General
Information
Page 17
1. Outdoor unit
2. Hydraulic module
3. Domestic hot water storage tank
4. Radiator
5. Water separator
6. Floor heating
7. Auxiliary heat source
If the unit selection is too small, additional heat is
provided.
8. Pipeline auxiliary electric heating
If the unit selection is too small, additional heat is
provided.
9. External circulating water pump
When the water resistance is greater than the head
provided by the internal machine, the pump shall be added
to the branch with excessive water resistance.
10. Backwater pump
Control the pump switch through the back-water
temperature-sensing package to keep hot water at any
time.
11. Mixing water pump
With the water mixing valve, lower the temperature of
the foor heating, and do not install it when there is no
radiator.
12. Return water temperature sensing bag
Control the operation of return water pump and keep hot
water available at any time.
13. Heating water supply main pipe temperature sensing
package
Work with external heat source 7 or 8.
14. Globe valve
Close water fow for maintenance.
NOTE: In addition to the outdoor unit and hydraulic module, other materials are prepared by users.
22-26 is an indispensable part of domestic hot water tank.
15. Electric three-way valve
Used for switching between heating and domestic hot
water mode, working with domestic hot water tank.
16. Filter
Water supply system,flter impurities.
17. Differential pressure make-up valve
Adjust the system water pressure to ensure that it is in the
normal working range.
18. Check valve
To prevent the internal machine water supply from fowing
back into the external heat source 7, this valve is not
needed for electric pipeline heating.
19. Electric two-way valve
It is used when there is cooling mode.
20. Mixing valve
Used with mixed water pump.
21. Differential pressure bypass valve
In the case of multiple branch water closure, bypass water
fow to ensure suffcient water fow to prevent water fow
failure.
22. Anode magnesium rod
Improve corrosion resistance, need to be replaced regularly.
23. Electric immersion heater
Used for auxiliary heating and sterilization.
24. Heating coil
Heat the water in the water tank to isolate the heating
water.
25. Temperature probe tube
Place a water tank temperature sensing package to control
the temperature of domestic hot water.
26. Sewage outlet
used for water tank cleaning.