• Under Parameters > Temperature ensure
the values are set as follows:
• Switching type = On/O
• Switching Dierential = 1.0°C
• Sensor Selection, Radiators = Built In,
Underoor = Built In and Floor Sensor.
Floor sensing only also available.
• Room Temp > Sensor Oset/Calibration
= Used to calibrate the temperature
measured at the thermsotat
• Floor Temp > Min (Heating) = 20°C,
Max (Heating) = 30°C. This will
vary dependant on oor coverings.
• Floor Temp > Min (Cooling) = 15°C,
Max (Cooling) = 20°C. This will
vary dependant on oor coverings.
• Floor Temp > Sensor Oset/Calibration
= Used to calibrate the temperature
measured at the oor probe.
• Floor Temp > Dew Point Check = Disabled
• Set point > Min = 10°C, Max = 35°C. Can be
adjusted 0-99°C for various applications.
• Optimum Start/Stop = Disabled
• Factory Reset > If required the thermostat can be
set back to the default factory settings by holding
this down for 10 seconds.
Note: If Factory Reset is done the thermostat will
power on in the Stop System state, you will need
to enter the Advanced Settings menu again and
under Setup select Start System.
• Please refer to the user manual for pairing of
App, changing modes and setting up time
schedules etc.
• Note: When thermostat looses power or the
advanced menu is being access the 0-10V
humidity output will drop o. This can cause a L5
error on a Chofu heat pump using humidity input
for radiant cooling. Error must be manually reset
at heat pump controller.