ClimaCheck R560 User manual

R560 Hardware Manual –2021-01-13 Page 2 of 9
Table of Contents
1Technical data ............................................................................................................... 3
1.1 Power supply ........................................................................................................... 3
1.2 Analog inputs........................................................................................................... 3
2Configuration ................................................................................................................ 4
2.1 Change Modbus address............................................................................................ 4
2.2 Change Analog input mode ........................................................................................ 6
2.3 Configuration on PA Pro II ......................................................................................... 6
3ClimaCheck Onsite portable version ................................................................................. 8
4Electrical wiring diagram................................................................................................. 9

R560 Hardware Manual –2021-01-13 Page 3 of 9
1Technical data
This section covers the basic technical data of the R560 unit, see the product sheet for more
details.
1.1 Power supply
In ClimaCheck onsite systems, the R560 unit is supplied with 24V DC via the serial communication
cable connected to the panel. In ClimaCheck online installations, the R560 unit is supplied with 24
VDC from the common power supply but it can handle 10-35 V DC.
1.2 Analog inputs
There are 8 analog inputs on the unit, configurable for temperature sensors (Pt1000), pressure
transducers or other sensors with voltage (0-10V), current (4-20mA), or resistance signals.

R560 Hardware Manual –2021-01-13 Page 4 of 9
2Configuration
This section explains how to change Modbus address and analog input configuration between 4-
20mA and V/PT input. In most cases the R560 modules will be delivered pre-configured to fit the
system, but changes in the setup compared to the order may cause a need for change of these
settings.
The ClimaCheck PA Pro III configurator is used to set scale and offset for the analog inputs, to
change the inputs to PT1000 or to configure additional R560 modules. See the PA Pro III hardware
manual for more details.
2.1 Change Modbus address
Modbus address is set with DIP switches marked ADR on the top left side of the unit, see Figure 1.
Address is entered as binary where DIP8 = bit 0, switches increase their bit weight from right to
left. Default address for module 1 is 00010100 (20), module 2 is 00010101 (21) and so on, see
Table 1, Figure 1 and Figure 2 below.
RS485 bus termination is activated with the BUS END switch. The last device in the Modbus chain
should have BUS END ON, all other R560 units should be set to OFF.
Figure 1 - R560 module
Figure 2, Modbus address calculation

R560 Hardware Manual –2021-01-13 Page 5 of 9
Table 1, Modbus address dip switch

R560 Hardware Manual –2021-01-13 Page 6 of 9
2.2 Change Analog input mode
DIP switches for the analog inputs can be found in between the AI terminals on the bottom side of
the device, see Figure 1. Default setting is 0-10V and PT1000 (DIP switch 1-8 OFF). In this mode
each input is configured on the ClimaCheck Online server or in the PA Pro III configurator, see PA
Pro III Hardware manual for details. For current measurement (0-20mA) the particular DIP switch
is changed to ON, see Table 2 and Figure 3.
Table 2, Input mode Dip switch, all set to 0-10V
Figure 3, Analog input DIP switch, AI_5 set to current measurement
2.3 Configuration on PA Pro II
It is possible to use the R560 with PA Pro II. To configure, the R560 script needs to be uploaded to
the PA Pro. Contact ClimaCheck support for more information. With the script in place, follow the
steps below:
-Connect the PA Pro to your computer
-Open a web browser and enter http://169.254.1.1
-The default user name is “config” and password “ef56” (default)
-Select Settings -> Advanced - > External Units
-Select a unit
-Ensure the correct type of unit is selected R560
-Check Activate and click OK.
-Select the same unit again
-Enter the address and the type for each input. Check Table 3 for more information. Input
type 10 is selected in the example of Figure 4.
-Select the telegram update times: 1 minute (or longer) for Set input type and 10 seconds
for Read all
-Click OK
-Continue the setup process by connecting the external channels and activating them

R560 Hardware Manual –2021-01-13 Page 7 of 9
Figure 4, R560 configuration in PA Pro II
The configuration of each input type can be done in the PA Pro II. The correct type needs to be
entered to ensure correct values with applicable scale and offset.
Table 3, input types for configuration in PA Pro II
Input type
Description
10
PT1000 with an offset of 0.35 K
20
Voltage, 0-10 V
21
5 Bar pressure transducer with 0-5V output
22
10 Bar pressure transducer with 0-5V output
23
35 Bar pressure transducer with 0-5V output
24
50 Bar pressure transducer with 0-5V output
25
150 Bar pressure transducer with 0-5V output
30
Resistance, 0-1600 Ω
40
Current, 4-20 mA (check section 2.2)
41
0-25 mm/s Vibration sensor with 4-20mA output
50
Resistance, 0-5000 Ω

R560 Hardware Manual –2021-01-13 Page 8 of 9
3ClimaCheck Onsite portable version
Each portable R560 has 8 tele plug inputs and 4 DIN 5D inputs to be used with the standard
PT1000 temperature sensors and pressure transducers. Inputs 3, 4, 7 and 8 are connected to tele
plug inputs and inputs 1,2,5 and 6 have both a tele plug and a DIN 5D each to be able to handle
both types of sensors, see electrical wiring diagram and Table 4. Note that it is not possible to use
an input for both PT1000 and pressure transducer
Table 4
AI
Available connection
1
Tele plug and DIN 5D
2
Tele plug and DIN 5D
3
Tele plug
4
Tele plug
5
Tele plug and DIN 5D
6
Tele plug and DIN 5D
7
Tele plug
8
Tele plug

R560 Hardware Manual –2021-01-13 Page 9 of 9
4Electrical wiring diagram
Table of contents