Chenzhu GS8535-EX User manual

GS8535-EX
GYB13.1107
IECEx CQM14.0048
CZ.GS8535-EX.11(S)E-5.0/15.07
5
4
1
2
3
3
2
1
M3
8.0
XK06-014-00557
Connections
(1)
(2).
(3).
(4).
. This barrier adopts knock-down connector with screw terminals. The
intrinsically safe(IS for short) terminals (blue plugs) should be connected
to hazardous area devices and the non-IS ones (green plugs)to the safe
area devices.
Choose for the harzardous area the blue-marked wires. Its minimum
2
cross section area should be 0.5 mm ,and minimum dielectric strength
should be 500V.
The wirings in safe area and hazardous area must be separated,
and both have protection bushes.
A length of 8mm bared wire is locked by the M3 bolt. See as shown
below.
Installation
The isolated barrier should be located at safe area, according to
the related requirements in IEC60079-17(EN60079-17)and
IEC60079-19(EN60079-19).
GS8500-EX series isolated barrier are designed for mounting on
35mm DIN guide rail.
Installation according to the following steps:
(1). First make the bus-powered outlet locked into the guide rail;(If no
bus-powered function,omit this step);
(2). Make the upside of the barrier locked into the guide rail;
(3). Push the downside of the barrier in the rail.
Disassembly
(1).Insert a screwdriver (its edge length≤6mm)into the downside metal
lock of the barrier;
(2).Push the screwdriver upwards,then prize the metal lock downwards;
(3).Take the barrier out of the guide rail.
(1).Before using, please check again whether the module’s Ex-proof
rating accords to the operation conditions, and also wiring and polarity
are correct.
(2).It is disallowable to test insulativity among the terminals with a
megameter. If necessary, the wires must be cut off before testing ,or the
internal fuse would blow.
(3).Every product has been test strictly before leaving factory. If users
find any abnormality in the module, please contact the nearest agent or
our company.
(4).In 5 yeras from the delivery date, if the product works improperly
during normal operation, we will repair or replace it without payment.
Non-intrinsically safe terminals Intrinsically safe terminals
Maintenance
Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350 Fax : +86-21-64846984
Email:chenzhu@chenzhu-inst.com
http://www.chenzhu-inst.com
Isolated Barrier
User Manual
Caution
Please check whether the product type on the package accords
to the ordering contract;
Read this manual carefully before installation or using. If there is
something unclear, please dial technic support hotline-400 881 0780;
Isolated barrier should be located in the safe area;
Supply voltage is 24VDC, 220VAC is forbidden;
Users are not allowed to dismantle or repair the barrier otherwise
it will induce malfunction.
Please read the instruction manual carefully before use the product,
and please safekeeping.

