
Page 3
To avoid equipment damage, do not use these units as
a source of heating or cooling during the construction
process. The mechanical components and filters used
in these units quickly becomes clogged with
construction dirt and debris which may cause system
damage.
To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must
only be serviced by technicians which meet local, state
and federal proficiency requirements.
All refrigerant discharged from this unit must be
recovered without exception. Technicians must follow
industry accepted guidelines and all local, state and
federal statutes for the recovery and disposal of
refrigerants.
When a compressor is removed from this unit, system
refrigerant circuit oil will remain in the compressor.
To avoid leakage of compressor oil, the refrigerant
lines of the compressor must be sealed after it is
removed.
Storage
CAUTION: DO NOT store or install CS/CL units in
corrosive environments or in locations subject to
temperature or humidity extremes (e.g., attics,
garages, rooftops, etc.). Corrosive conditions and high
temperature or humidity can significantly reduce
performance, reliability, and service life. Always
move units in an upright position. Tilting units on
their sides may cause equipment damage.
Upon the arrival of the equipment at the job site, immedi-
ately store units in their shipping cartons in a clean, dry
area. Store units in an upright position at all times.
Stack units a maximum of 3 units high. Use pallets to
separate each layer of units. Do not remove equipment
from shipping cartons until equipment is required for
installation.
Unit Protection
Cover CS/CL units on the job site with either shipping
cartons, vinyl film, or an equivalent protective covering.
Cap the open ends of pipes stored on the job site. In areas
where painting, plastering, or the spraying of fireproof
material has not been completed, all due precautions
must be taken to avoid physical damage to the units and
GENERAL INFORMATION
Inspection
Upon receipt of shipment, carefully check the shipment
against the bill of lading. Verify all CS/CL units have
been received. Inspect each unit for damage. Be certain
the carrier makes proper notation on the delivery receipt
of all shortages and noticeable damage and he completes
a Carrier Inspection Report. Concealed damage not
discovered during unloading must be reported to the
carrier within fifteen (15) days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file
all necessary claims with the carrier. Notify the
ClimateMaster Traffic Department within fifteen (15)
days of receipt of all damaged shipments.
Introduction
ClimateMaster Console Air Conditioner Water Source
Heat Pump units are decentralized room terminals
designed for field connection to a closed-circuit piping
loop. They are offered in capacities ranging from 6,800
to 17,600 BTUH cooling and 8,500 to 21,000 BTUH
heating.
Units are typically installed in perimeter zones, usually
under windows. Supply air is discharged directly into the
conditioned space through discharge grills located in the
top of the unit.
contamination by foreign material. Physical damage and
contamination may prevent proper start-up and may
result in costly equipment clean-up.
Examine all pipes, fittings, and valves before installing
the system components. Remove any dirt found on these
components.
Pre-Installation
Installation, operation and maintenance instructions are
provided with each unit. Before unit start-up, read all
manuals and become familiar with the unit and its
operation. Thoroughly check out the system before
operation. Complete the inspections and instructions
listed below to prepare a CS/CL unit for installation.
1. Compare the electrical data on the unit nameplate
with ordering and shipping information to verify that
the correct unit has been shipped.
2. Keep both the chassis and cabinet covered with the
shipping carton until all plastering, painting, and
finish work is complete and it is time to install the
chassis and cabinet.
3. Verify that the refrigerant tubing is free of kinks or
dents, and that it does not touch other unit compo-
nents.
4. Inspect all electrical connections. Connections must
be clean and tight at the terminals.