Circutor line-M-4IO-R User manual

INSTRUCTION MANUAL
Expansion modules for the line-CVM and
line-EDS devices
(M239B01-03-20B)

2
line-M
Instruction Manual

3
Instruction Manual
line-M
SAFETY PRECAUTIONS
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a specific point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following should be
taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the
unit. In particular, handling with voltages applied may result in electric shock, which may cause death
or serious injury to personnel. Defective installation or maintenance may also lead to the risk of fire.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance in-
structions throughout the unit’s working life. Pay special attention to the installation standards of the
National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result
in injury or damage to the unit and/or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior notification.
DISCLAIMER
CIRCUTOR, SA reserves the right to make modifications to the device or the unit specifications set
out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device specifica-
tions and the most updated manuals.
www.circutor.com
CIRCUTOR, recommends using the original cables and accessories that are supplied
with the device.

4
line-M
Instruction Manual
CONTENTS
SAFETY PRECAUTIONS .........................................................................................................................................................3
DISCLAIMER ..........................................................................................................................................................................3
CONTENTS.............................................................................................................................................................................4
REVISION LOG .......................................................................................................................................................................7
SYMBOLS...............................................................................................................................................................................7
1 VERIFICATION UPON RECEPTION....................................................................................................................................8
2 PRODUCT DESCRIPTION .................................................................................................................................................8
3. INSTALLATION OF THE DEVICE ..................................................................................................................................... 10
3.1.- PRELIMINARY RECOMMENDATIONS ...................................................................................................................... 10
3.2.- INSTALLATION ........................................................................................................................................................11
3.3.- PANEL ADAPTER 72 x 72 mm................................................................................................................................ 12
4. LINEM4IOR ............................................................................................................................................................... 14
4.1.- DEVICE TERMINALS ............................................................................................................................................... 14
4.2.- CONNECTION DIAGRAM ........................................................................................................................................ 15
4.3 .- LED INDICATORS................................................................................................................................................... 16
4.4.- CONFIGURATION line-M-4IO-R ............................................................................................................................ 17
4.4.1.- CONFIGURATION OF DIGITAL INPUTS 1 ... 4 ................................................................................................... 18
4.4.2.- CONFIGURATION OF RELAY OUTPUTS 1 ... 4..................................................................................................20
4.5.- MODBUS MEMORY MAP line-M-4IO-R.................................................................................................................29
4.5.1.- INPUT AND OUTPUT STATUS .........................................................................................................................29
4.5.2.- PULSE METERS .............................................................................................................................................29
4.5.3.- ALARMS .........................................................................................................................................................30
4.5.4.- DEVICE CONFIGURATION VARIABLES ............................................................................................................30
4.6.- TECHNICAL FEATURES: line-M-4IO-R...................................................................................................................36
5 . LINEM4IOT .............................................................................................................................................................38
5.1.- DEVICE TERMINALS ...............................................................................................................................................38
5.2.- CONNECTION DIAGRAM ........................................................................................................................................39
5.3 .- LED INDICATORS...................................................................................................................................................40
5.4.- CONFIGURATION line-M-4IO-T ............................................................................................................................ 41
5.4.1.- CONFIGURATION OF DIGITAL INPUTS 1 ... 4 ...................................................................................................42
5.4.2.- CONFIGURATION OF TRANSISTOR OUTPUTS 1 ... 4 .......................................................................................42
5.5.- MODBUS MEMORY MAP line-M-4IO-T .................................................................................................................42
5.5.1.- INPUT AND OUTPUT STATUS .........................................................................................................................42
5.5.2.- PULSE METERS ..............................................................................................................................................42
5.5.3.- ALARMS .........................................................................................................................................................42
5.5.4.- DEVICE CONFIGURATION VARIABLES ............................................................................................................42
5.6.- TECHNICAL FEATURES: line-M-4IO-T ...................................................................................................................43
6 . LINEM4IOA..............................................................................................................................................................44
6.1.- DEVICE TERMINALS ...............................................................................................................................................44
6.2.- CONNECTION DIAGRAM ........................................................................................................................................45
6.3 .- LED INDICATORS...................................................................................................................................................45
6.4.- CONFIGURATION Line-M-410-A ........................................................................................................................... 47
6.4.1.- CONFIGURATION OF ANALOGUE INPUTS 1 ... 4..............................................................................................48
6.4.2.- CONFIGURATION OF ANALOGUE OUTPUTS 1 ... 4..........................................................................................50
6.5.- MODBUS MEMORY MAP line-M-4IO-A ................................................................................................................. 51
6.5.1.- ANALOGUE INPUT........................................................................................................................................... 51
6.5.2.- DEVICE CONFIGURATION VARIABLES ............................................................................................................ 51
6.6.- TECHNICAL FEATURES: line-M-4IO-A...................................................................................................................55
7. LINEM4IORV .............................................................................................................................................................57
7.1.- DEVICE TERMINALS................................................................................................................................................57
7.2.- CONNECTION DIAGRAM.........................................................................................................................................58
7.3 .- LED INDICATORS ...................................................................................................................................................59
7.4.- CONFIGURATION line-M-4IO-RV .......................................................................................................................... 60
7.4.1.- CONFIGURATION OF DIGITAL INPUTS 1 ... 4.................................................................................................... 61
7.4.2.- CONFIGURATION OF RELAY OUTPUTS 1 ... 4 .................................................................................................. 61
7.5.- MODBUS MEMORY MAP Line-M-410-RV............................................................................................................. 61
7.5.1.- INPUT AND OUTPUT STATUS ......................................................................................................................... 61
7.5.2.- ALARMS ......................................................................................................................................................... 61
7.5.3.- DEVICE CONFIGURATION VARIABLES............................................................................................................. 61

