CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
INSTRUCTION MANUAL - Issue 1 - 02/2014 | 4
TESTING
Recommended Routine Test Procedure
The unit is designed to carry out self testing in accordance with (EN 62034:2006 3.6), (EN 62034:2006 3.7) & (EN 62034:2006 5.1).
The following test is designed to ensure the continued protection of your premises and occupants. Because of the possibility of a failure of the normal
lighting supply occurring shortly after a period of testing, all tests should, whenever possible, be undertaken at times of least risk, e.g. during daylight hours.
Once A Day
Visual inspection of battery charge led.
Once A Month
Each unit should be energised from it’s battery for adequate time to ensure, by simulation of a failure of the normal lighting supply, the emergency mode is
functioning correctly.
Once Each Year
All units should be placed into emergency mode and checked that the duration provided by the battery meets the specied time period.
Forest ‘Self-Test’
• 20 hours after applying mains voltage a function test is automatically run (30 sec. The items checked are ‘emergency changeover and lamp.
• After a further 4 hours, an automatic 3 hour duration test is run. (If the test button is pressed for 5 sec. before the duration test has ended, the test is
aborted.)
• Following the rst duration test, regardless of whether or not this was passed, the weekly function test and yearly duration test are automatically started.
Manual Operation
TEST BUTTON GREEN LED STATUS
Press for about 1 second OFF Emergency mode for 1 second
Press for about 3 seconds Blinking Functional test for 30 seconds
Press for about 5 seconds Flashing Duration test
Press again for about 5
seconds
Functional Interruption of duration test