1.5 Recycling the Used Battery
•Do not dispose of the battery in a fire. Battery may explode. Proper disposal of battery is required. Refer
to your local codes for disposal requirements.
•Do not open or mutilate the battery. Released electrolyte is harmful to the skin and eyes. It may be toxic.
•Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries
and must be disposed properly. For more information, contact your local recycling/reuse or hazardous
waste center.
•Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact
your local recycling/reuse or hazardous waste center.
2 Installation
2.1 Initial Inspection
1. Visually examine if there is any damage inside and outside of packages in the process of the transportation. If
any damage, report it to the carrier immediately.
2. Verify the product label and confirm the consistency of the equipment.
3. If the equipment needs to be returned, carefully repack the equipment by using the original packing material
that came with.
2.2 Installation Environment
1. The UPS is designed for indoor use only and should be located in a clean environment with adequate
ventilation to keep the environmental parameters within the required specification.
2. Make sure that transportation routes (e.g. corridor, door gate, elevator, etc.) and installation area can
accommodate and bear the weight of the UPS, the external battery cabinet and handling equipment.
3. The UPS uses forced convection cooling by internal fans. Cooling air enters the module through ventilation
grills located at the front of the cabinet and exhaustedthrough grills located in the rear part of the cabinet. Please
do not block the ventilation holes.
4. Ensure that the installation area is spacious for maintenance and ventilation.
5. Keep the temperature of installation area around 30°C and humidity within 90%. The highest operating
altitude is 5,200 ft above sea level.
6. If necessary, install a system of room extractor fans to avoid formation of room temperature. Air filters are
necessary if the UPS is operated in a dusty environment.
7. It is recommended that you parallel the external battery cabinets to the UPS. The following instructions of
clearances are suggested:
•Keep a clearance of 40” from the top of the UPS for maintenance, wiring and ventilation.
•Keep a clearance of 36" back clearance, or install flex-conduit to allow for moving of cabinet to access
switches. When pushed toward wall, leave 6" of clearance for ventilation.
•Front clearance should be per local and NEC code.
8. For safety concerns, we suggest that you shall:
•Equip with CO2 or dry powder fire extinguishers near the installation area.
•Install the UPS in an area where the walls, floors and ceilings were constructed of fireproof materials.
9. Do not allow unauthorized personnel to enter the installation area. Assign specific personnel to keep the
UPS key.