5
Instruction Manual
line-M
7.6.- TECHNICAL FEATURES: Line-M-410-RV ...............................................................................................................62
8. LINEMEXTPS............................................................................................................................................................64
8.1.- INSTALLATION ........................................................................................................................................................64
8.2.- DEVICE TERMINALS................................................................................................................................................65
8.3.- CONNECTION DIAGRAM .........................................................................................................................................65
8.3.1.- MAXIMUM CONNECTION.................................................................................................................................65
8.3.2.- MULTIPLE CONNECTION Line-M-EXT-PS ..................................................................................................... 66
8.4.- LED INDICATORS .................................................................................................................................................. 66
8.5.- TECHNICAL FEATURES: Line-M-EXT-PS ..............................................................................................................67
9. LINEM3G ................................................................................................................................................................... 68
9.1.- INSTALLATION OF THE SIM CARD......................................................................................................................... 68
9.2.- LED INDICATORS................................................................................................................................................... 69
9.3.- COMMUNICATIONS ................................................................................................................................................70
9.3.1.- USAGE ENVIRONMENT AND HEALTH ..............................................................................................................70
9.3.2.- 3G COMMUNICATIONS ....................................................................................................................................70
9.4.- TECHNICAL FEATURES: line-M-3G........................................................................................................................ 71
10. LINETCPRS1 ...............................................................................................................................................................73
10.1.- INSTALLATION......................................................................................................................................................73
10.2.- DEVICE TERMINALS .............................................................................................................................................73
10.3.- LED INDICATORS..................................................................................................................................................74
10.4.- COMMUNICATIONS ..............................................................................................................................................75
10.4.1.- USAGE ENVIRONMENT AND HEALTH ............................................................................................................75
10.4.2.- Wi-Fi COMMUNICATIONS ..............................................................................................................................75
10.4.3.- Bluetooth® COMMUNICATIONS....................................................................................................................75
10.4.4.- CONFIGURATION WEBSITE ............................................................................................................................75
10.4.5.- MOBILE APP..................................................................................................................................................78
10.5.- TECHNICAL FEATURES: line-TCPRS1 ..................................................................................................................79
11. LINEM20I .................................................................................................................................................................. 81
11.1.- INSTALLATION....................................................................................................................................................... 81
11.2.- DEVICE TERMINALS.............................................................................................................................................. 81
11.3.- CONNECTION DIAGRAM........................................................................................................................................82
11.4.- LED INDICATORS.................................................................................................................................................. 83
11.5.- MODBUS MEMORY MAP...................................................................................................................................... 83
11.5.1.- DIGITAL INPUTS ........................................................................................................................................... 83
11.5.2.- PULSE METERS .............................................................................................................................................84
11.5.3.- OTHER DEVICE PARAMETERS ...................................................................................................................... 85
11.5.4.- DEVICE CONFIGURATION VARIABLES .......................................................................................................... 85
11.6.- TECHNICAL FEATURES: line-M-20I.................................................................................................................... 86
12. LINELM20ITCP KIT .................................................................................................................................................. 88
12.1.- INSTALLATION ..................................................................................................................................................... 88
12.2.- DEVICE TERMINALS ............................................................................................................................................ 89
12.3.- CONNECTION DIAGRAM ...................................................................................................................................... 90
12.4.- LED INDICATORS .................................................................................................................................................. 91
12.5.- MODBUS MEMORY MAP ......................................................................................................................................92
12.6.- COMMUNICATIONS...............................................................................................................................................92
12.6.1.- USAGE ENVIRONMENT AND HEALTH.............................................................................................................92
12.6.2.- Wi-Fi COMMUNICATIONS...............................................................................................................................92
12.6.3.- Bluetooth® COMMUNICATIONS....................................................................................................................92
12.6.4.- CONFIGURATION WEBSITE ............................................................................................................................93
12.6.5.- MOBILE APP ..................................................................................................................................................93
12.7.- TECHNICAL FEATURES: line-LM20I-TCP kit........................................................................................................93
13. LINELM40ITCP KIT .................................................................................................................................................. 96
13.1.- INSTALLATION ..................................................................................................................................................... 96
13.2.- DEVICE TERMINALS .............................................................................................................................................97
13.3.- CONNECTION DIAGRAM ...................................................................................................................................... 98
13.4.- LED INDICATORS ................................................................................................................................................. 99
13.5.- MODBUS MEMORY MAP ....................................................................................................................................100
13.6.- COMMUNICATIONS.............................................................................................................................................100
13.6.1.- USAGE ENVIRONMENT AND HEALTH...........................................................................................................100
13.6.2.- Wi-Fi COMMUNICATIONS ............................................................................................................................100
13.6.3.- Bluetooth® COMMUNICATIONS..................................................................................................................100
13.6.4.- CONFIGURATION WEBSITE........................................................................................................................... 101