Number of channels: 1/2
Supply voltage: 20~35V DC
Current consumption: mA (at 24Vdc supply,20mA output)
Safe-area output:
Current: 0/4~20mA, HART digital signal
Load resistance: RL≤300Ω
Load resistance: RL≥250Ω(HART)
Voltage: 0/1~5V
Load resistance: RL≥330kΩ
Output loop-powered: Power supply Ue=12~30V DC
Note: Users can specify current output or voltage output or output loop-
powered when ordering.
Hazardous-area input:
Current: 0/4~20mA, HART digital signal
Available voltage: Open circuit voltage: ≤28V
Voltage: ≥15.5V at 20mA
Normal working current: ≤25mA
each 90 of final value in 2ms
Power supply protection: Protect the barrier form reverse supply voltage
destroy
Electromagnetic compatibility: According to IEC 61326-1(GB/T 18268),
IEC 61326-3-1
Dielectric strength:
Between non-intrinsically safe part and intrinsically safe part≥2500VAC
Between power supply part and non-intrinsically safe part≥500VAC
Insulation resistance:
Between non-intrinsically safe part and intrinsically safe part≥100MΩ
Between power supply part and non-intrinsically safe part≥100MΩ
Weight: Approx.115g
Suitable location: Mounting in non-hazardous area,and connected to the
IS apparatus in zone 0 hazardous area.
Suitable IS apparatus:
2-wire HART transmitter,3-wire transmitter, current source
≤75
Transfer accuracy: 0.1%F.S.
Temperature drift: 0.005%F.S./℃
Response time: R %
National Supervision and Inspection Center for Explosion Protection
and Safety of Instrumentation(NEPSI)
Compliancy with standard: IEC60079-0(EN60079-0)
IEC60079-11(EN60079-11)
IEC60079-26(EN60079-26)
Ex-marking: [Ex ia Ga] ⅡC
maximum voltage: Um=250V
Intrinsic safety parameter:(7,8,9,10 terminals)
Uo=28V, Io=93mA, Po=651mW
ⅡC:Co=0.083μF , Lo=4.2mH
ⅡB:Co=0.65μF , Lo=12.6mH
ⅡA:Co=2.15μF , Lo=33.6mH
9,10 terminals:
Uo=3.5V, Co=100μF
Ui=20V , Ii=110mA, Ci=0μF, Li=0.54μH
(1) For distributed inductance and capacitance e.g. as in a cable, allow
the values of capacitance and inductance;
(2) For circuits containing up to 1 % inductance or up to 1%
capacitance with a cable, allow the values of capacitance and inductance;
(3) For connection of the combined inductance and capacitance where
both are greater than 1% of the allowed value (excluding the cable), allow
up to 50% each of the values of capacitance and inductance.
Largest external capacitance (Co) and inductance (Lo) numerical
attention when using the following requirements:
Application
Dimensions
118.9mm×106.0mm×12.5mm
Safety related application(SIL2)-
1.These models have been assessed for use in IEC61508 functional
safety applications.
2.Failure rates and safety-related parameters refer to the certificate.
Note: 1. It is not allowed to use HHC (HART hand-held communicator) in
hazardous area and safe area at the same time.
2.
must have EX certification.
HHC (HART hand-held communicator) used in hazardous area
SIL 2
IEC 61508
1 2 3
Safe-area
Hazardous-area
Summarize Operation Conditions
Specification
Intrinsic safety description
2-wire HART transmitter, 3-wire transmitter, current source input
isolated barrier(1 input, 2 outputs), provide isolated dc supplies for
transmitters which located in hazardous area. Transfer 4~20mA signal(or
current source signal) which generated by the transmitter form hazardous
area to safe area separately, also allows bi–directional transmission of
HART communication signals . The product needs an independent power
supply.Input circuit,output circuit and power supply are each galvanically
isolated.
(1). The air should not contain any medium corrupting the coat of
chrome,nickel and silver.Moreover,violent quiver and impact or any cause
of electromagnetic induction (such as big current or spark,etc.)must be
avoided when using.
(2). Operating temperature: -20℃~+60℃
(3). Storage temperature: -40℃~+80℃
(4). Relative humidity: 10%~90%
Intrinsic safety explosion protection loop system
Special requirements have to be confirmed before using the intrinsically
safe explosion loop system(intrinsically circuit) which connected by isolated
barrier and intrinsically safe apparatus in field:
(1) The explosion level of intrinsically safe apparatus should meet the
requirements of operation conditions. The apparatus should pass the
explosion protection test and get the certificate by state-authorized
explosion-proof product certification bodies.
(2) The intrinsic safety parameters of isolated barrier and intrinsically
safe apparatus both are sure, and comply with 12.2.5 of GB 3836.15-2000.
(3)If any parameters are unclear, the system has to be confirmed by
state-authorized explosion-proof product certification bodies.
IN OUT
2(-)
1(+)
6(-)
5(+)
-+
Power supply
4(-)
3(+)
HHC
HHC
Current
source
3-wire
Transmitter
7 (+)
8 (-)
9 (+)
10(-)
-
+
9
10
8/9
10
S
7
+
-
HHC
-
+
HHC
GS8535-EX
2-wire
Transmitter
Power supply
OUT1
OUT2
Other Chenzhu Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Nordson
Nordson EPC-15 instruction sheet

SAF
SAF Tire Pilot Plus troubleshooting guide

Midwest Specialties
Midwest Specialties FlexArm A-32 Installation & operation manual

Acoustic Signature
Acoustic Signature TA-9000 Neo instruction manual

BIG
BIG BBT40-SSL -135 Series Operation manual

EMUGE
EMUGE FRANKEN Softsynchro 6 Operating instruction

Smithco
Smithco Spray Star 1200 Parts & Service

ABB
ABB HT842293 Operation manual

WALTERSCHEID
WALTERSCHEID ZWL 30 Installation and operating instructions

PLX Technology
PLX Technology PEX 8624-AA RDK Hardware reference manual

RINGSPANN
RINGSPANN DV 025 PFM Installation and operating instructions

JUKI
JUKI AMS-221F instruction manual