IE-SNC-T2214-04 5
Analog output:
Range: from 0 to 10 V
Output load capability: min. 20 k
Output accuracy: ±(accuracy of value shown on LCD display + 0.06 % FS) hPa
Voltage output in case of error: approximately –0.1 V or >10.5 V
Recommended calibration interval: 1 year
Measuring interval and LCD display refresh: 2 s
Communication with computer:via USB port by means of USB communication
cable SP003 (option)
Protection: IP54
Operating conditions:
Operating temperature range: -30 to +80 °C, over +70 °C switch LCD display OFF
Operating humidity range: 0 to 100 %RH
Outer characteristics in accordance with Czech National Standard 33-2000-3:
normal environment with the specifications: AE1, AN1, BE1
Working position: communication cable is entering from the top side
Electromagnetic compatibility: complies EN 61326-1
Not allowed manipulations: It is not allowed to operate the device under other than
specified conditions in technical parameters. Devices are not designed for locations
with chemically aggressive environment. Do not use the device in an explosive
environment.
Storing conditions: temperature -30 to +80 °C,
humidity 0 to 100 %RH without condensation
Dimensions: see dimensional drawings
Weight: approximately 135 g
Material of the case: ASA
Procedure of modification of device adjustment:
•Device adjustment is performed by means of the optional SP003 communication cable,
connected to USB port of the PC.
•It is necessary to have installed configuration program TSensor on the PC. It is free to
download at www.cometsystem.com. During installation please take care about
installation of driver for USB communication cable.
•Connect SP003 communication cable to the PC. Installed USB driver detect connected
cable and create virtual COM port inside the PC.
•Unscrew four screws of the device lid a remove the lid. If device is already installed to
measuring system, disconnect leads from terminals.
•Connect SP003 communication cable to the device. Display must light up, or at least
must light up all symbols for one second (if LCD was switched OFF by program
before).
•Run installed TSensor program and select corresponding communication COM port
(as described above).
•When new setting is saved and finished, disconnect the cable from the device, connect
leads into its terminals and place the lid back to the device.