6
line-M
Instruction Manual
13.6.5.- MOBILE APP .................................................................................................................................................101
13.7.- TECHNICAL FEATURES: line-LM40I-TCP kit........................................................................................................101
14. MAINTENANCE AND TECHNICAL SERVICE................................................................................................................ 104
15 . GUARANTEE.............................................................................................................................................................. 104
16. CE CERTIFICATE ........................................................................................................................................................ 105
ANNEX A. CONFIGURATION MENUS................................................................................................................................108
A.1.- line-M-4IO-R, line-M-4IO-T and line-M-4IO-RV................................................................................................108
A.2.- line-M-4IO-A........................................................................................................................................................110

7
Instruction Manual
line-M
REVISION LOG
Table 1: Revision log.
Date Revision Description
03/20 M239B01-03-19A First Version
06/20 M239B01-03-20A
Changes in the following sections:
2.- 3.2.- 4.2.- 4.4.1.1. - 4.5.4.1.- 4.6.- 5.2.- 5.6.- 6.6.- 7.2.- 7.6.-
9.- 10.- 11.- 14.
11/20 M239B01-03-20B Changes in the following sections:
2.- 9.4.- 10.- 10.2.- 10.3. - 10.4.5.- 11.- 11.1.- 12.- 13.
Note: The images of the devices are for illustrative purposes only and may differ from the original
device.
SYMBOLS
Table 2: Symbols.
Symbol Description
In accordance with the relevant European directive.
In accordance with the CMiM directive.
Device covered by European Directive 2012/19/EC. At the end of its useful life, do not leave the
device in a household refuse bin. Follow local regulations on electronic equipment recycling.
Direct current.
~Alternating current.

8
line-M
Instruction Manual
1 VERIFICATION UPON RECEPTION
Upon reception of the device check the following points:
a) The device meets the specifications described in your order.
b) The device has not suffered any damage during transport.
c) Perform an external visual inspection of the device prior to switching it on.
d) Check that it has been delivered with the following:
- An installation guide
- An expansion connector.
- 4 clamping clips.
If any problem is noticed upon reception, immediately contact the transport com-
pany and/or CIRCUTOR's after-sales service
2 PRODUCT DESCRIPTION
The line-CVM and line-EDS devices have expansion modules to increase their performance.
The expansion modules available are:
line-M-4IO-R, expansion module with 4 digital inputs and 4 relay outputs.
line-M-4IO-T expansion module, with 4 digital inputs and 4 transistor outputs.
line-M-4IO-A, expansion module with 4 analogue inputs and outputs.
line-M-4IO-RV, expansion module with 4 digital inputs (230 V~) and 4 relay outputs.
Line-M-EXT-PS, power adapter module.
line-M-3G, expansion module that adds 3G connectivity to line-EDS devices.
line-M-20I, hub with 20 digital inputs.
line-TCPRS1, RS-485/RS-232 to TCP/IP converter.
line-LM20I-TCP kit, hub with 20 digital inputs that includes an RS-485/RS-232 to TCP/IP con-
verter.
line-LM40I-TCP kit, hub with 40 digital inputs that includes an RS-485/RS-232 to TCP/IP con-
verter.
Each line-CVM or line-EDS device enables up to 2 expansion modules to be directly connected to their
right-hand side.(1)
line-EDS line-M line-M line-M line-M
line-CVM
Figure 1: Line-EDS and line CVM expansion module connection.
(1) Expansion module types: line-M-4IO-R, line-M-4IO-T, line-M-4IO-RV, line-M-4IO-A and line-TCPRS1.

