IE-SNC-T03(4)10-02 7
1 …Selection of communication protocol and setting of its parameters (transmitter address,
communication speed…). For entering numeric values use digits 0 to 9 and characters
„A“ to „F“ (upper case letters), transmitter address is entered always as two digits
hexadecimal number (no decimal, e.g. address 11 i.e. Bh must be entered as 0B).
2 …Setting of LCD display of the transmitter (display switched ON/OFF, selection of
displayed values)
8 …Setting communication to default value from manufacturer (Modbus, address 01h,
9600 Bd)
9 …End of setting
All changes in setting are continuously automatically stored.
•At the end open the Jumper and if needed, close the transmitter again with cover.
Description of communication protocols
Detailed description of each communication protocols including examples of
communication is available in individual document “Description of communication protocols of
Txxxx series” which is free to download at www.cometsystem.cz.
To change communication protocol use User’s software or proceed in accordance with
chapter „Setting of transmitter, selection of communication protocol“
Note: After switching ON the power of the transmitter it can last up to 2 s before the transmitter
starts to communicate and measure!
Modbus RTU
Control units communicate on master-slave principle in half-duplex operation. Only master
can send request and only addressed device responds. During sending of request no other slave
station should respond. During communication, data transfer proceeds in binary format. Each Byte
is sent as eight bit data word in format: 1 start bit, data word 8 bit (LSB first), 2 stop bits2, without
parity. Transmitter supports communication speed from 110Bd to 115200Bd.
Sent request and response have syntax: ADDRESS OF DEVICE – FUNCTION – Modbus CRC
Supported functions
03 (0x03): Reading of 16-bit registers (Read Holding Registers)
04 (0x04): Reading of 16-bit input gates (Read Input Registers)
16 (0x10): Setting of more 16-bit registers (Write Multiple Registers)
Jumper and button
Jumper and button are located next to connection terminals. If communication protocol
Modbus is selected the function of jumper and button is as follows:
•Jumper opened – transmitter memory is protected from writing, from transmitter side it is
only enabled to read measured value, writing to memory is disabled (no change of
transmitter address, communication speed and LCD setting is enabled)
•Jumper closed – writing to transmitter memory is enabled by means of User’s software
•Jumper closed and button pressed for longer than three seconds – causes restoring of
manufacturer setting of communication protocol, i.e. sets transmitter address to 01h and
communication speed to 9600Bd
2Transmitter sends two stop bits, for receive one stop bit is enough.