Important Safety Warnings
This manual contains instructions and warnings that should be followed during the
installation, operating and storage of the UPS system. Please keep this manual for
further reference.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area free of conductive contaminants. (See the specifications for the
acceptable temperature and humidity range)
CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and
avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances
such as radiators.
CAUTION! Do not plug the UPS input into its own output.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages
or any other liquid-containing vessels on or near the unit.
CAUTION! In the event of an emergency, press the OFF button and disconnect the power
cord from the AC power supply to completely disable the UPS.
CAUTION! The UPS installation must be correctly ground in order to reduce leakage current
below 3.5mA.
Attention The UPS output is supplied by two sources. When the UPS is disconnected from
mains power, hazardous voltage may still be present from the internal battery. The battery
should be disconnected when maintenance or service work inside the UPS is necessary.
CAUTION! Servicing of batteries should be performed or supervised by qualified personnel
only.
CAUTION! When replacing the batteries, use the same number and type of batteries.
CAUTION! Dispose of batteries in the correct manner and in line with local laws and
regulations. Never dispose of batteries in a fire. Do not attempt open the battery. Released
electrolyte is harmful to the skin and eyes.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
CAUTION! A battery can present a risk of electric shock and short circuit.
CAUTION! This is a category C2 UPS product. In a residential environment, this product may
cause radio interference, in which case the user many be required to take additional measures.
Designed and Engineered by:
Power Control Ltd
www.certaups.com
Specifications
MODEL
C60-800
C60-1000
C60-1500
C60-2000
CAPACITY
800VA/480W
1000VA/600W
1500VA/900W
2000VA/1200W
INPUT
Input Voltage
220/230/240VAC
Voltage Range
162-290VAC
OUTPUT
Voltage Regulation
+/-10%
Transfer Time
Typical 2-6ms, 10ms max.
Waveform
Simulated Sinewave
BATTERY
Type & Number
12V/9Ah x 1
12V/7Ah x 2
12V/9Ah x 2
12V/9Ah x 2
Charging Time
4-6 hours recover to 90% capacity
PHYSICAL
Dimension
(WxDxH) mm
100 x 287 x 142
146 x 350 x 160
146 x 397 x 205
Net Weight (KG)
4.9
8.0
11.1
11.5
C60 Uninterruptible Power Supply
User Manual
Installation & Operation
Initial Set-up
After unpacking the unit, please avoid placing the unit in direct sun light, excessive heat,
excessive humidity or in contact with fluids of any type. Please allow 20cm space around the
unit.




Connect Mains Power
Plug the UPS into an electrical outlet that does not share a circuit with any other heavy
electrical load. Please allow the UPS to charge at least 6 hours prior to use.

Connect Equipment
Connect critical equipment to the battery backup outlets, these are supported automatically
when a mains failure occurs. Connect other equipment that needs only surge suppression to
the surge protected outlets. Power is not supplied to these outlets when the unit is switched off.
Therefore, please be sure to switch on the unit.
NOTE: Please DO NOT connect scanners or printers to the battery backup outlets.

Connect Modem/Phone/Network for Surge Protection
Connect a single modem/phone line into surge-protected “IN” outlet on the back panel of the
UPS unit. Connect from “OUT” outlet to the computer with another phone line cable.
Connect Communication Port
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB port and the other to the communication port of your
PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and
monitor UPS status through PC.
Software Installation
1) Please download the monitoring and shutdown software from the website
www.certaups.com/downloads to download ViewPower software.
2) When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
Power On/Off UPS
Press power switch on the front panel of the UPS to turn on the UPS. Press switch again to turn
off the UPS.
Front Panel & Back Panel
LCD panel
Power switch
C60-800 C60-1000 C60-1500/2000
Troubleshooting
Problem
Possible Cause
Solutions
Nothing displays on the
front panel.
Low battery
Charge the UPS at least 6 hours.
Battery fault
Replace the battery with the same
type of battery.
The UPS is not turned on
Press the power switch again to turn
on the UPS.
Alarm continuously
sounds when the
mains is normal.
The UPS is overloaded
Remove some load first. Before
reconnecting equipment, please
verify that the load matches the UPS
capability specified in the specs.
When power fails, the
back-up time is very
short.
The UPS is overloaded
Remove some critical load.
Battery voltage is too low
Charge the UPS at least 6 hours.
Battery defect. It might be due
to high temperature operation
environment, or improper
operation to battery
Replace the battery with the same
type of battery.
The mains is normal but
UPS is on battery mode.
Power cord is loose
Reconnect the power cord properly.
LCD Panel:
Input voltage Load level indicator, flashing
Output voltage indicates overload
AC mode indicator Battery capacity indicator, flashing
Battery mode indicator indicates low battery
Battery backup outlets
Surge protected outlets
AC input
USB communication port
Modem/Phone Line
/Network surge
protection

Other manuals for C60-800

1

This manual suits for next models

3

Other CertaUPS Power Supply manuals

CertaUPS C750 User manual

CertaUPS

CertaUPS C750 User manual

CertaUPS C60-800 User manual

CertaUPS

CertaUPS C60-800 User manual

Popular Power Supply manuals by other brands

Vimar Elvox 6942 Installer's guide

Vimar

Vimar Elvox 6942 Installer's guide

Assa Abloy SECURITRON BPSM-12-6 Operation and installation instructions

Assa Abloy

Assa Abloy SECURITRON BPSM-12-6 Operation and installation instructions

Pulsar PSC12030 quick start guide

Pulsar

Pulsar PSC12030 quick start guide

OCZ OCZ500SXS - MECHANICAL DRAWING Mechanical drawing

OCZ

OCZ OCZ500SXS - MECHANICAL DRAWING Mechanical drawing

Pulsar PSD12020 manual

Pulsar

Pulsar PSD12020 manual

Ultra Products X-Finity 2G ULT33120 user manual

Ultra Products

Ultra Products X-Finity 2G ULT33120 user manual

Hameg HM8040-3 manual

Hameg

Hameg HM8040-3 manual

T+A PS 3000 HV user manual

T+A

T+A PS 3000 HV user manual

Elenco Electronics XP-625 instruction manual

Elenco Electronics

Elenco Electronics XP-625 instruction manual

Siemens 7XV5810 0BA00 operating instructions

Siemens

Siemens 7XV5810 0BA00 operating instructions

Enterasys C2RPS-SYS installation guide

Enterasys

Enterasys C2RPS-SYS installation guide

Phoenix Contact SHDSL-PROFIBUS user manual

Phoenix Contact

Phoenix Contact SHDSL-PROFIBUS user manual

GW Instek GPE-1326 Series user manual

GW Instek

GW Instek GPE-1326 Series user manual

BEL TCP3500-1024G Installation instruction

BEL

BEL TCP3500-1024G Installation instruction

Honeywell GENT VCS-PSU-N Installation

Honeywell

Honeywell GENT VCS-PSU-N Installation

TAKASAGO HX-S-G4 Series instruction manual

TAKASAGO

TAKASAGO HX-S-G4 Series instruction manual

ecolight EC79772 user manual

ecolight

ecolight EC79772 user manual

Tescom NEOLINE PRO RT user manual

Tescom

Tescom NEOLINE PRO RT user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.