manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cleveland Controls
  6. •
  7. Switch
  8. •
  9. Cleveland Controls AFS-460-136 User manual

Cleveland Controls AFS-460-136 User manual

Bulletin LT-AFS-460-136-07
Cleveland Controls
1111 Brookpark Rd
Cleveland OH 44109
Tel: 216-398-0330
Fax: 216-398-8558
Email:saleshvac@clevelandcontrols
.com
Web page: http://www.clevelandcontrols.com
Are you
reading a FAX
or a COPY of this
bulletin? DOWNLOAD
the full-color PDF ver-
sion of this and other
literature at our
website!
(Figure 1)
APPLICATION
The Model AFS-460–136 is a general pur-
pose airow proving switch designed for
120 VAC HVAC and Energy Management
applications where a manual reset switch
with DPDT contacts is desirable. It may be
used to sense positive, negative, or differ-
ential air pressure.
GENERAL DESCRIPTION &
OPERATION
The plated housing contains a diaphragm, a
calibration spring, a snap-acting switch with
manual reset button, and a dpdt relay.
The sample connections located on each
side of the diaphragm accept .25" OD tub-
ing via the integral compression ferrule and
nut.
An enclosure cover guards against acci-
dental contact with the live switch terminal
screws and the set point adjusting screw.
The enclosure cover will accept a 0.5" con-
duit connection. The manual reset button is
located on the top surface of the enclosure
cover.
MOUNTING (SEE FIGURE 1)
Select a mounting location which is free
from vibration. The AFS-460–136 must be
mounted with the diaphragm in any vertical
plane in order to obtain the lowest specied
operating set point. Avoid mounting with the
(Figure 2)
sample line connections in the "up" position.
Surface mount via the two 3/16" diameter
holes in the integral mounting bracket. The
mounting holes are 3-7/8" apart.
AIR SAMPLING
CONNECTION
(SEE FIGURE 2)
The AFS-460–136 is designed to accept
rm-wall sample lines of ¼" OD tubing by
means of ferrule and nut compression con-
nections. An optional ¼" adapter, suitable
for slip-on exible tubing is available. For
sample lines of up to 10 feet, ¼" OD tubing
is acceptable. For lines up to 20 feet, use ¼"
ID tubing. For lines up to 60 feet, use ½" ID
tubing. Locate the sampling probe a mini-
mum of 1.5 duct diameters downstream from
the air source. Install the sampling probe as
close to the center of the airstream as pos-
sible. Refer to Figure 2 to identify the high
pressure inlet (H), and the low pressure inlet
(L). Select one of the ve application options
listed below, and connect the sample lines
as recommended.
POSITIVE PRESSURE ONLY: Connect
the sample line to inlet H; inlet L remains
open to the atmosphere.
NEGATIVE PRESSURE ONLY: Connect
the sample line to inlet L; inlet H remains
open to the atmosphere.
TWO NEGATIVE SAMPLES: Connect the
higher negative sample to inlet L. Connect
the lower negative sample to inlet H.
TWO POSITIVE SAMPLES: Connect the
higher positive sample to inlet H. Connect
the lower positive sample to inlet L.
ONE POSITIVE AND ONE NEGATIVE
SAMPLE: Connect the positive sample
to inlet H. Connect the negative sample
to inlet L.
Model
AFS-460-136
Manual Reset DPDT Air Pressure Sensing Switch for 120 VAC Applications
SPECIFICATIONS
Model AFS–460–136 Air Pressure
Sensing Switch
with manual reset feature,
DPDT contact arrangement,
for 120 VAC applications.
Sample Media: Air or combustion
by-products that will not degrade
silicone.
Mounting Position (in order
to meet lowest operating
specications): Diaphragm in any
vertical plane.
Field Adjustable Range:
0.40 ± .06"w.c. to 12.0"w.c.
Maximum Pressure:
0.5 psi (0.03 bar)
Operating Temperature Range:
-40 to 180F (-40 to 82C)
Electrical Rating:
4.5 VA @ 120 V AC, 50/60 Hz.
Contacts: DPDT, 2 form-C
rated 8 amp @ 250 V AC.
Electrical Connections:
Screw terminals.
Sample Line Connections:
Ferrule and nut compression type
connectors will accept .25" OD rigid
tubing.
Shipping Weight: 1.2 lbs.
Agency Approvals: pending
ELECTRICAL CONNECTIONS
(SEE FIGURE 3)
Before pressure is applied to the diaphragm,
the snap switch contacts will be in the nor-
mally closed (NC) position. As differential
pressure rises above the eld adjustable set
point, the snap switch opens, de-energizing
the coil on the slave relay, which activates
the DPDT contacts. An LED indicates that
the snap switch exceeds differential set
point. It remains lit until the manual reset
push button is depressed.
FIELD ADJUSTMENT
The AFS-460–136 Manual Reset Air Switch
has an adjustment range of 0.40 to 12.0"
w.c., ±.06" w.c. To adjust the set point:
Turn the adjusting screw counterclockwise
until motion has stopped. Next, turn the ad-
justing screw 4 complete turns in a clockwise
direction to engage the spring. From this
point, the next ten turns will be used for the
actual calibration. Each full turn represents
approximately 1.16" w.c.
Please note: To properly calibrate an Air
Switch, a digital manometer or other mea-
suring device should be used to conrm the
actual set point.
(Figure 3) Shown in "on shelf" condition:
no power and no differential pressure
applied.

