
22 23
Object List - Modbus (FPC-02-OD-AB only!)
Modbus
Use DIP switch S6 located on the side of thermostat
to select BMS (A,B) network protocol - S6 OFF –
Modbus
MODBUS RTU Mode, Address Slave1-127,
Baud rate: 9600, n, 8, 1
Supported Commands:
0x03 = Read Holding Registers (for all).
0x06 = Preset Single Register (For R/W registers only),
Command 0x2B is used to identify controller
Object List - BACnet (FPC-02-OD-AB only!)
Use DIP switch S6 located on the side of
thermostat to select BMS (A,B) network
protocol - S6 ON – BACnet
N° Object Value Object Name Default Access
1 AnalogValue_#0 -10...25°C (14...77°F) SetPoint 3°C (37°F) R/W
2 AnalogValue_#1 -40...0°C (-40...32°F) LowLimitHeat -35°C (-31°F) R/W
3 AnalogValue_#2 1...6000 min HeatersOffDelay 90 min R/W
4 AnalogValue_#3 10...6000 min ManualPeriodTime 240 min R/W
5 AnalogValue_#6 10...1999 min StaggeringTime 120 min R/W
6 AnalogValue_#7 -40...35°C (-40...95°F) TemperatureOutside - R
7 AnalogValue_#8 0...6000 min HeatersOffTimeDelay - R
8 AnalogValue_#9 0...4 HeaterMode 0 R/W
9 AnalogValue_#20 -10...15°C (14...59°F) InternalTemperature(T3) - R
10 AnalogValue_#24 1… 4194303 BacnetDeviceInstanceNumber 315000+MAC R/W
11 AnalogValue_#29 0...2 TemperatureAquastatLogic 0 R/W
0 – No error 1 – Internal sensor 2 – External sensor
12 AnalogValue_#30 0...99 Sensors error 0 R/W
13 BinaryInput_#2 1-On,0-Off SettingMode - R
14 BinaryInput_#3 1-On,0-Off ShortTimeMode - R
15 BinaryInput_#4 1-On,0-Off StageringMode - R
16 BinaryInput_#5 1-On,0-Off StageringMode - R
17 BinaryInput_#8 1-On,0-Off Aquastat_Signal - R
18 BinaryOutput_#0 1-On,0-Off Heater 1 - R
19 BinaryOutput_#1 1-On,0-Off Heater 2 - R
20 BinaryOutput_#2 1-On,0-Off Heater 3 - R
21 BinaryOutput_#3 1-On,0-Off Heater 4 - R
22 BinaryOutput_#4 1-On,0-Off Heater 5 - R
23 BinaryOutput_#5 1-On,0-Off InternalHeater - R
24 BinaryValue_#0 1-On,0-Off OnOff 0-Off R/W
25 BinaryValue_#2 1-On,0-Off C_F_Scale 0-Off R/W
26 BinaryValue_#4 1-On,0-Off CommissioningMode 0-Off R/W
27 BinaryValue_#5 1-On,0-Off RestoreDefaults 0-Off R/W
28 BinaryValue_#14 1-On,0-Off GroundFault 0-Off R
N° Object Value Object Name Default Access
1 0 [0x00] -40...35°C (-40...95°F) TemperatureOutside - R
2 1 [0x01] -10...25°C (14...77°F) SetPoint 3°C (37°F) R/W
3 2 [0x02] -40...0°C (-40...32°F) LowLimitHeat -35°C (-31°F) R/W
4 3 [0x03] 1...6000 min HeatersOffDelay 90 min R/W
5 4 [0x04] 10...6000 min ManualPeriodTime 240 min R/W
6 5 [0x05] 10...1999 min StaggeringTime 120 min R/W
7 6 [0x06] 0...2 TemperatureAquastatLogic 0 R/W
8 7 [0x07] 0...4 HeaterMode 0 R/W
9 8 [0x08] 1-On,0-Off CommissioningMode 0 R/W
10 9 [0x09] 1-On,0-Off Heater1 - R
11 10 [0x0A] 1-On,0-Off Heater2 - R
12 11 [0x0B] 1-On,0-Off Heater3 - R
13 12 [0x0C] 1-On,0-Off Heater4 - R
14 13 [0x0D] 1-On,0-Off Heater5 - R
15 14 [0x0E] 1-On,0-Off Aquastat_Signal - R
16 15 [0x0F] 1-On,0-Off SettingMode - R
17 16 [0x10] 1-On,0-Off ShortTimeMode - R
18 17 [0x11] 1-On,0-Off StageringMode - R
19 18 [0x12] 1-On,0-Off StageringMode - R
20 19 [0x13] 1-On,0-Off OnOff 0-Off R/W
21 20 [0x14] 1-On,0-Off C_F_Scale 0-Off R/W
22 21 [0x15] 1-On,0-Off RestoreDefaults 0-Off R/W
23 22 [0x16] 1-On,0-Off GroundFault 0-Off R
24 23 [0x17] -40...35°C (-40...95°F) InternalTemperature(T3) 0-Off R
25 24 [0x18] 1-On,0-Off InternalHeater - R
26 25 [0x19] 0...99 SensorsError - R/W
0 – No error 1 – Internal sensor 2 – External sensor
The MODBUS Register No. X is addressed in the MODBUS Register Address (PDU) X-1.
All Registers are signed Integer 16 bit.
BACnet MSTP Baud rate: 9600, 19200, 38400, 76800 no parity, 8 data bits, 1 stop bit