2 IE-SNC-T0211-01
Instruction manual for use of T0211 transmitter
Transmitter is designed for measurement of air temperature and relative humidity of air without
aggressive ingredients with computing one of the following values: dew point temperature, absolute
humidity, specific humidity, mixing ratio and specific enthalpy. Instrument is equipped with an
external humidity and temperature probe on a cable. The probe is a non-removable instrument part.
Measured and computed values are displayed on dual line LCD display. The first line displays
temperature. Value displayed on the second line is selectable among relative humidity and
computed value. It is also possible to display both readings with cyclic overwriting in 4 seconds
interval. It is possible to switch OFF the LCD at all. It is possible to assign measured or computed
value to output Uout1 or output Uout2. Both voltage outputs have common ground with power
source (GND terminal).
All transmitter setting is performed by means of the PC connected via the optional SP003
communication cable (not included in delivery). Program Tsensor for transmitter setting is available
to download free at www.cometsystem.cz. Program enables to assign each output measured value
(temperature, relative humidity, computed value) and its range. It is also possible to assign both
outputs to the same value (with the same range), if two evaluation devices are necessary to connect.
Transmitter setting before operation
Transmitter is set from the manufacturer to the following parameters:
value at output Uout1: relative humidity, range 0 - 10 V corresponds 0 to 100 % RH
value at output Uout2: temperature, range 0 - 10 V corresponds -30 to +105 °C
display: switched ON
value displayed at line 2: relative humidity only
Modification of the setting is possible to do by means of the PC using procedure described at
the end of this document.
Installation of the transmitter
Transmitter case with electronics is designed for wall mounting. It is NOT recommended to
use the probe for long time under condensation conditions. It could be the cause of water steam
condensation inside the sensor’s cover into water phase. This liquid phase stays inside sensor’s
cover and can’t escape from the cover easily. It can dramatically increase response time to relative
humidity change. If water condensation occurs for longer time it can cause sensor damage. Similar
effect can occur under water aerosol conditions. If this effect may occur, it is necessary to use the
probe at operation position with sensor cover downwards. Don’t connect transmitter while power
supply voltage is on. Interconnection terminals are accessible after unscrewing four screws and
removing the lid. Lace the cable through a gland at the case wall. Connect the cable to terminals
with respecting the signal polarity (see figure). Terminals are self-clamping and can be opened by a
suitable screwdriver. For the opening, insert the screwdriver to upper terminal hole and lever by
him. Do not remember to tighten glands and case lid with inserted packing after cables connecting.
It is necessary for warranting of protection IP65.
It is recommended to use shielded copper cable (e.g. SYKFY) with outside diameter of the
cable must be from 3.5 to 8 mm, maximal length 15m. The cable must be located at indoor rooms
(probe is not protected for outdoor use). The cable should not be led in parallel along power
cabling. Safety distance is up to 0.5 m otherwise undesirable induction of interference signals can
appear.