9
Instruction Manual
line-M
The line-M-3G module can only be connected on the left side of line-EDS devices. If the line-EDS has
a line-M-3G connected to it, only 1 expansion module can be connected on its right side.
In installations with line-EDS devices a total of up to seven devices may be connected to their right-
hand side.
line-EDS line-M line-M line-CVM line-M line-M line-CVM line-CVM
Figure 2: Typical installation of a line-EDS with 7 devices.
Note: An installation may only be fitted with one line-EDS device.
Note: In installations without line-EDS devices only one line-CVM may be installed.
Note: All line-EDS or line-CVM must be connected to the auxiliary power supply.

10
line-M
Instruction Manual
3. INSTALLATION OF THE DEVICE
3.1.- PRELIMINARY RECOMMENDATIONS
In order to use the device safely, personnel operating it must follow the safety meas-
ures that comply with the standards of the country where it is to be installed; operators
must wear the required personal protective equipment (rubber gloves, approved facial
protection and flame-resistant clothing) to prevent injuries from electric shock or arcs
caused by exposure to current-carrying conductors, and they must heed the various
warnings indicated in this instruction manual.
The line-M device must be installed by authorised, qualified personnel.
The power supply plug must be disconnected and measurement systems switched off before handling,
altering the connections or replacing the device. It is dangerous to handle the device while it is pow-
ered.
Cables must always be kept in perfect condition to avoid accidents or injury to personnel or installa-
tions.
Restrict the operation of the device to the specified measurement category, voltage or current values.
The manufacturer of the device is not responsible for any damage resulting from failure by the user
or installer to heed the warnings and/or recommendations set out in this manual, nor for damage
resulting from the use of non-original products or accessories or those made by other manufacturers.
Do not use the device to take any measurements if an anomaly or malfunction is detected.
Check the surrounding environment before starting to take measurements. Do not take any measure-
ments in hazardous or explosive environments.
Before carrying out maintenance, repair or handling of any of the device's connections,
the device must be disconnected from all power sources, both from the device's own
power supply and the measurement's.
Contact the after-sales service if you detect that the device is not working properly.

11
Instruction Manual
line-M
3.2.- INSTALLATION
When the device is on, its terminals, opening covers or removing elements may ex-
pose the user to parts that are hazardous to touch. Do not use the device until it is
fully installed.
The device must be installed inside electric panel or enclosure, with DIN rail mounting (IEC 60715).
Before installing the expansion module, the line-CVM or line-EDS devices must be
disconnected from all power supplies, both the device's power supply itself and the
measurement's.
The line-M-3G module can only be connected on the left side of the line-EDS device.
The line-CVM and line-EDS devices may only have 2 expansion modules connected
to their right-hand side.
If the line-EDS has a line-M-3G connected to it, only 1 expansion module can be
connected on its right side.
See "2. PRODUCT DESCRIPTION".
The steps to follow to connect the expansion modules are:
1.- Using a flat head screwdriver, remove the expansion connector's protective covers located on the
side of the devices, (Figure 3).
line-CVM-D32
Figure 3: Installation step 1.
2.- Insert the expansion connector and fastening clips into one of the devices (Figure 4).

12
line-M
Instruction Manual
line-CVM-D32
Figure 4: Installation step 2.
3 .- Connect both devices and fasten them by pushing the front clips down (Figure 5).
line-CVM-D32
Figure 5: Installation step 3.
3.3.- PANEL ADAPTER 72 x 72 mm
Note: The panel adapter 72 x 72 mm is a separately sold accessory.
CIRCUTOR has a panel adapter for the line-M expansion modules for their installation on 72 x 72 mm
panels.
The Figure 6 illustrates how the panel adapter connects to a line-M.
Before installing the adapter, the device must be disconnected from all power and
measurement supplies.