Other Cleveland Controls Switch manuals

Cleveland Controls RSS-495-011 Series User manual

Cleveland Controls

Cleveland Controls RSS-495-011 Series User manual

Cleveland Controls AFS–460 User manual

Cleveland Controls

Cleveland Controls AFS–460 User manual

Cleveland Controls AFS–442 User manual

Cleveland Controls

Cleveland Controls AFS–442 User manual

Cleveland Controls AFS-951 User manual

Cleveland Controls

Cleveland Controls AFS-951 User manual

Cleveland Controls FS-751-112 User manual

Cleveland Controls

Cleveland Controls FS-751-112 User manual

Cleveland Controls AFS-961 Operating and installation instructions

Cleveland Controls

Cleveland Controls AFS-961 Operating and installation instructions

Cleveland Controls AFS-951-1 User manual

Cleveland Controls

Cleveland Controls AFS-951-1 User manual

Cleveland Controls AFS-460-137 User manual

Cleveland Controls

Cleveland Controls AFS-460-137 User manual

Popular Switch manuals by other brands

Brightlink BL-5X1-4K operating instructions

Brightlink

Brightlink BL-5X1-4K operating instructions

Generac Power Systems RTG24SHA1 owner's manual

Generac Power Systems

Generac Power Systems RTG24SHA1 owner's manual

Alcatel OS6850-P48 manual

Alcatel

Alcatel OS6850-P48 manual

Kramer VP-440X user manual

Kramer

Kramer VP-440X user manual

AXIOMTEK TEN100 Series user manual

AXIOMTEK

AXIOMTEK TEN100 Series user manual

ADTRAN NetVanta 1560-08-65W quick start

ADTRAN

ADTRAN NetVanta 1560-08-65W quick start

Renkforce RF-4821051 operating instructions

Renkforce

Renkforce RF-4821051 operating instructions

MBA Instruments MBA888 Installation and operation instructions

MBA Instruments

MBA Instruments MBA888 Installation and operation instructions

HPE FlexNetwork 5130 EI Series Compliance and Safety Manual

HPE

HPE FlexNetwork 5130 EI Series Compliance and Safety Manual

Cisco Nexus 2000 Series Hardware installation guide

Cisco

Cisco Nexus 2000 Series Hardware installation guide

LevelOne FGP-1000 quick start guide

LevelOne

LevelOne FGP-1000 quick start guide

Giovenzana FGR2 instruction manual

Giovenzana

Giovenzana FGR2 instruction manual

ATEN Master View CS-1754 user manual

ATEN

ATEN Master View CS-1754 user manual

Avocent SwitchView IP 1020 Installer/user guide

Avocent

Avocent SwitchView IP 1020 Installer/user guide

ADTRAN TRACER 1280050L1 quick start guide

ADTRAN

ADTRAN TRACER 1280050L1 quick start guide

KROHNE ARV52 Handbook

KROHNE

KROHNE ARV52 Handbook

Sierra Video 7272HD-3G user manual

Sierra Video

Sierra Video 7272HD-3G user manual

Siemens NXAirS manual

Siemens

Siemens NXAirS manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.