima quick start guide

GEV LBC 18280 manual

GEV

GEV LBC 18280 manual

Bacharach H-10 PRO instruction manual

Bacharach

Bacharach H-10 PRO instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.