13
Instruction Manual
line-M
Figure 6: Installation of the panel adapter.
Table 3: Technical characteristics of the Panel Adapter.
Technical Specifications
Protection degree IP40
Enclosure Self-extinguishing V0 plastic
68 mm
68 mm
Figure 7: Cut in the panel.

14
line-M
Instruction Manual
4. line-M-4IO-R
The line-M-4IO-R expansion module has 4 digital inputs and 4 relay outputs.
4.1.- DEVICE TERMINALS
10
9
8
7
12
11
3
4
5
6
1
2
22
21
20
19
24
23
Figure 8: Line-M-4IO-R terminals: Upper - Lower.
Table 4: List of line-M-4IO-R terminals.
Device terminals
1: C, Common digital inputs 10: NO, Relay Output 1 (NO)
2: 1, Digital input 1 11: C, Relay output 1 (Common)
3: 2, Digital input 2 12: NC, Relay output 1 (NC)
4: 3, Digital input 3 19: NO, Relay output 4 (NO)
5: 4, Digital input 4 20: C, Relay output 4 (Common)
6: Vcc, + 12V 21: NC, Relay output 4 (NC)
7: NO, Relay output 2 (NO) 22: NO, Relay output 3 (NO)
8: C, Relay output 2 (Common) 23: C, Relay output 3 (Common)
9: NC, Relay output 2 (NC) 24: NC, Relay output 3 (NC)

15
Instruction Manual
line-M
4.2.- CONNECTION DIAGRAM
Enabling digital inputs with the device’s
internal source (+12 V)
Enabling digital inputs with an external
source (+24 V)
1
line-M-4IO-R
1
2
3
4
1
2
3
4
IN OUT
6 12
24
19
Relé 1
Relay 1
Relé 2
Relay 2
Relé 4
Relay 4
Relé 3
Relay 3
+12 V
3k
Entradas digitales
Digital inputs
1 2 3 4
C
1
line-M-4IO-R
1
2
3
4
1
2
3
4
IN OUT
6 12
24
19
Relé 1
Relay 1
Relé 2
Relay 2
Relé 4
Relay 4
Relé 3
Relay 3
+12 V
3k
Entradas digitales
Digital inputs
1 2 3 4
C
24 V
+
-
Figure 9: Line-M-4IO-R connection diagram.

16
line-M
Instruction Manual
4.3 .- LED INDICATORS
line-M-4IO-R
CPU
OUT 1
OUT 2
OUT 3
OUT 4
IN 1
IN 2
IN 3
IN 4
1
2
3
4
1
2
3
4
IN OUT
Figure 10: LEDs: line-M-4IO-R.
The line-M-4IO-R have 9 indicating LEDs:
CPU, Indicates device status:
Table 5: CPU LED.
LED Description
CPU Flashing:
White: Indicates that the device is powered
IN x, Indicates digital input x status:
Table 6: Led IN x.
LED Description
IN x On:
Green: Indicates activated input
OUT x, Indicates relay output x status:
Table 7: LED OUT x.
LED Description
OUT x On:
Red: Indicates activated output

17
Instruction Manual
line-M
4.4.- CONFIGURATION line-M-4IO-R
Configuration via display of the line-M-4IO-R is carried out via line-CVM to which it is connected.
To access the configuration menu, hold down (>2s) key .
AVG 230.00 V
5.00
50.00
1.00
AVG
LIII
INST
A
Hz
cos
T1
PRIMARY VT
V
1.0
1.00
SECONDARY VT
SETUP
V
PROG OUT1
PROG OUT2
MEASURE
CLOCK
PROG
kgCO2
PROG
SETUP SLOT1
MODE
IMPULSE
IN1
NAME
D IN1
SETUP SLOT1
MODE
IMPULSE
IN1
NAME
D IN2
SETUP SLOT1
MODE
IMPULSE
IN1
NAME
D IN3
SETUP SLOT1
MODE
IMPULSE
IN1
NAME
D IN4
SETUP SLOT1
VARIABLE
1 V1
D OUT1
SETUP SLOT1
VARIABLE
1 V1
D OUT2
PROG
SLOT1
VARIABLE
1 V1
D OUT3
PROG OUT1
SETUP SLOT1
VARIABLE
1 V1
D OUT4
VARIABLE
VARIABLE
SETUP
MEASURE, Measurement parameters
D IN1, Digital Input 1
D IN2, Digital Input 2
D IN3, Digital Input 3
D IN4, Digital Input 4
D OUT1, Relay output 1
D OUT2, Relay output 2
D OUT3, Relay output 3
D OUT4, Relay output 4
Expansion module line-M-4IO-R
Figure 11: Configuration menu.

