
Page 3
Unit Protection
Cover Horizontal and Vertical units on the job site with
either shipping cartons, vinyl film, or an equivalent
protective covering. Cap the open ends of pipes stored on
the job site. In areas where painting, plastering, or the
spraying of fireproof material has not been completed, all
due precautions must be taken to avoid physical damage
to the units and contamination by foreign material.
Physical damage and contamination may prevent proper
start-up and may result in costly equipment clean-up.
Examine all pipes, fittings, and valves before installing
any of the system components. Remove any dirt found on
these components.
Pre-Installation
Installation, Operation and Maintenance (IOM)
instructions are provided with each unit. Before unit
start-up, read all manuals and become familiar with the
unit and its operation. Thoroughly check the system
before operation.
Prepare Horizontal and Vertical units for installation as
follows:
1. Compare the electrical data on the unit nameplate
with ordering and shipping information to verify the
correct unit has been shipped.
2. Keep both the chassis and the cabinet covered with
the shipping carton until installation is complete and
all plastering, painting, etc., is finished.
3. Verify refrigerant tubing is free of kinks or dents and
it does not touch other unit components.
4. Inspect all electrical connections. Connections must
be clean and tight at the terminals.
5. Loosen compressor bolts on units equipped with
compressor spring vibration isolation until the
compressor rides freely on the springs. Remove
shipping restraints. Note: HP/VP units are not
spring mounted, no futher action is required.
6. Some airflow patterns are field convertible. Contact
your local sales representative for specific
instructions.
To avoid equipment damage, DO NOT use these units
as a source of heating or cooling during the
construction process. The mechanical components
and filters used in these units will quickly become
clogged with construction dirt and debris which may
cause system damage.
Inspection
Upon receipt of shipment at the job site, carefully check
the shipment against the bill of lading. Make sure all
units have been received. Verify Hanger Brackets are
located inside the fan compartment of Horizontal Units.
Inspect the carton or crating of each unit, and inspect
each unit for damage. Assure that the carrier makes
proper notation of any shortages or damage on all copies
of the freight bill and he/she completes a Carrier
Inspection Report. Concealed damage not discovered
during unloading must be reported to the carrier within
15 days of receipt of shipment. Note: It is the
responsibility of the purchaser to file all necessary
claims with the carrier. Notify the ClimateMaster
Traffic Department of all damage within fifteen (15)
days of shipment.
Introduction
This Installation, Operation and Maintenance Manual is
for ClimateMaster Horizontal and Vertical Water Source
Heat Pump systems (HS/HL/HP & VS/VL/VP).
ClimateMaster Horizontal Water Source Heat Pump (HS/
HL/HP) units are designed for installation above a false
ceiling or in a ceiling plenum. Vertical (VS/VL/VP) units
are typically installed in a floor level closet or in a small
mechanical room. The installation site chosen for these
units must allow adequate clearance for maintenance and
servicing of the unit without its removal from the
installation location.
Refer to project submittal drawings for specific unit
technical data and wiring diagrams.
Storage
DO NOT store or install Horizontal and Vertical units
in corrosive environments or in locations subject to
temperature or humidity extremes (e.g., attics,
garages, rooftops, etc.). Corrosive conditions and high
temperature or humidity can significantly reduce
performance, reliability, and service life. Always
move units in an upright position. Tilting units on
their sides may cause equipment damage.
Upon the arrival of equipment at the job site,
immediately store units in their shipping cartons in a
clean, dry area. Store units in an upright position at all
times. Stack Horizontal units a maximum of 4 units high.
Stack vertical units a maximum of 3 units high. DO NOT
remove equipment from shipping cartons until
equipment is required for installation.
GENERALINFORMATION
▲CAUTION
!