WYVERN CONVENTIONAL EMERGENCY LUMINAIRE
MOUNTING AND WIRING
The luminaire is suitable for both Indoor and Outdoor applications - Please make reference to the diagram below for Luminaire Assembly details.
SPECIFICATION
IP Rating IP65
Battery Voltage 2.4V 4mAh
Duration 3 hours
Battery Format 1 x 2 cells (4.4AH Nickel-Cadmium)
Lamp 8W 12" T5
Ballast Lumen Factor 0.25
Rated lumen Output 65 lumens
Rated Supply Voltage 230V 50Hz ±10%
Supply current 70mA (max)
Charging current 0.17-0.3 A
Discharge current 1.15 A Nominal
Ambient temperature range 0°C to +30°C and up to 80% Relative Humidity
Max continuous cell temp for 4-year battery life. 55ºC
Standards EN60598-2-22:1999, EN55015:1996, EN61547:1996
Weight 1.3Kg
Remove diffuser retaining screws
Remove hinged geartray-retaining screws
BESA box mounting option
Cable entry option
Drill start wall fixing
Cable entry option
Connect battery to the PCB on emergency luminaries before re-tting gear tray.
The luminaire should be mounted using the xing holes provided, on a sound at surface. If the luminaire is to be used in a weatherproof application, Please
ensure that all cable entry and xing points are suitably sealed. Route the incoming cables around the outside of the body well away from the control gear,
and make-o the conductors in the gear-tray mounted terminal block.