18
line-M
Instruction Manual
Note: SLOT1 is the expansion module nearest line-CVM, SLOT2 is the following expansion module.
To exit the configuration menu, hold down (>2s) key .
4.4.1.- CONFIGURATION OF DIGITAL INPUTS 1 ... 4
Note: Digital input x configuration is identified by the literal D INx at the bottom centre of the display.
4.4.1.1.- Mode and name of digital input x
The operating mode and name of digital input x are configured on this screen.
SETUP SLOT1
MODE
IMPULSE
IN1
NAME
D IN1
Hold down key to set operating mode (MODE).
Use keys and to skip through the different options:
IMPULSE, The digital input functions as a pulse input.
STATUS, Functions as a status input
TARIFF, It enables selection of tariff.
Note: The option TARIFF is only available for Digital inputs 1 and 2.
Note: To select the TARIFF, digital inputs 1 and 2 are needed simultaneously.
Note: If 2 modules are configured in the TARIFF option, the device will apply the tariff set in the second
module.
Table 8: Tariff selection.
D IN2 D IN1
Tariff 1 0 0
Tariff 2 0 1
Tariff 3 1 0
Tariff 4 1 1
Hold down key to set input name (NAME).
Use keys and to modify the digit's value.
Press key to skip through the digits.
To validate the option, hold down key .
Use key to skip to the next programming point.

19
Instruction Manual
line-M
4.4.1.2.- Units and energy per pulse
Note: Screen visible if the selected operating mode is a pulse input, IMPULSE.
This screen enables unit and energy per pulse configuration.
SETUP SLOT1
UNITS
kWh
1
WEIGHT
D IN1
Hold down key to set the units (UNITS).
Hold down key to set the energy per pulse (WEIGHT).
Use keys and to modify the digit's value.
Press key to skip through the digits.
To validate the option, hold down key .
Use key to skip to the next programming point.
4.4.1.3.- Decimals
Note: Screen visible if the selected operating mode is a pulse input, IMPULSE.
This screen enables decimal number configuration.
SETUP SLOT1
DECIMALS
0
D IN1
Hold down key to set number of decimals (DECIMALS).
Use keys and to modify the digit's value.
To validate the option, hold down key .
No. of decimals:
Minimum value: 0.
Maximum value: 9.
Use key to skip to the next programming point.

20
line-M
Instruction Manual
4.4.1.4.- Input signal logic
Note: Screen visible if the selected operating mode is a pulse input, STATUS.
This screen enables configuration of input signal operating logic.
SETUP SLOT1
INPUT LOGIC
POSITIVE
D IN1
Hold down key to set the operating logic (INPUT LOGIC).
Use keys and to skip through the different options:
POSITIVE, Positive logic, a high signal input shows 1 and a low signal input shows 0.
NEGATIVE, Negative logic, a high signal input shows 0 and a low signal input shows 1.
To validate the option, hold down key .
Use key to skip to the next programming point.
4.4.2.- CONFIGURATION OF RELAY OUTPUTS 1 ... 4
Note: Configuration of relay output x is shown by the literal D OUTx at the bottom centre of the display.
4.4.2.1.- Variable
This screen enables configuration of the relay output variable (VARIABLE).
SETUP SLOT1
VARIABLE
D OUT1
1 V1
Hold down key to enter programming mode.
Use keys and to modify the digit's value.
Press key to skip through the digits.
The codes for the variables are shown in Table 9, Table 10, Table 11 and Table 12.
To validate the option, hold down key .
Use key to skip to the next programming point.
This manual suits for next models
9
Table of contents
Other Circutor Control Unit manuals
Popular Control Unit manuals by other brands

Kubic
Kubic CA15 manual

oventrop
oventrop Regudis W Installation and operating instructions

Whelen Engineering Company
Whelen Engineering Company CenCom Core-R CEM4HC installation guide

Elatec
Elatec TWN4 Slim LEGIC user manual

Inel
Inel ST-01R Instructions for installation and use

Sonance
Sonance VC60S installation instructions